Astria Gemini33REN Installation And Operation Instructions Manual Download Page 40

Installation 

900285-01  08/2016

Innovative Hearth Products
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces

40

Figure 32 -  Junction Box Wiring, 120 V, 60 hz, 1 phase

Figure 33 - Wiring Diagram—Millivolt Gas Valves

 

Ground: green

Neutral: white 120 V

AC: black

Wall-mounted ON/
OFF blower switch 
or variable speed 
control switch

*

Junction 

box

Tab 
broken

Hot side of 
receptacle

Neutral side 
of receptacle

Green ground screw

Tab 
intact

Field wired

Factory wired

Blower

Ground

Plug blower into 

this receptacle

Red

Black

Green

White

TP-TH

TP

TH

APPLIANCE- MOUNTED
ON/OFF SWITCH
(OPTIONAL)

BK/W(1)

BK/W(1)

WALL-MOUNTED ON/OFF SWITCH (OPTIONAL)
THERMOSTAT (OPTIONAL)

JUNCTION BOX

BLACK

W

GR

120 V

AC

WALL MOUNTED CONFIGURATION FOR FAN SWITCH (OPTIONAL)

BK

R

THERMOPILE

GAS VALVE

FAN

(OPTIONAL)

13. 

 Connect the Gas Line

All codes require a shutoff valve mounted in the supply line. 

Figure 35

 illustrates two methods for connecting the 

gas supply. The fl ex-line method is acceptable in the U.S., however, Canadian requirements vary depending on 
locality. Installation must be in compliance with local codes.

NOTE: 

Ensure the CPI/IPI switch is set to intermittent mode with the pilot in the OFF position. See control 

compartment door label for more information.

NOTE: 

A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line 

from damaging the valve.

NOTE: 

Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds 

are used in propane applications). Seal around the gas line to prevent cold air leakage. Gas line holes and other 
openings can be caulked or stuffed with unfaced fi berglass insulation.

Figure 34 -  Control Compartment

Figure 35 -  Gas Line Connection

 

(Optional) fl exible gas 

line connector

Gas 

valve

3/8” Nipple

3/8” Union

3/8” Close nipple

3/8” Shutoff valve

3/8 NPT x 3/8” 
Flare fi tting

1/2 x 3/8” Flare 
shutoff valve

3/8” Flex tubing

Gas 
stub

1/2 x 3/8” 

Reducer

Main gas shutoff 

valve

Gas valve

Optional burner ON/OFF switch (millivolt units)

CPI/IPI switch (electronic units)

Piezo 
(millivolt units)

Door latch

These fi replaces are equipped with a gas fl ex line for use (where permitted) in connecting the unit to the gas line. A 
gas fl ex line is provided to aid in attaching the direct-vent fi replace to the gas supply. The gas fl ex line can only be 
used where local codes permit. The fl ex line is rated for both natural and propane gas. A manual shut off valve is also 
provided with the fl ex line.
The gas control valve is located in the lower control compartment 

(

Figure 34

).

 Access the Control Compartment

See 

Page 53

 for instructions on 

Accessing the Control Compartment

.

Millivolt and electronic control valves have a 3/8” (10 mm) NPT thread inlet port.

Summary of Contents for Gemini33REN

Page 1: ...eur de gaz appelez le service des incindies L installationetl entretiendoiventêtreassuréspar un installateur ou un service d entretien qualifié ou par le fournisseur de gaz INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference Installateur Laissez cette notice avec l appareil Consommateur Conservez cette notice pour consultation ultérieure This appliance m...

Page 2: ...LA VITRE EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO L écran pare étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques Una barrera diseñada para reducir el riesgo de quemaduras desde la mir...

Page 3: ...maduras graves si se toca Mantenga a los niños alejados de la chimenea en funcionamiento Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros líquidos inflamables alejados de la chimenea Aún después de haber apagado el gas las superficies de la chimenea permanecen extremada...

Page 4: ...tts 10 Cold Climate Insulation 10 Manufactured Home Requirements 11 Location 11 Vent Termination Clearances 12 Minimum Clearances to Combustibles 14 Wall Finishes Surrounds Mantels 15 Installation Preparation 15 Installation Installation Sequence 16 Construct the Fireplace Framing 16 Prepare the Fireplace Top Spacers 18 Route the Gas Supply Line to the Fireplace 18 Vent System Preparation 21 Insta...

Page 5: ...euvent subir des brûlures s ils viennent en contact avec la surface chaude Il est recommandé d installer une barrière physique si des personnes à risques habitent la maison Pour empêcher l accès à un foyer ou à un poêle installez une barrière de sécurité cette mesure empêchera les tout petits les jeunes enfants et toute autre personne à risque d avoir accès à la pièce et aux surfaces chaudes 7 Tou...

Page 6: ...gerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Turn off the gas supply to the appliance and have it serviced by a qualifie...

Page 7: ...els or combinations of fuels will degrade the performance of this system and may be dangerous Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation Never obstruct the front openings of the appliance These appliances are designed as supplemental heaters Therefore it is advisable to have an alternate primary heat source when installed i...

Page 8: ...imperative that control compartments burners and circulating air passageways of the fireplace be kept clean Remarqué L installation et la réparation devrait être confiées à un technicien qualifié L appareil devrait faire l objet d une inspection par un technicien professionnel avant d être utilisé et au moins une fois l an par la suite Des nettoyages plus fréquents peuvent être nécessaires si les ...

Page 9: ... 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Manifold Gas Supply Pressure Fuel Pressure Natural Gas 3 5 WC 0 87 kPa Propane 10 0 WC 2 49 kPa Test gauge connections are provided on the front of the millivolt and electronic gas control valve identified IN for the inlet and OUT for the manifold side The control valves have a 3 8 10 mm NPT thread inlet and outlet side of the valve Figures...

Page 10: ...egulations 248 C M R Sections 4 00 through 8 00 Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a T handle type valve Massachusetts Horizontal Vent Requirements In the Commonwealth of Massachusetts horizontal t...

Page 11: ...edition LOCATION In selecting the location the aesthetic and functional use of the fireplace are primary concerns However vent system routing to the exterior and access to the fuel supply are also important Due to high temperatures the fireplace should be located out of traffic and away from furniture and draperies En raison des températures élevées l appareil devrait être installé dans un endroit...

Page 12: ... 2 ft minimum 2 ft minimum Lowest discharge opening H H minimum height from roof to lowest discharge opening of vent Horizontal overhang Vertical wall Vent termination Storm collar Concentric vent pipe Flashing 1 26 mm minimum clearance to combustibles TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS Table 6 Termination Heights for Vents above Flat or Sloped Roofs NFPA 54 ANSI Z223 1 Gas V...

Page 13: ...to inside corner 6 152 mm minimum 6 152 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 36 910 mm 36 910 mm J Clearance to nonmechanical air supply inlet to building or t...

Page 14: ...stible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Hearth Extension A hearth extension is not required with this fireplace If a hearth extension is used do not block the lower control compartment door Any hearth extension used is for appearance only and does not have to conform to standard hearth ex...

Page 15: ... NOTE Combustible wall finish materials and or surround materials must not be allowed to encroach the area defined by the fireplace front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the fireplace face Figure 40 Non combustible materials such as surrounds and other fireplace trim may be installed on the fireplace face but they must not cover ...

Page 16: ...replace Operation Page 41 Finishing 16 Optional Install the Firebox Liners Page 42 17 Install the Logs Volcanic Stone and Glowing Embers or Glass Media Page 42 18 Install the Glass Door Page 42 19 Adjust the Air Shutter to Ensure Proper Flame Appearance Page 42 20 Install the Hood in Traditional Fireplaces Page 43 21 Reinstall the Included Barrier Page 44 22 Install the Finishing Materials and Fac...

Page 17: ...1 4 921 25 5 8 651 12 1 8 308 5 1 2 140 35 35 3 8 899 59 1 2 1511 42 1 8 1070 30 1 4 768 14 1 4 362 6 5 8 168 40 40 3 8 1025 63 7 8 1622 45 3 8 1153 33 1 4 845 15 7 8 403 8 1 2 216 45 45 3 8 1153 70 3 8 1788 49 3 4 1264 35 1 4 895 17 1 2 445 10 1 4 260 Table 11 Fireplace Framing Specifications Corner Installation with Horizontal Termination Table 12 Fireplace Specifications Model A B C D door E F ...

Page 18: ...eplace framing Pipe coupling recommended 5 1 4 140 mm 3 77 mm Proper Sizing of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code NFPA 54 latest edition USA or CAN CGA B149 1 latest edition Canada The gas supply line should not be connected to the appliance until s...

Page 19: ...ck off from rear venting and proceed with fireplace installation If you require a top vented unit use the following steps to convert the fireplace before use Outside preparation of the fireplace for top vent conversion Step 1 Remove the eight 8 screws holding the top vent cover plate and gasket Discard cover plate and reinstall screws Step 2 Remove the round flue cover from the top venting outlet ...

Page 20: ...lace and plug it into the junction box in the right rear of the fireplace Figure 32 5 Install the blower control switch according to its included instructions 5 Installing Non Combustible Fireboard Standoff All Models A non combustible standoff board is provided for all model fireplaces to prevent overlap of drywall or other material of portions of the fireplace that may be prone to the buildup of...

Page 21: ...ecure the fireplace to the side framing members using the unit s nailing flanges one top and bottom on each side of the fireplace front Figure 11 Use 8d nails or the equivalent Figure 11 Nailing Flanges Side framing Unit nailing flange no clearance to combustible framing is required VENT SYSTEM PREPARATION 8 Select a Horizontal or Vertical Vent System 1 With the fireplace secured in the framing de...

Page 22: ... 10 40 25 ft Maximum horizontal run flat to near level 60 ft Maximum vertical run 60 1 9 25 Horizontal Distance ft Vertical Height ft from top of unit Vertical Height ft 2 5 Elbow 5 10 15 3 Base wing 3 Base 6 ft Minimum vertical run 6 ft Minimum vertical run None For straight runs or runs with elbows as illustrated in Vertical Vent Figures Tables starting on Page 28 No rise required On 33 Models u...

Page 23: ...ired a telescopic vent section SV4 5LA may be used to provide the installer with an option to install in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telescopic Vent Section has an effective length of from 1 1 2 to 7 38 to 191 mm The SV4 5LA is fitted with a locking ...

Page 24: ...3 0 0 3 465 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0 1 10 11 91 5 7 625 0 0 2 0 1 3 504 42 1 0 0 1 10 12 93 7 75 0 0 0 0 2 2 511 5 42 625 0 0 0 0 11 11 97 5 8 125 1 0 0 0 2 3 520 5 43 375 0 2 0 1 11 14 103 5 8 625 0 0 0 3 0 3 531 44 25 0 2 2 0 11 ...

Page 25: ...t walls is specified in ANSI Z223 1 In Canada the current CAN CGA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the gas vent rule Table 6 The following figures and their associated vertical vent tables illustrate the various configurations that are possible for use with these fireplaces Secure Vent pipe is sh...

Page 26: ...If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer with 8d nails or other appropriate fasteners at each corner Remember to maintain 1 26 mm clearance to combustibles framing members and attic or ceiling insulation when running vertical chimney sections NOTE The gap ...

Page 27: ...h waterproof caulking 11 Install the storm collar Install the storm collar supplied with the flashing over the vent flashing joint Figure 22 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the adjusting screw Apply non combustible caulking or mastic around the circumference of the joint to provide a water tight seal Figure 22 Installing the Storm Coll...

Page 28: ...used WARNING Do NOT join separate sections of concentric flexible vent pipe Figure 24 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling firestop spacer SF4 5VF 60 ft 18 3 m maximum Ceiling firestop spacer SV4 5VF When using Secure Flex use ceiling firestop spacer SF4 5VF H V Install the U shaped vent restrictor in any vent run with...

Page 29: ... 6 ft of vertical rise See Page 22 for more information If 20 ft of H horizontal vent run is needed then 4 ft straight section minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 20 ft NOTE The vent system may have a maximum of three 3 90 elbows Minimum 6 ft of vertic...

Page 30: ... center 3 Frame the ceiling opening If the vertical route is to penetrate a ceiling use plumb line to locate the center above the fireplace Cut and or frame an opening 10 1 2 x 10 1 2 267 x 267 mm inside dimensions about this center Figure 20 4 Attach the vent components to the fireplace See Connecting the vent pipe on Page 23 5 Attach the vent components to each other See Connecting the vent pipe...

Page 31: ...which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall The horizontal termination must not be recessed into the exterior wall or siding by more than the 1 1 4 32 mm Figure 27 NOTE If the venting exits the building below grade or close to grade see Installation Accessories on Page 49 for available snorkel terminatio...

Page 32: ...e silicone caulking to seal the top and sides of the termination up to the underlayment stucco or masonry wall surface Adaptor SV4 5RCH For thicknesses greater than 9 1 4 235mm see Table 20 SV4 5HT 2 Square Termination Maximum Wall Thickness 9 1 4 235 mm Exterior Surface of Siding Exterior Surface of Framing 6 to 9 1 4 152 to 235 mm 1 1 4 Maximum Recess of the Square Termination into Exterior Fini...

Page 33: ...a constant surface and adjust the support straps as necessary NOTE SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible wall WARNING Do not join separate sections of concentric flexible vent together Ta...

Page 34: ...5 ft of H horizontal vent run is needed then 5 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 25 ft 7 62 m When using Secure Flex use Ceiling Firestop Spacer SF4 5VF When using Secure Flex use Wall Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF Ceiling F...

Page 35: ...r a particular range of exterior wall thicknesses If 20 ft of H horizontal vent run is needed then 4 ft minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 20 ft 6 096 m When using Secure Flex use Ceiling Firestop Spacer SF4 5VF When using Secure Flex use Wall Firesto...

Page 36: ...lant P N 10K81 to the inner adaptor collar approximately 1 2 from the end c Pull and extend the inner flexible vent d Slide the inner flex vent over the adaptor collar at least 1 3 4 NOTE Ensure the flex vent is free from damage or tears e Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar approximately 3 4 from the end of the flex f Install thre...

Page 37: ...n and adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has an longer center tube to improve ease of installation 11 Complete the Field Wiring CAUTION The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box see wiring diagrams Failure to do so will result in a potential safety hazard The appliance must ...

Page 38: ...BOX 120V AC HOT NEUTRAL GROUND B BL 2B 1B 2A 2 1 1A R O B 1 2 G W BL BL O O R R W G B B W G R W B Y G O W R BL B BL W G G Y O Y B B B R B B Electronic Wiring One of the following optional controls must be used ON OFF Wall Switch Thermostat or Remote Control See the Operation section on Page 51 for more details NOTE Electronic models must be connected to the main power supply 1 Route a 3 wire 120 V...

Page 39: ...ent door Page 53 FBK 100 FBK 200 and FBK 250 Kits An electrical outlet box is provided for the installation of the FBK 100 FBK 200 and FBK 300 forced air blower kits Electrical power must be provided to the box to operate the blower Install the blower kit according to the installation instructions provided with the kit NOTE The tab connecting the receptacles of the outlet box must be broken in FBK...

Page 40: ...commended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve NOTE Secure all joints tightly using appropriate tools and sealing compounds ensure propane resistant compounds are used in propane applications Seal around the gas line to prevent cold air leakage Gas line holes and other openings can be caulked or stuffed with unfaced fiberglass insulat...

Page 41: ... or refasten the leaking connection and then retest as described above 3 When the gas lines are tested and leak free rinse off the leak testing solution 14 Verify Proper Fireplace Operation 1 With the gas line installed inspect the system before closing the front of the unit 2 Follow the pilot lighting instructions Millivolt Systems Pages 67 68 Electronic Systems Pages 69 70 SIT fireplaces Pages 7...

Page 42: ...or if the flame is orange with evidence of sooting black tip the air shutter opening may need to be adjusted If the air shutter opening is closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very long orange flames Sooting results in black deposits forming on the logs fireplace inside surfaces and on exterior surfaces adjacent to the vent termination So...

Page 43: ...sly to ensure that the proper flame appearance is achieved Figure 39 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the air shutter incrementally to a more open position until the proper flame appearance is achieved If flame remains blue adjust the air shutter incrementally to a more closed position until the proper flame appearance is achieved 4 W...

Page 44: ...rary models only finish wall flush to face of unit and install facade base and panel Frame assembly to complete the front of the fireplace see facade installation instructions Page 45 Figure 40 Combustible Wall Framing Figure 41 Face Mounting Elements Top Face Brackets Fireplace face foot slots NOTE See Cold Climate Insulation on Page 10 and Vent Termination Clearances on Page 12 22 Attach the Saf...

Page 45: ...top trim pieces over flange of panel until seated squarely Step 2 Slide side trim pieces into place top will overlap slightly Repeat Step 1 and Step 2 for bottom and opposite side trim for panel NOTE Remove protective film from all stainless components before installation Step 3 Plug lead wires into the IPI CPI Switch on right side of facade base ...

Page 46: ...ts see Figure 41 on both sides near the bottom of the fireplace opening Step 4b Tilting the facade base up on its foot tabs secure the top by engaging the three brackets see Figure 41 on the face of the fireplace with the three cut outs on the back top of the facade base Step 5 Slide the tabs on the back of both sides of the facade panel into the slots on the base Black Base and Stainless Panel sh...

Page 47: ...ôle le fonctionnement du foyer en le faisant basculerdeMarcheàArrêt etvice versa Nettoyez soigneusement la plaque murale de l interrupteur ou le thermostat mural pour éliminer la poussière et les traces de graisse ou d huile Collez l étiquette sur la surface de la plaque de l interrupteur mural qui contrôle le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principaleme...

Page 48: ...0 SV4 5HTSK Termination Shroud Guard for Horizontal Square Termination 1 pack see 750246M H3907 SV4 5ARSA Attic Insulation Shield with adjustable height 12 to 22 Cat No Model Description H1968 SV4 5HT 2 Horizontal Square Termination with Firestop Spacer H2246 and Adaptor 74L61 94L10 SV4 5HTSS Rigid Horizontal Small Square Termination with Firestop Spacer H2246 Adaptor 74L61 see 750204M H5817 SV4 5...

Page 49: ...IT24S Square Term for flex with 24 610 mm compressed flex 77L90 SFKIT36S Square Term for flex with 36 914 mm compressed flex 77L91 SFKIT48S Square Term for flex with 48 1219 mm compressed flex 91L66 SFGC4 6 Gear Clamp 4 5 114 mm for flex 6 pack 91L67 SFGC7 6 Gear Clamp 7 5 190 5 mm for flex 6 pack Cat No Model Description 94L04 SFKIT12SS Small Square Termination for flex with 12 305 mm of compress...

Page 50: ... of the CAN CGA B149 1 Installation code La conversion devra être effectuée conformément aux recommandations des autorités provinciales ayant juridiction et conformément aux exigences du code d installation CAN CGA B149 1 Gas conversion kits are available to adapt your fireplace from the use of one type of gas to the use of another These kits contain all the necessary components needed to complete...

Page 51: ...more affected by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or other combustible materials within 36 of the front of viewing area s NOTE Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns...

Page 52: ...rruptor opera la chimenea encendiéndola y apagándola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea Figura A o en el termostato de pared Figura B Seleccione el idioma que más se habla en la casa 2 Si se usa un control remoto para controlar la chimenea encuentre el transmisor y límpielo bien p...

Page 53: ...crew Figure 43 inside the control compartment securing the control compartment door Retain the screw for later reinstallation 2 Position the left side door tab Figure 43 out of the tab groove and align it with the vertical slot Figure 43 Figure 43 Control compartment door slots Figure 44 Control compartment door tabs Vertical slot Screw hole Tab pivot hole Tab groove Door tabs 3 Lift the left side...

Page 54: ...ic fireplaces can automatically switch to battery power In the event of a power outage this allows ON OFF operation without blower functionality Install new batteries before every burn season 1 Open the control compartment Page 53 and locate the battery holder 2 Install four 4 AA batteries in the battery holder 3 Close the control compartment door Continuous Pilot Ignition Switch Fireplaces with a...

Page 55: ...E Install the firebox liner before placing the stone Logs can be installed after the volcanic stone 1 If necessary remove the glass door Page 58 2 In contemporary fireplaces install glass media in recessed areas between front and rear floors In 35 fireplaces use less than one bag The 40 contemporary models require a full bag Spread the glass in a thin layer evenly over the burner Leave the pilot a...

Page 56: ... Figure 50 Place embers and other media see Page 55 Figure 50 Locating the log placement brackets Figure 51 Placing logs 1 and 2 Front Left Log Placement Bracket Burner Slots Do Not Obstruct Rear Left and Rear Right Log Placement Brackets 3 Align the notches in the Rear left log 1 with the Rear left brackets Figures 50 and 51 in 35 units ONLY 4 Position the Center Log 2 on the right rear log place...

Page 57: ...cate and bend up the log placement brackets Figure 54 Figure 54 Locating the log placement brackets Figure 55 Placing logs 1 and 2a Burner Slots Do Not Obstruct Left and Right Rear Log Bracket Left Front Bracket Right Front Bracket 2 Position rear left log 1 on the left rear log bracket Figure 55 3 Position the center log 2a against the log grate and to the rear of the fireplace Figure 55 Figure 5...

Page 58: ...nçue pour réduire le risque de brûlure par le hublot chaude est fournie avec l appareil et doit être installé WARNING Do not operate appliance with the glass front removed cracked or broken AVERTISSEMENT Ne pas utiliser l appareil si le panneau frontal en verre n est pas en place est craqué ou brisé WARNING Any safety screen guard or barrier removed for servicing an appliance must be replaced prio...

Page 59: ... fasten the two 2 latches beneath the firebox floor to the door V flange 4 Install the barrier 5 Close the control compartment door Removing the glass door NOTE In contemporary models remove facade panel and base first 1 Open the control compartment door in traditional models Page 40 NOTE If necessary remove the door and place it in a safe location for later reinstallation 2 Remove the barrier Pla...

Page 60: ...g of the venting system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodically during the burn season inspect the horizontal termination for debris such as bird nests leaves paper or branches Remove any items from the surfaces of the termination prior to use Also be ...

Page 61: ...brush e g paint brush Reinstalling the embers and logs Carefully follow the placement instructions Page 55 All logs should fit onto the corresponding pins and or log stoppers This will ensure proper flame and safe combustion NOTE Improper positioning of logs can create carbon build up and will alter the performance of the fireplace Replacing the logs If the logs become damaged and need replacement...

Page 62: ...uction Look for any signs of dislocation of the vent components Fireplace Inspection Qualified Service Technician Perform the appropriate fireplace inspection procedure detailed in this manual Replacing Glowing Embers Homeowner Qualified Services Technician Remove the old glowing embers and vacuum the area Place new glowing embers Figures 48 49 Replacing Batteries Homeowner Qualified Services Tech...

Page 63: ...e Speed with thermal snap switch Glowing Embers and Volcanic Stone Traditional Models Table 44 Glowing Embers and Volcanic Stone Catalog Model Description 88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone Firebox Liner Kits Traditional Models Table 45 Ceramic Fiber Liner Kits Catalog Model Description Used on F1887 MBLK33B Buff 33 Models F1886 ABLK33V Vintage Red F2187 BLK33OTR H Ol...

Page 64: ...docking station Receiver wall mounted or placed in the control compartment Thermostatic or manual ON OFF operation Programmable weekday weekend modes Flame icon Low battery indicator Batteries included H8865 Model RC S TOUCH WS S STAT Wall control Catalog Number Large LCD display Shows room and set temperatures in F and C Wall mounted Thermostatic or manual ON OFF operation Connects to wall switch...

Page 65: ...able 50 Unit Mountable Rocker Switch Table 51 OFF ON Wall Switch Kit ACCESSORY COMPONENTS continued Ecoflow Control Kits Required Option for Ecoflow Fireplaces Ecoflow Basic Remote Control Catalog Number Manual ON OFF operation Off Continuous pilot feature Kit includes remote and receiver F2687 Model EF BRCK Ecoflow Thermostat Remote Control Catalog Number Thermostatic or manual operation Off Cont...

Page 66: ...cription H8412 CRSHGL RBLK Bag of Glass Media Reflective Black H8424 CRSHGL RBLU Bag of Glass Media Reflective Blue H8413 CRSHGL P Bag of Glass Media Platinum H8538 CRSHGL GF Bag of Glass Media Goldfinger H8539 CRSHGL C Bag of Glass Media Copper NOTE No more than one 5 lb bag should be used in the fireplace Reflective Blue Goldfinger Platinum Reflective Black Copper Catalog Model Description F2487...

Page 67: ...LY CALL your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE s F THE PILOT WILL NOT STAY LIT AFTER SEVERAL TRIES TURN THE GAS CONTROL knob to OFF and call your service technician or gas supplier 10 Turn gas control knob counterclockwise to ON 11 Close control compartment 12 If applicable Turn on all electrical power to the appliance 13 If applicable Set thermo...

Page 68: ... le fournisseur de gaz s 3I LA VEILLEUSE NE RESTE PAS ALLUM E APRáS PLUSIEURS TENTATIVES réglez la manette d admission du gaz à la position OFF et appelez un technicien qualifié ou le fournisseur de gaz 10 Tournez le bouton de réglage du gaz en sens inverse des aiguilles d une montre jusqu à sa position de marche ON 11 Fermer le compartiment de contrôle 12 Si applicable Mettez l appareil sous tens...

Page 69: ...Electronic Gas Control Valve SIT Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remove batteries if installed 4 Close the main line gas shut off valve 1 STOP Read the safety information above on this label 2 Read the Care and Operation manual including the section on Remote Control System if applicab...

Page 70: ...r les batteries au besoin 8 Placez l interrupteur du récepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bouton ON OFF pour sélectionner ON 10 Si applicable Ajustez le thermostat sur la télécommande à l ajustement désiré 11 Si l appareil ne se met pas en marche suivez les instructions intitulées Comment couper l admission de gaz de l appareil et appel...

Page 71: ...ol which has been under water Copreci Gas Valve Switches Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remove batteries if installed 4 Close the main line gas shut off valve 1 STOP Read the safety information above on this label 2 Read the Care and Operation manual including the section on Remote Co...

Page 72: ...N REFROIDIE NE LAISSEZ JAMAIS UN ENFANT DE TOUCHER LA VITRE L écran pare étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques Interupteurs Option Hi Lo MARCHE ARRÊT Option IPI Mode Intermittent Veilleuse Apprenez Quelques modèles Jaune Bleu Brun fil noir 1 ARRÊTEZ...

Page 73: ...lowing the lighting instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that the connection between the valve and thermocouple are tight and secure 3 Pilot burning no gas to burner Valve knob ON and the standard burner OFF ON switch is ON NOTE If an optional remote swi...

Page 74: ...ck the gas supply and gas shutoff valves b Loose wires to the valve or ignition module Check control compartment for any obviously loose wiring call a service technician if necessary c Pilot flame is not engulfing the sensor Call a service technician d Obstructed vent system Call a service technician 4 Soot is present on the logs and glass a Excessive flame impingement on the logs Properly positio...

Page 75: ...t Electrode and Cable H6212 1 H6212 1 H6212 1 H6212 1 Orifice Holder H7257 1 H7257 1 H7257 1 H7257 1 Gas Flex Line Connector 93L32 1 93L32 1 93L32 1 93L32 1 Gas Valve Millivolt Natural Gas H6209 1 H6209 1 H6209 1 H6209 1 Gas Valve Millivolt Liquid Propane 88J53 1 88J53 1 88J53 1 88J53 1 1 Log Set F2191 1 F2192 1 F2194 1 F2196 1 Vent Restrictor Base H8987 1 H8987 1 H8987 1 H8987 1 Vent Restrictor W...

Page 76: ... Gas J7934 1 J7934 1 J7934 1 J7934 1 Ecoflow V Wire J7933 1 J7933 1 J7933 1 J7933 1 Ecoflow Control Module CD models only J7937 1 J7937 1 J7937 1 J7937 1 Ecoflow Remote wire harness F2690 1 F2690 1 F2690 1 F2690 1 Ecoflow RF Control Module F2694 1 F2694 1 F2694 1 F2694 1 Ecoflow Power Adaptor J7930 1 J7930 1 J7930 1 J7930 1 Ecoflow Battery Holder J7931 1 J7931 1 J7931 1 J7931 1 WARNING Never use s...

Page 77: ...ifiquement approuvées avec cet appareil sont utilisées Table 57 Homeowner Replacement Parts Description 33 Models 35 Models 40 Models 45 Models Catalog Number Catalog Number Catalog Number Qty Catalog Number Qty Catalog Number Qty 5 Hood F1900 1 F1837 1 F1838 1 F1901 1 6 Barrier F1902 1 F1839 1 F1840 1 F1903 1 7 Glass Door F1905 1 F1841 1 F1842 1 F1906 1 8 Control Compartment Door F1898 1 F1835 1 ...

Page 78: ...Operation 900285 01 08 2016 Innovative Hearth Products Gemini and GeminiCD Series Direct Vent Gas Fireplaces 78 NOTES ...

Page 79: ...flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Product is designed to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatu...

Page 80: ...eplace serial number Date fireplace was Installed Type of gas fireplace uses Dealer name IHP reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2015 Innovative Hearth Products P N 900285 01 Rev F 08 2016 1508 Elm Hill...

Reviews: