41
Flue gas system
Connections
Collective flue gas outlet overpressure
Diameter and venting lengths of the flue gas outlet/air supply:
Closed system with over
-
pressure.
Closed system, overpressure, parallel
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2
-
5
h = 6
-
10
h = 11
-
15
h = 16
-
20
114
–
285
150
150
150
150
285
-
524
150
200
200
200
524
-
1440
180
300
300
300