4. Now  prepare  for  wiring.  Use  4  power  cables  and  1  PE  cable,  it  is  suggested  to 
use a 5-core cable(with PE included) for the convenience of using the water-proof 
cable  gland.  The  live  wires  shall  be  at  least  16mm²,  PE  shall  be  greater  than 
10mm². The PE wire shall be crimped to a M6 size ring terminal. Open the 2 locks 
at  the  left  side  of  the  upper  front  cover  and  open  it.  Connect  the AC  input  cables 
into  the  corresponding  terminals  through  the  cable  gland  on  the  bottom  left  side 
and  fasten  them(Refer  to  the  Internal  view  and  terminal  definition  part  for  wire 
connection),  put  the  transparent  cover  on  the  terminal  block  for  safety  purpose. 
Connect the network cable through the hole in front of the AC input cable gland to 
the  RJ45 socket and fasten  the  water-proof gland. Turn on  the  RCBO. Close and 
lock  the  upper  cover  after  checking  internal  wiring  and  breaker  position.  The 
wiring is then finished. 

Notice

1. Only  professional  personnel  can  do  the  wiring,  connect  the  AC  input  wires  in 
correct phase order according to the markings on the terminal block.
2. The PE terminal shall be connected to the Earth firmly and reliably!
3. No  live  work!  Turn  off  the  upstream  breaker  in  the  distribution  panel  and  the 
breaker inside the charging equipment before repairing or maintaining.
4. Please do no disassemble the unit unless authorized!

IV. Parameter configuration

After  installed  and  connected,  the  charging  equipment  must  first  be  configured 
according to the actual needs of the user. The parametersare configured through 
the LCD touch screen. Save the change and exit then the charging equipment can 
be used normally.

After the system enters standby, click thebutton marked by the red rectangle in the 
above figure to enter the system management page, as shown below.

System management page

L1

L2

L3

N

PE

Terminal

Wire

2

16mm

AWG5

2

16mm

AWG5

2

16mm

AWG5

2

16mm

AWG5

2

10mm

AWG7

Summary of Contents for EVD-40D

Page 1: ...ser manual 86 755 2998 8492 T Shenzhen Atess Power Technology Co Ltd 3rd floor building 9 Henglong industrial park the fourth industrial zone of Shuitian community Baoan district Shenzhen China E info...

Page 2: ...connector works independently Up to 2 EV could be charged at the same time All the above features make it most suitable for outdoor charging We sincerely hope that this product can meet your needs and...

Page 3: ...stem Parameters 4 2 Network parameters 4 3 Protection parameters V Operation instruction and LCD introduction 5 1 Charging mode and operation 5 2 LCD interface introduction 5 3 Appendix Fault code VI...

Page 4: ...n device Note The charging equipment will detect the current status of the lightning arrester module in real time When the lightning protection module is damaged the display will have an alarm indicat...

Page 5: ...d 3 holes for cable hooker mounting on the wall Take out the expansion bolts in thepacking accessory bag hammer the expansion bolts into the holes Remove the nuts and washers for later use 2 Loosen th...

Page 6: ...internal wiring and breaker position The wiring is then finished Notice 1 Only professional personnel can do the wiring connect the AC input wires in correct phase order according to the markings on...

Page 7: ...n may consist of multiple charging equipment 5 Number of power modules Number of power modules inside the mode 4 charging equipment 6 Modules power Rated power setting of power module 7 Plug and Charg...

Page 8: ...Authentication Key OCPP login authentication setting 4 3 Protection parameters The protection related parameters such as voltage current temperature power etc No Parameters Function description 1 2 3...

Page 9: ...e Charging will start automatically after EV plugged in If you want to stop the charging just press the stop icon on the screen Plug Charge mode operation process flow The charging equipment is equipp...

Page 10: ...he 4 digit password A wrong password will cause no response and action System parameters page Network parameters page used to set network related parameters of back office server and the charging equi...

Page 11: ...fault Plug line disconnection fault AC Contactor sticking fault AC Input Overvoltage AC Input Undervoltage BMS communication fault VI Specification Model EVD 40D Dimension mm 775 556 270 L W H Weight...

Page 12: ...t Over temperature protection Short circuit protection Emergency stop protection Lightning protection Leakage protection 25 50 derate since 50 Ip54 5 95 2000m derate for higher than 2000m Forced air c...

Page 13: ...7 3 Contact Company Name Shenzhen Atess Power Technology Co Ltd Address 3rd floor building 9 Henglong industrial park the fourth industrial zone of Shuitian community Baoan district Shenzhen China Web...

Reviews: