Fireplace Model Ladera™ CAT - Approved Venting Components manu-

factured by Security Chimneys

®

 only.

•   6” diameter chimney 

- AC (air cooled),  Secure Temp

®

 

 ASHT+ (or Nova Temp

®

 

 

) and Secure Temp

 

S-2100+ (or Nova Temp

 

).

•   6” diameter chimney for relining masonry chimneys 

- Tubinox

®

 chimney (or 

Projet

®

 SS), 6” diameter with adaptor for installation in a masonry chimney.

•   7” diameter chimney

 - Secure Temp ASHT+ (or NovaTemp ).

Fireplace Model  Ladera™ CAT - Approved Venting Components 

manufactured by DuraVent

®

 only.

•   6” diameter chimney 

- M&G DuraVent model DuraTech

®

 DTC

NOTES:

j

 

Nova Temp is equivalent to Secure Temp S-2100+

 

k

 

DuraTech

®

 DTC and Nova Temp are equivalent to Secure Temp ASHT+ 

l

 

This appliance is equipped with the ASHT Chimney Adaptor. When other 
chimney is used, a chimney adaptor for that chimney will be required.

m

 Chimney Adaptor (S-2100+ / ) for CANADA ONLY -  If you want to 

install a S-2100+ / chimney, an adaptor is available (6UCA).

AC Chimney is NOT recommended at elevations above 4,000 feet or in cold 
climates (climates where temperatures will fall below 32° F / 0° C).  When 
using AC chimney, an AC6SB starter section must be used before installing 
an elbow.  When an offset is needed immediately off the top of the fireplace, 
an elbow starter section, AC6SB30, is available.

o

Chimney Adaptor 7in - If you want to install a 7in ASHT / HT6103 chimney, an 

adaptor is available (6AW7).

Secure Temp

 

ASHT  1” High Temp. Insulated Stainless Steel Chimney 

6” I.D. and 8” O.D., Double-Wall Stainless Steel, Listed to 

CAN/UCL-S604, UL-103HT and CAN/ULC S629

Description

Part/Cat. No.

Lengths and Misc. Chimney Components 

8” length, 6” Dia.

6L8

12” length, 6” Dia.

6L12

18” length, 6” Dia.

6L18

24” length, 6” Dia.

6L24

36” length, 6” Dia.

6L36

48” length, 6” Dia.

6L48

Adjustable Length 12”, 6” Dia.

6LA

15º elbow, 6” Dia.

6E15

30º elbow, 6” Dia.

6E30

Rain Termination Cap, 6” Dia.

6CC

Spark Arrester Screen (universal spark arrester band)

PE

Wall Band

BM

Supports

Offset Support

SO

Roof Support

ST

Roof Brace

BS2

Firestops

Firestop

6BF

Radiation Shield

6RS

Insulated Attic Radiation Shield

6RSA2

Insulated Wall Radiation Shield

6RSM

Insulated Wall Radiation Shield, 30º

6RSMI30

Uninsulated Wall Radiation Shield, 30º

6RSM30

Attic Radiation Shield

ACRSA

Roof Flashings

Flat Roof Flashing

6FR

1/12  -  7/12  (5º - 30º)

6FAR

8/12  -  12/12  (30º - 45º)

6FBR

Storm Collar

6FC

Chimney Adaptors

Chimney Adaptor, 6” (S2100, HT6000)

6UCA

Chimney Adaptor, 6 to 7” (ASHT, HT6103)

6AW7

DuraTech DTC  1” High Temp. Insulated Stainless Steel Chimney 

6” I.D. and 8” O.D., Double-Wall Stainless Steel, Listed to 

CAN/UCL-S604, UL-103HT and CAN/ULC S629

Description

Part/Cat. No.

Lengths and Misc. Chimney Components 

8” length, 6” Dia.

6DTC-08SS

12” length, 6” Dia.

6DTC-12SS

18” length, 6” Dia.

6DTC-18SS

24” length, 6” Dia.

6DTC-24SS

36” length, 6” Dia.

6DTC-36SS

48” length, 6” Dia.

6DTC-48SS

Adjustable Length 12”, 6” Dia.

6DTC-12TASS

15º elbow, 6” Dia.

6DTC-E15SS

30º elbow, 6” Dia.

6DTC-E30SS

Rain Termination Cap, 6” Dia.

6DTC-VC 

Spark Arrester Screen (universal spark arrester band)

DTC-SA

Wall Band

DTC-WSU

Supports

Offset Support

DTC-RESU

Roof Support

DTC-RS

Roof Brace

DTC-XRB

Firestops

Firestop

6DTC-FS

Radiation Shield

6DTC-FRS

Insulated Attic Radiation Shield

6DTC-ISI

Insulated Wall Radiation Shield

6DTC-WTI

Insulated Wall Radiation Shield, 30º

6DTC-WRSI30

Uninsulated Wall Radiation Shield, 30º

6DTC-WRSI45

Attic Radiation Shield

6DTC-ISIA

Roof Flashings

Flat Roof Flashing

6DTC-FF

1/12  -  7/12  (5º - 30º)

 6DTC-F7

8/12  -  12/12  (30º - 45º)

6DTC-F12

Storm Collar

6DTC-SC

SECURITY CHIMNEYS

®

  AND DURAVENT

®

 - PARTS AND COMPONENTS LISTS

The components listed below must be ordered from Security Chimneys

®

 or DuraVent

®

.  Contact your Security Chimneys or 

DuraVent Distributor or Dealer for ordering information.  

450-973-9999
1-800-361-4909 (USA)
1-800-667-3387 (Canada)

1-800-835-4429

Security Chimneys

®

2125 Monterey, Laval, Quebec
Canada, H7L 3T6
securitychimneys.com

M&G DuraVent
877 Cotting Court, Vacaville, 
California, 95688
duravent.com

*These appliances are also approved for use with DuraTech - galvanized. 
Contact your DuraVent Distributor or Dealer for ordering information. 

Summary of Contents for 900880-00

Page 1: ...rds ULC S610 and UL 127 Report 14 181 EPA Cert No 111 17 WARNING The fireplace cannot be operated without a door Consult your dealer to select the correct replacement door The fireplace is equipped wi...

Page 2: ...that are of suf ficient length to be blown in front ofanopenflamewhenthewindow is opened Keep any combustible furniture materials or decorative pillows at least 48 1219 mm from the front fireplace op...

Page 3: ...era CAT fireplace is NOT intended for use with a gas log set Do not use a fireplace insert or any other product with this fireplace unless it is specified by IHP for use with this appliance Failure to...

Page 4: ...thecatalyticcombustor Openingthe CAT bypass damper control increases the draft allowing the unit to achieve proper operating temperatures during a cold start up It also provides more draft to prevent...

Page 5: ...tent of the wood For instance a long chimney will necessitate closing the damper more To obtain the proper combustion closethedampercompletely then open it about 1 4 to 1 2 6 4mm to 13mm Two medium si...

Page 6: ...esabout15 30minuteswiththeCATbypass opened to reach proper light off temperatures for the catalytic combustor Step 5 Set the primary control to the desired burn level The fireplace will automatically...

Page 7: ...sture content can exceed 80 which must be reduced to less than 20 Wood properly seasoned is then capable of generating the heat the stove was designed to provide Greenwooddoesnotburneasily Attemptingt...

Page 8: ...remove the combustor Remove dust accumulation after chimney sweep and put the combustor back in place CATALYTIC COMBUSTOR This fireplace is designed with a catalytic com bustor which will reduce pollu...

Page 9: ...rewsandslidingthehingebracketupordown to create better seal and then retightening Catalyst Bypass linkage replacement see Figure 9B Toolsrequired 2 9 16 wrenches 2square drive bit driver Withcatalystb...

Page 10: ...ombustorProblem Thermal Cracking ThiscombustordoesNOTexperiencethermalcracking Notap plicable Appliestohoneycombcombustorsonly CombustorProblem CombustorPeeling ThiscombustordoesNOTexperiencecombustor...

Page 11: ...the ashes are cold 24 to 48 hours after the fire is out Do not leave the ashes in the house as they give off carbon monoxide and other toxic gases Figure 10 WARNING DisposalofAshes Ashesshould be plac...

Page 12: ...dealer see Replacement Parts Page 28 DO NOT OPERATE THE UNIT WITH CRACKED OR BROKEN GLASS Glass Cleaning TheLaderaCATfireplaceisdesignedtokeeptheglasscleanundernormal operating conditions If the Lade...

Page 13: ...replace is determined by considering the location of windows doors and the traffic flow in the room where the fireplace is located allowing space in front of the unit for the hearth exten sion and the...

Page 14: ...must cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with at least a 1 2 inch of non combustible material tile marble stone etc See Figure 15 CO...

Page 15: ...phs are not to scale consult installation instructions Product designs materials dimensions specifications colorsandpricesaresubjecttochangeordiscontinu ance without notice Allframingdimensionscalcula...

Page 16: ...Fireplace Side Mantel Rock Board or Other Noncombustible Facing 39 990 mm Drywall 2 x 3 Min 51mm x 76mm Spacer Mantel and Facing Side View Rock Board or Other Noncombustible Facing Drywall Figure 17...

Page 17: ...mbustible Facing Drywall 2 x 3 Min Rock Board or Other Spacer Figure 22 A wall on off switch must be installed to control theblower Anoptionalheatswitchandvariable speed control are available see Page...

Page 18: ...front of fireplace must be non combustible below this area u NOTES Seal the top and both sides of the roof flashing with waterproof caulk ing The gap between the vent pipe and a vertical firestop shal...

Page 19: ...the base of the fireplace C The fresh air must come from outside the house The air intake must not draw air from the attic basement or garage D The air intake should be installed where it is not like...

Page 20: ...feet 3 7 m In altitude add 18 450 mm to the chimney for every 2 000 feet 600 m above sea level 6 All chimney installations must include at least one support Re ducing the amount of chimney weight on t...

Page 21: ...he joint between the roof and the flashing with roofing pitch see Figures 34 and 35 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to...

Page 22: ...4 Use a plumb bob to line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From b...

Page 23: ...6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 2432 mm...

Page 24: ...ed wall radiation shield since it will maintain the home s thermal barrier Figure 39 Drywall Insulated Wall Angel Wall Radiation Shield Insulated Available from Security Chimneys Available from DuraVe...

Page 25: ...AND MULTIPLE TERMINATIONS For the purpose of this manual a chimney chase is considered a part of the chimney system rather than part of a building The termination must be placed a minimum of 18 460 mm...

Page 26: ...rily install the ASHT elbow on the top of the fireplace and using a level mark with an oval the location where the flue liner will enter the masonry chimney 2 In the middle of the oval drill a hole in...

Page 27: ...er EPA certification If installed this appliance no longer qualifies for EPA certification Check with local authorities having jurisdiction for requirements in your area Central Forced Air Kit Accesso...

Page 28: ...tory 2 pieces PR SR2829 Secondary air tubes set of three F3540 Fireplace Ashlip F3551 Fireplace Front Bottom F3550 Top Front Insulation Protector F3554 Gasket Catalyst F3552 Catalyst Replacement Cartr...

Page 29: ...fset Support SO Roof Support ST Roof Brace BS2 Firestops Firestop 6BF Radiation Shield 6RS Insulated Attic Radiation Shield 6RSA2 Insulated Wall Radiation Shield 6RSM Insulated Wall Radiation Shield 3...

Page 30: ...Relining A Masonry Chimney 6 Diameter Listed to ULC S635M UL 1777 and ULC S640M at 2100 F Description Cat Part No 6 Length 6 Dia 6LL6 6LL6 12 Length 6 Dia 6LL12 6LL12 24 Length 6 Dia 6LL24 6LL24 36 Le...

Page 31: ...ES AVEC LE FOYER DOIVENT TRE HO MOLOGU ES VOIR LA LISTE DANS LE MANUEL D INSTALLATION REMPLACER LA VITRE AVEC UN VERRE C RAMIQUE DE 5mm D PAISSEUR POUR UNE UTILISATION S CURITAIRE INSTALLER CONFORM ME...

Page 32: ..._______________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ___________________...

Page 33: ...r may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning dry seaso...

Page 34: ...NT PARTS See Page 28 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be ship...