OPERATION:
The Model A655-8-3000 timer is a microprocessor-based
device capable of performing 2 different timing modes
over five different timing ranges.The timing ranges allow
for delays from 1 millisecond to 199 hours 59 minutes.
The timing modes and ranges are selected using a DIP
switch assembly located on the inside of the timer.
The time setting is entered through the front panel key-
pad while the time value is displayed on the LCD readout.
The timer keypad can be disabled to guard against acci-
dental time changes by using the internal DIP switch.
The timer is housed in a standard 15-terminal plug-in
round case and can directly replace most existing electro-
mechanical or electronic plug-in round case timers. A
totally sealed faceplate allows this timer to be used in
harsh environments.
Both instantaneous and timed contacts are provided and
A655 timer models are available for operation on either
120VAC or 240VAC.
SPECIFICATIONS
TIMING RANGES
0.001 sec. to 19.999 sec.
0.01 sec. to 199.99 sec.
0.1 sec. to 1999.9 sec.
1 sec. to 199 min., 59 sec.
1 min. to 199 hrs., 59 min.
TIMING MODES
On-Delay
Reverse Start, Delay
TIME SETTING
Front Panel Keypad
TIME REPEAT ACCURACY
±005 sec.
RESET TIME
25 milliseconds
CONTROL VOLTAGE INITIATE TIME
25 milliseconds
MEMORY
Replaceable Lithium Battery
OPERATING POWER
120 or 240VAC, +10%, -20%, 50/60Hz.
POWER CONSUMPTION
5.2VA
INSTANTANEOUS RELAY OUTPUT
7 Amps Resistive, 240VAC, 2 N.O.
2 N.C. Contacts
TIMED RELAY OUTPUT
7 Amps Resistive, 240VAC, 2 N.O.
2 N.C. Contacts
RELAY MECHANICAL LIFE
50,000,000 Operations
DISPLAY
LCD - 4 1/2 Digit, 7/16” High
TERMINATION
Screw Terminals
MOUNTING
Plug-in Case
SHORT CIRCUIT PROTECTION
1/4 Amp Fuse
TRANSIENT VOLTAGE
PROTECTION
Metal Oxide Varistor
OPERATING TEMPERATURE
0°-60°C
UL LISTING
File No. E104697
C-UL (Canada) LISTING
File No. E104697
NEMA RATING
NEMA 12
ORDERING INFORMATION
Part Number
Description
655-8-3000
Timer 120 VAC, W/Battery
655-8-3001
Timer 240 VAC, W/Battery
651-3-0128
Gasket 1/8” Thick (Included With Timer)
651-3-0129
Gasket ¼” Thick (Included With Timer)
600-3-3950
Surface Mounting Bracket
652-3-0130
Battery (Included With Timer)
A655-8-1000/1001/3000/3001
INSTALLATION
INSTRUCTIONS
MARCH, 2001
A655
EXTERNAL DIMENSIONS
MOUNTING DIMENSIONS
MINIMUM DIMENSIONS-MULTIPLE MOUNTINGS
MODEL A600-3-3950-SURFACE MOUNTING BRACKET
www.automatictiming-usa.com
(800) 576 - 6308
AUTOMATIC
TIMING & CONTROLS
Distributed By Inc,