To reset the High Level Thermal cutout:
1. IMPORTANT: Disconnect heater from electrical power.
2. Remove the cover screw and cover.
3. Firmly press reset button (see above) and listen for a “click”.
4. Replace the cover and cover screw.
5. Reconnect power.
6. IMPORTANT: Check the operation of the thermostat, turn temperature dial from high
to low, if the red light does not go off on low setting, turn off the power supply, and
call a qualified service person to replace thermostat.
7. If the system works, please set thermostat to desired setting.
Note: a lower setting is more economical, and reduces the risk of scalding.
CAUTION: Call a technician if the high limit needs to be reset frequently.
5 Litre Hi Level Reset
10 and 15 Litre Hi Level Reset
TROUBLESHOOTING
Water does not heat up
1. Make sure the power supply is on and there is power available.
2. If light does not come on, check that the reset button is pushed in; follow steps from
previous section.
3. If the indicator light works properly but the temperature does not get hot at the tap,
test for a plumbing crossover. Shut off cold supply to heater and open hot water tap.
There should be no water flowing. Any continued flow indicates a crossover which
will affect the temperature and will need to be corrected.
4. Replace heating element (see previous section on changing the heating element).