Appendix
81
Administrator Login Failure
If you are unable to perform an Administrator login (because the Username and
Password information has become corrupted, or you have forgotten it, for
example), you can clear the login information with the following procedure:
1. Power off the eco PDU and remove its housing.
2. Short the jumper labeled J3 (PIN10 and PIN9).
3. Power on the eco PDU.
4. After the beep indicates successfully powered on, power off the switch.
5. Remove the jumper cap from J3.
6. Close the housing and start the eco PDU.
After you start, you can use the default Username and Password to log in.
Summary of Contents for eco PE Series
Page 21: ...Chapter 1 Introduction 11 PE5324LKJA Front View 1 4 5 6 4 4 2 3 7 3 3...
Page 23: ...Chapter 1 Introduction 13 PE5324LJA Front View 1 4 5 2 3 6 3 3...
Page 25: ...Chapter 1 Introduction 15 PE6324LB PE6324LG PE6324LJ Front View 1 5 8 6 8 8 7 2 3 3 3 4 4 4...
Page 27: ...Chapter 1 Introduction 17 PE6324LJA 1 4 7 5 7 7 6 2 3 3 3...
Page 29: ...Chapter 1 Introduction 19 PE5340SLB PE5340SLG PE5340SLJ Front View 1 4 5 6 2 3 3...
Page 31: ...Chapter 1 Introduction 21 PE5340SLJA Front View 1 4 5 6 2 3 3...
Page 38: ...eco PDU PE Low Profile Series User Manual 28 3 2 1 4 1...
Page 78: ...eco PDU PE Low Profile Series User Manual 68 This Page Intentionally Left Blank...