![ATH KN-10 Control Manual Download Page 63](http://html.mh-extra.com/html/ath/kn-10/kn-10_control-manual_2998286063.webp)
HeatNet Control V3 1.x
Setpoint Source Messages
General Messages:
0-10V Setpoint
Settings are configured to allow a 0-10VDC signal to change setpoint.
4-20mA Setpoint
Settings are configured to allow a 4-20mA signal to change setpoint.
DHW Setpoint
The DHW sensor is controlling the setpoint for DHW heating.
Local Setpoint
Boiler is watching the Local Setpoint.
.
OA Setpoint
The Outside Air sensor is controlling the setpoint.
.
System DHW
Setpoint
A Member boiler is being controlled by a HeatNet Master – Reference
System Setpoint
Boiler is watching the System Setpoint from the HeatNet Master.
Air Switch (Blower)
If the ignition control closes its BLOWER relay, and the control does not see the PILOT relay close
within (2) minutes, this message will be displayed. This alarm protects the boiler from freeze ups
being caused by a blower bringing in cold outside air with no fire.
BLOWER, RPM
HIGH: (Ametek
Blower)
If the signal from the HeatNet control board to the Ametek blower exceeds the factory limits, or the
blower “runs away” (excessive speed), this message will be displayed. With this event, the HeatNet
control will lockout the boiler and the boiler will require a manual reset to restart. Operation of the
blower above the boiler’s maximum blower rpm setting could over fire the boiler.
Blower Signal not
Received, Retrying
The Boiler attempted to start by sending the J5 FLAME SAFE ALARM signal to the Ignition Control. The
control then waited for the Blower signal from the Ignition Control and timed out. The Blow out
switch (air box safety relief) may have opened.
Call For Service
When theH-Net control issues a start signal to the ignition control and doesn't receive a Blower Relay
signal, the H-Net control wait s 2 minutes. A retry start ignition sequence for the duration of the local
pump post purge time will occur. During this time ,“
Blower Signal not Received, Retrying
” will be
displayed. After (5) attempts the H-Net control will lock out.
Combustion Air
Damper Fault
Caused when the damper is detected closed, but should be open . Input on J12B.7 & J12B.8.
DHW Heating
The boiler is performing DHW Heating.
Failsafe: HeatNet
Communications
Lost
The control has entered the Failsafe mode due to a loss of HeatNet communications from the Master.
63
Summary of Contents for KN-10
Page 107: ...107 ...