L20-LV100-5100(v1.0)
Aerosol (simulated smoke) test
MAINTENANCE
WARNINGS AND LIMITATIONS
WARRANTY
For this test only use test aerosols from an approved manufacturer, in accordance with their application instructions, in order to prevent
contamination or possible damage to the detector. We suggest to spray the aerosol into the detector by using a recommended applica-
tor. The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should be activated by
the control panel itself.
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted alarm or fault condi-
tions. Remove the detector from its mounting base to allow inspection in good light at ground level. Inspect the smoke entry ports around
the detector; use a small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs, hairs, etc. Use a small
vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small particles from the smoke entry screen area.
Wipe the exterior housing of the detector with a clean, damp, lint free cloth to remove any surface film that can later attract airborne
contaminants. Use the hand-held programming unit to read the pollution percentage of the chamber; please, refer to the programming
unit instruction manual. After all detectors have been inspected, repositioned on their mounting bases and power has been re-applied,
check correct operation as described under the “TESTING” paragraph.
Our devices use high quality electronic components and plastic materials that are highly resistant to environ-
mental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in
order to minimize the risk of reduced performance caused by external factors. Ensure that this device is only
used with
VELOX
control panels. Detection systems must be checked, serviced and maintained on a regular
basis to confirm correct operation.
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice should be
sought for special risks. Sensors cannot respond correctly if barriers exist between them and the fire location
and may be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated
periodically.
ATEЇS MIDDLE EAST
FZCO, LIU 11 , DUBAI
SILICON OASIS,POBOX
293640 DUBAI, UAE
EN 54-7:2000
A1:2002 & A2:2006
Point Type Smoke Detec-
tor (Optical)
LV100
Technical data: see docu-
ment TS-LV100-01 held by
the manufacturer.
All devices are supplied with the benefit of a limited 5 year warranty relating to faulty materials or manufacturing
defects, effective from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or
usage.
Product must be returned via your authorized supplier for repair or replacement together with full information
on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon request.
If the detector does not respond to the tests correctly it may be necessary to clean it: in this case follow the instructions indicated in the
“MAINTENANCE” paragraph.
If testing fails again after maintenance then replace the detector with a new one and return the faulty one for servicing.
Alignment between the detector and
the base’s reference raised marks
Figure 4 - The correctly installed detector
Magnet test position (model TMD-01)
TESTING
Detectors should be tested after installation and during periodic maintenance visits (it is recommended each device should be tested at
least once per year). When the system has been reset, allow, after each test, at least one minute for power stabilisation before the next
test. Detectors can be tested as follow:
0832
13
0832-CPD-2141