IDA8 Global-Net User Manual
82
© 2017, ATEÏS, member of PAX ProAV Group
Troubleshooting: Check the URGP16I16O trigger source.
3.1.9.1.14 Remote Offline
The IDA8C/S cannot communicate with peripheral devices.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
G. Fault LED on the front panel of the IDA8C/S.
Log:
The text messages display at the touch screen of the IDA8C:
"Remote Offline"
"PPM Port:2 ID:1", where Port N is the Nth PDC port for the peripheral connection, the ID is
the unique number for each peripheral device on the PDC port.
A text message displays at the window [Machine Fault Record] in Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting: Replace the peripheral device with a working one. If the fault is resolved, the
problem is from the peripheral device. Send the peripheral device to your technician. If the fault is not
resolved, change the IDA8C/S and contact your technician.
3.1.9.1.15 URGP 32I Fault
There is an error on the evacuation inputs or fault inputs on the URGP.
Indication:
LED Indicator:
When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
o
EVAC Input Error(Open):
The text messages display on the touch screen of theIDA8C:
"URGP 32I Fault"
"Port:1 IP:1, ch1 Open", where Port N is the Nth PDC port for a peripheral connection.
The IP is the unique number for each peripheral device on the PDC port, ch is the
number of channel.
A text message displays at the window [Machine Fault Record] in Ateis Studio:
o
EVAC Input Error(Short):