Astria Craftsman 42P2 Installation And Operation Instructions Manual Download Page 11

Astria.US.com

126662-01D

11

VENTING INSTALLATION 

Continued

Pitch

Slope Opening 

"A" Max. 

Used Flashing 

Model No. 

Flat

15"

V6F-8DM

0-6/12

26.6°

16 

1

/

8

"

V6F-8DM

6/12- 12/12 45.0°

20 

3

/

8

"

V12F-8DM

Figure 15 - Roof Opening Measurements

FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)

Determine flashing to be used with roof opening chart. Slide flashing 

over pipe until base is flat against roof. Replace as many shingles as 

needed to cover exposed area and flashing base. Secure in position 

by nailing through shingles (see Figure 16). DO NOT NAIL THROUGH 

FLASHING CONE.

Installing Flashing on a Metal Roof

When installing flashing on a metal roof, it is required that putty tape 

be used between flashing and roof. Flashing must be secured to roof 

using #8 x 3/4" screws and then sealed with roof coating to prevent 

leakage through screw holes. A roof coating must also be applied 

around perimeter of flashing to provide a proper seal.

Nail Only Outer 

Perimeter of 

Flashing

Storm Collar

Underlap Shingles 

at Bottom

Figure 16 - Flashing Installation

Flashing 

Cone

Overlap 

Shingles Top 

and Sides Only

Figure 14 - Firestop Spacer with Attic Space Above Ceiling

If area above is an attic or insulated area, install 

firestop above framed hole.

IMPORTANT NOTICE 

When penetrating a ceiling into an attic, a firestop 

thimble (38FST or FST30) is required to avoid intru-

sion by insulation and recommended to negotiate a 

joist (see Figure 14a).

30"

(76.2 cm)

Minimum Measurements

Opening "A"

14 

3

/

8

"

(48.3 cm)

1"

(2.54

cm)

1"

(2.54

cm)

1"

(2.54 cm)

Figure 14a - Firestop Thimble

Thimble 

38FST

 or 

FST30

Firestop

PENETRATING ROOF

To maintain a 1" clearance to pipe on a roof with a pitch, a rectangular 

opening must be cut.
1.  Determine center point where pipe will penetrate the roof.
2.  Determine center point of the roof. Pitch is the distance the roof 

drops over a given span, usually 12". A 6/12 pitch means that the 

roof drops 6" for each 12" measure horizontally down from roof 

rafters.

3.  Use roof opening chart (Figure 15) to determine correct opening 

length and flashing required.

4.  Remove shingles around opening measured. Cut out this section.
5.  Add next sections of pipe until end penetrates roof line. Check to see 

that proper clearances are maintained. Extend chimney by adding 

sections of double wall pipe until pipe is minimum of 30" above 

highest point of roof cutout. Termination and chimney must extend 

a minimum of 36" above highest point where it passes through 

roof.

Summary of Contents for Craftsman 42P2

Page 1: ...wood burning fireplace or for use with a vented gas log approved to ANS Z21 60 Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard An INNOVATIVE HEARTH PRODU...

Page 2: ...e voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace components doors air inlet system and damper control b Use of any component part not manufac...

Page 3: ...insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poiso...

Page 4: ...TIBLE MATERIAL ON FACE NO COMBUSTIBLE MATERIAL BELOW TOP SPACERS GAS LINE KNOCK OUT AIR KIT KNOCK OUTS GAS LINE STARTER SECTION 8DM PIPE INNER DIA OUTER DIA 15 KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE R...

Page 5: ...ace directly in front of this opening and slide unit back until nailing flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prep...

Page 6: ...ce if projection from front face falls within limits shown in Figure 6 Figure 4 Mantel Clearances to Combustible Material with Louver Figure 5 Mantel Clearances to Combustible Material without Louver...

Page 7: ...ower Source Receptacle Supplied Power Source Wiring Not Supplied Prewired Receptacle and Ground Sheet Metal Screws Figure 8 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of 1...

Page 8: ...ELBOW OFFSET 30E 12DMO 8DMR To clear overhead obstructions you may offset your chimney system using 30E 12DMO 8DMR 30 Offset return elbow A section or sections of chimney may be used between offsets a...

Page 9: ...e Detail B Ceiling Support Pipe 12S 8DM 30E 8DM Return Elbow 30E 8DM Return Elbow 30E 8DM Offset Elbow 30E 8DM Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR Offse...

Page 10: ...with Living Space Above Ceiling If area above is a living space install firestop below framed hole Figure 12 Elbow Offset OFFSET CHART WITH TRANSITION PIPE OFFSET RISE OFFSET RETURN ELBOW TRANSITION...

Page 11: ...Attic Space Above Ceiling If area above is an attic or insulated area install firestop above framed hole IMPORTANT NOTICE When penetrating a ceiling into an attic a firestop thimble 38FST or FST30 is...

Page 12: ...l use only noncombustible mortar or adhesive Storm Collar Installation SC1 Place storm collar over pipe and slide down until it is snug against open edge of flashing see Figure 17 Use SC1 for all roun...

Page 13: ...duit sleeve if using a raised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION VENTING INSTALLATION Continued connection see Figure 23...

Page 14: ...ARELEFT PARTLYOPEN GASANDFLAMEMAYBEDRAWNOUT OF THE FIREPLACE OPENING CREATING RISKS OF BOTH FIRE AND SMOKE WARNING Discontinue use of the appliance imme diately if doors are damaged and contact a qual...

Page 15: ...of place while fireplace was in transit These coverplatesmustbekeptintheproperlocationpriortousingthefireplace See Figure 26 For further operating guidelines instructions and warranty informa tion ple...

Page 16: ...tria US com 126662 01D 16 PARTS WOOD BURNING FIREPLACE MODELS Craftsman 42P2 Craftsman 42P3 9 12 25 20 30 17 8 1 5 21 2 34 18 11 14 3 37 13 22 10 6 31 7 38 36 35 28 29 15 27 26 16 16 27 4 32 33 19 23...

Page 17: ...ractory 1 12 See Page 18 Bottom Rear Refractory 1 13 See Page 18 Bottom Front Refractory 1 14 Firebox Support Leg 4 15 106687 02 Damper Can Collar 1 16 107839 01 Screen Rod 2 17 Firebox Top Assembly 1...

Page 18: ...hed Brass BD42P Platinum FAN KIT BK3 30 OFFSET AND RETURN 30E 8DM 30E 8HT 30E 12DMO 8DMR F1908 30E 12HTO 8HTR F2199 HERRINGBONE BRICK LINER WHITE Craftsman 42P3 F0713 F0716 Left 108169 01 Right 108170...

Page 19: ...8DM MESH SQUARE TOP TERMINATION WITH SLIP SECTION ETLO 8DM OUTSIDE AIR KIT FOR FLOOR INSTALLATION AK4F MESH ROUND TOP TERMINATIONS RT 8DM TR 8HT RTL 8DM AND RTL 8HT 1 FIRESTOP SPACER 3600FS 8DM 1 OUTS...

Page 20: ...n design materials specifications pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 126662 01 Rev D 10...

Reviews: