PPAARRAAMMEETTEERR 0066
Parameter 6 - Inrush optimization
Setting range:
OFF, 1. . . 8 h
Factory setting:
1
HHCC
Application
(for weather dependent systems only):
Enhanced heating comfort for objects with individual occupati-
on characteristic, such as detached houses or condominiums
with their own control circuit.
This parameter calculates the latest heat-up time within a pre-
determined adjustment value and under consideration of the
outside temperature curve, in order to assure the desired room
temperature at the start of the specified occupation.
The inrush times stored in the timeprograms therefore no lon-
ger refer to the start of heating, but to the start of occupation,
i.e. the point in time at which the desired room temperature is
reached.
next parameter
Parameter 25 - Day temperature
(standard value)
Setting range:
5.0. . . 30.0 °C
Factory setting:
21.0 °C
Application:
Determination of the standard room temperature - simple
adjustment for all daytime room setvalues in case of other occu-
pation situations (e.g. changing of tenents or owner)
This parameter determines the desired daytime room
temperature when operated in operational modes
PARTY
and
HEATING
and serves as a base value for the temperatures in
the automatic programs.
Important!
The temperature settings during the heating cycles implemen-
ted in the timeprograms will change by the same magnitude
when changing the Parameter!
PPAARRAAMMEETTEERR 2255
HHCC
2211..00
°C