IDA8 Global-Net User Manual
42
© 2017, ATEÏS, member of PAX ProAV Group
Bypass Mode LED:
This LED will light up if the IDA8 is in bypass mode.
Bypass Monitoring LED:
This LED will light up if monitoring of the IDA8 is disabled by manual operation.
Global EVAC LED:
This LED will light up if the system is in EVAC paging state. This LED will light up if any of the IDA8
processor is performing the EVAC paging via Ateis-Net.
To learn more about how to configure an EVAC paging, please see [
] chapter.
Zone EVAC LEDs:
The LED will light up if the audio channel is in EVAC paging. Each LED corresponds to an output
channel of a Network Paging component. For example, 1st LED is for pin M1, 2nd LED for pin M2
and so on.
Power LED:
This LED will light up when the IDA8S is power on.
Network LED:
This LED will light up if there are more than two deployed IDA8 processors in Ateis-Net.
Zone Fault LEDs:
The LED will light up if one of following faults is detected:
Normal AMP Error
Line Speaker Error
Backup AMP Error
AMP Line Leakage Error
3.1.3.2
Rear Panel
Speaker Zone Outputs:
There are 8 zones for speaker & amplifier connection. each zone consists of following connectors
(from left to right):
connector of line speaker.
connector of 100V audio coming from amplifier.
Backup Amplifier I/Os:
Two backup amplifier connectors included 0 dB to amplifiers and 100V return from amplifiers.
Amplifier Zone Outputs: