background image

 

 

 

 

While the device is holding on operation mode to pass to programing mode press and hold on button and press  button. 

Enter the menu after seing

 “



on the display. 



is flushing and  



menu on the display firstly.

 

 

                 

 

    

  

 

            

If the password is activated the device asks for password while changing the parameter values. If you enter wring password 
the device gives FALSE masage. You can enter the menu but you can’t change the values. If you enter the right password the 
device gives TRUE masage, you can change the values. 

  

 

 

       

   

 
 

 

 
 

 
 

 

Select the prefered menu by UP Down buttons .   Press button to enter menu which you will change. To change the value 
press PRG again. Use UP DOWN buttons to change values. UP button for increase and DOWN button to decrease. To save 
the value press PRG.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

           

 

 

   

 

 

ALC-94 Series 

PROGRAMMING MENU  











.



Enter the password





.



RST

RST

RST













 
Set-1 Set-2 menus are used for presetting set values. (set-3 or set-4 are also used if they exist.  Each 
menu  controls  aan  output.  When  the  given  set  value  reached  the  related  relay  is  become  activated 
and the LED of the relay signs. There are different output functions. There outputs will be descripted in 
OUTPUT MENU.  
 
To  enter  the  SET  menu  first  enter  the  Programme  menu.  To  enter  the  programme  menu  press  and 
hold PRG button and press RST button. You will see the Set-1 menu. To find Set-2 Set-3 and Set –4 the 
UP DOWN buttons are used. To change the Set-1 value press PRG. You will see the present SET value 
on  the  display.  When  you  press  to  PRG  button  again  the  last  digit  will  flashing.  You  can  set  the 
intended value by using UP DOWN buttons. To pass to other digit press LEFT button. The digit will pass 
left  for  each  LEFT  button  pressing.  To  change  the  point  place  POINT  menu  is  used.  This  subject  will 
descripe  in  POINT  MENU.  After  presetting  the  intended  value  press  PRG  to  save  the  value.  If  you 
would like to leave without saving press RST button.  You can change the other set values by this way. 

 



PRESET SET VALUES ( Set )

 

Output menu allows he different outputs regarding to set values. There are 11 different output types. 
The output types are exit in the graphics section. To select any output mode press and hold PRG and 
press  resent  button.  You  will  be  in  programme  mode.  Find  the  OUTPUT  MENU  by  using  UP-Down 
buttons.Press to PRG buton to see the menu. Press to PRG button again. The menu members will be 
flashing when you press to PRG again. You can select the MODE by using UP DOWN buttons and you 
may save it by pressing PRG button. 





The relay activation time can be controlled by Tout menu. If the time is 0 (zero ) there will be written 
HOLD  on  the  display.  It  means  the  relay  will  be  activated  when  the  relay  value  is  above  the  setted 
value. To enter output time press and hold PRG button and press to RST button. tout-1 tout-2 tout- 3 
tout-4 menus can be found by UP DOWN buttons. To display the Menus press PRG button.When you 
press to PRG button again the values will be flashing. The value can be set by UP DOWN buttons 

Relay Output Time ( tout ) 

 
 

Relay Output Menu ( Output ) 

 
 









Flushing Prog writing 

Summary of Contents for ALC-94 Series

Page 1: ...ns 600 KHz reading speed 6 digit display Functional External Z input Functional HOLD input Quadrature mode up down counting 2 or 4 couple contact relay output Set 1 can be set related with Set 2 Optional factor value between 0 00001 and 999999 Optional decimal point between 1 and 5 digits 5 VDC or 12 VDC encoder power supply 11 various output control mode OFFSET value is adjustable Password Protec...

Page 2: ...ED Signs by Out 1 output relay gets power 7 Out 2 output condition LED Signs by Out 2 output relay gets power 8 Out 3 output condition LED Signs by Out 3 output relay gets power Optional 9 Out 4 output condition LED Signs by Out 4 output relay gets power Optional ALC 94 Series FRONT PANEL DESCRIPTION FRONT PANEL USAGE Entering the value to numerical parameters Press RST and enter the programme the...

Page 3: ...3 SOCKET CONNECTION ALC 94 Series DIMENSION and PANEL CUT OUT Panel cut out ...

Page 4: ...esent SET value on the display When you press to PRG button again the last digit will flashing You can set the intended value by using UP DOWN buttons To pass to other digit press LEFT button The digit will pass left for each LEFT button pressing To change the point place POINT menu is used This subject will descripe in POINT MENU After presetting the intended value press PRG to save the value If ...

Page 5: ... point the accuracy of the value can be selected Also the SET and HYSTERESYS manus poing place can be adjust by this command To adjust the point menu press and hold PRG button and press to RST button POINT menu can be found by UP DOWN buttons In POINT Menu when you press to PRG button you can see the setted point possition Press to PRG button and the value will be flashing By Up Down buttons you c...

Page 6: ...enu Press Prg again to make flashing the options If you press to yes option the device asks you the password The password sets by UP Down buttons and use LEFT button to pass to other digits Press Prg to save the return to the factory settings Restoring Factory Settings Fac def Factory menu used for restoring factory settings All the settings will be changed by this menu So it will be beneficial to...

Page 7: ...f the decrease down the Set values the Outputs don t turn off Only if the RESET comes the outputs turns off When the counting value reachs to Set 1 value Out 1 turn ON and also reachs Set 2 value Out 2 turn ON Out 1 and Out 2 keeps on state in following condition Counting Value Set 1 Counting Value Set 2 NOTE It must be following conditins for all Output modes OFFSET SET 1 SET 2 OUTPUTS ALC 94 Ser...

Page 8: ...epend on the OUT 2 It should be enter the TOUT 2 is time and the TOUT 1 is HOLD Namely when the counting value reachs to Set 1 the OUT 1 turn on and if decrease under to Set 1 it s turn off When the counting value reachs to Set 2 the OUT 2 turn on and the counting value is held The counting value and outputs will be auto reseted in the end of the TOUT 2 time It is also Autoreset mode same as Outpu...

Page 9: ...e reachs to Set 1 the OUT 1 turn on and if it decrease under the Set 1 OUT 1 turns off When the counting value reachs to Set 2 the OUT 2 turn on Even if the decrease down the Set values Out 2 doesn t turn off unless the counting value reach to OFFEST value If the RESET comes the outputs turns off The OUT 1 keeps on until the counting value reachs to SET 1 When the counting value reachs to SET 1 OU...

Page 10: ... If the RESET comes the outputs turns off In this mode it should be selected the TOUT parameters as HOLD The OUT 1 keeps on until the counting value reachs to SET 2 When the counting value reachs to SET 2 OUT 1 turns off and OUT 2 turns on When the counting value increase and reaches reachs to Set 1 OUT 2 turns off and OUT 1 turns on If the RESET comes the counting value becomes the Offset ALC 94 ...

Page 11: ...ensor com ALC77 RS 232 parameters are as follows There is setting on the devices Is one way communications device to the receiving terminal Data format RS232 EOL 16bit data EOL End of line character Baud rate 57600 bps Data bits 8 Stop bits 1 Parity none DATA PROTOCOL ALC 94 Series ERROR MESSAGES If the value is very high 999999 is written If the value is very low 999999 is written ...

Reviews: