Cast Iron Condensing Boilers – Installation Manual
Cast Iron Condensing Boilers – Installation Manual
Figure 2 - Horizontal Air Intake and Venting for a Single Direct Vent System
Figure 3 - Horizontal Air Intake and Venting for Multiple Direct Vent Systems
1.5 FT [0.5 m] MINIMUM
DISTANCE FROM
INTAKE TO MAXIMUM
SNOW LINE.
COMBUSTION AIR
INTAKE TERMINAL
BANK
2 IN [50.8 mm] MINIMUM
BETWEEN TERMINALS
EXHAUST TERMINAL
BANK
AIOM-065_B
NOTES:
1. DIMENSIONS ARE IN INCHES (IN), FEET (FT), MILIMETERS [mm] OR
METERS [m] AS SHOWN.
PITCH PIPE DOWN
TOWARDS BOILER
1/4 IN/FT
[20 mm/m]
10 FT [3.1 m]
MINIMUM
TO ADJACENT
BUILDING
PITCH PIPE DOWN
TOWARDS TERMINAL
CAP 1/4 IN/FT
[20 mm/m]
EXHAUST
COMBUSTION AIR
1.5 FT [0.5 m] MINIMUM DISTANCE FROM
INTAKE TO MAXIMUM SNOW LINE.
"Y"
MI
NI
MUM
BETWEEN TERMINALS
"X"
MINIMUM
BETWEEN TERMINALS
@ CENTER LINE
REFER TO TABLE "Y"
FOR APPROVED VENT
TERMINATION AND
DIMENSIONAL DATA
NOTES:
1.
DIMENSIONS ARE IN INCHES (IN), FEET (FT), MILIMETERS [mm] OR
METERS [m] AS SHOWN.
WARNING: When running horizontal
combustion air and venting for single
or multiple units, exhaust and
combustion air terminals must be
installed on the same plane (outside
wall) in order to prevent pressure
differences due to prevailing winds.
In cold climates, double-wall or
insulated inlet pipe recommended to
prevent condensation.
Summary of Contents for KN Series
Page 45: ...45 Cast Iron Condensing Boilers Installation Manual Figure 24 KN6 10 16 20 26 30 and 40 ...
Page 46: ...46 Cast Iron Condensing Boilers Installation Manual Figure 25 KN6 10 16 20 26 30 and 40 ...
Page 47: ...47 Cast Iron Condensing Boilers Installation Manual Figure 26 Gas Train Drain Pan ...
Page 55: ...55 Cast Iron Condensing Boilers Installation Manual ...