background image

TIMING RANGE SELECTION

The Model A655 allows for the selection of five different
timing ranges. While operating in the “Hours:Minutes”
range, the colon will flash to give an indication that timing
is taking place. The correct timing range is selected using
switches #1, #2 and #3 on the seven switch DIP assembly
located on the inside of the timer. See the chart for the
correct switch settings.

TIME RANGE SELECTION CHART

SW1

SW2

SW3

TIMING RANGE

OFF

OFF

OFF

0.001 – 19.999 Sec.

OFF

OFF

ON

0.01 – 199.99 Sec.

OFF

ON

OFF

0.1 – 1999.9 Sec.

OFF

ON

ON

1 Sec.-190 Min., 59 Sec.

ON

OFF

OFF

1 Min.-199 Hrs., 59 Sec.

Note: OFF = Open    ON = Closed

KEYPAD LOCKOUT SELECTION

The Keypad can be disabled to guard against accidental
changes by using switch #4 on the five switch DIP
assembly located on the inside of the timer. See the
chart below for the correct switch setting.

SW4

KEYPAD LOCKOUT

OFF

Keypad Enabled

ON

Keypad Disabled

Note: OFF = Open   ON = Closed

PROGRAMMING THE TIME

After the timing mode and the timing range have both
been selected, the proper time delay value can now be
programmed.

The Model A655-8-3000 is equipped with a 10-year life,
replaceable lithium battery and can be programmed with-
out an outside power source. To program push the "SET"
button and the display will illuminate the timing range
selected. Four dashes will also appear indicating that no
set point is presently programmed. Depress the "SET" key
a second time and the word "SET" will now be illuminated
on the display along with four zeros. The desired time
value is now entered using the four increment keys.

Each key controls its own digit with the exception of the
left increment key which is used to set the left most 1 and
½ digits on the display (these increment to 19 before
returning to 0). With a timing range of “MIN:SEC” or
“HR:MIN”, the digit to the right of the colon will roll over
from 5 to 0. Holding a key depressed for longer than 1
second causes the digit to automatically increment at 
the rate of 2 numbers per second until released. When
the digits on the display correspond to the desired time
value, pressing the “ENT” key will enter that value into 
the memory.

The set point can be changed without interrupting the
timing cycle by following the normal programming proce-
dure. This new value will then be used on the next timing
cycle.

The set point can also be viewed without interrupting the
timing cycle by depressing the “SET” key. Press the
“ENT” key to return the display to the time remaining.
If the keypad lockout is enabled, you can still view the set
point by depressing the “SET” key but the set point cannot
be changed using the increment keys. To indicate that the
keypad is locked while a programmed value is being
viewed, the display alternates the numerical value with
the word “LOC”.

POWER FAILURE

If all power is lost during a timing cycle, the instantaneous
contacts will transfer back to their original state. When
power is restored, the timer will reset back to the set point
if programmed for “standard start” or continue from the
point of power interruption if programmed to “reverse
start”. The timer set point will be maintained.

INTERNAL SCHEMATIC

WIRING CONNECTIONS

Note: It is important that the metal bracket on the front of
the case be connected to earth ground. Mounting the
A655 in a grounded metal panel is satisfactory.

TYPICAL WIRING DIAGRAM

Dotted Lines Are External Wiring

Sustained Control Switch

Standard Start

Close to run and
Open to reset

Reverse Start

Close to reset and
Open to run

The above diagram shows the typical timer wiring for a
simple application involving the delayed closing and
opening of load circuits. Contacts may be wired in series
to achieve various timing schemes.

TIMING MODE SELECTION

The Model A655 is capable of performing two different
modes of timing operation; On-Delay, or Reverse Start,
Delay. The selection of the timing mode is accomplished
by setting DIP switches 5, 6 and 7 on the switch assembly
that is accessed when the timer is removed from its
mounting case.

SW5

SW6

SW7

TIMING MODE

OFF

OFF

OFF

On-Delay

OFF

ON

OFF

Reverse Start, Delay

Note: OFF = Open

ON = Closed

TIMING MODE DEFINITION
ON-DELAY

The supply voltage is applied at all times. When voltage
is applied to the control terminal, the instantaneous
contacts change state and timing begins. At the
completion of the timing period, the timed contacts
change state. Reset takes place upon removal of the
control voltage.

REVERSE START, DELAY

The supply voltage is applied at all times. When voltage
is applied to the control terminal, the instantaneous
contacts change state. When the voltage is removed 
from the control terminal, the instantaneous contacts
change back to their original state and timing begins. At
the completion of the timing period, the timed contacts
change state. Reset takes place when voltage is once
again applied to the control terminal.

TIMING RANGES 

ON-DELAY

REVERSE START, DELAY

INSTALLATION INSTRUCTIONS–A655-8-1000/1001/3000/3001

INSTALLATION INSTRUCTIONS–A655-8-1000/1001/3000/3001

www.automatictiming-usa.com

www.automatictiming-usa.com

Reviews: