www.Astria.US.com
126754-01B
5
D) The burning of anything other than the type of
gas approved for use in this gas appliance.
The installation must conform with local
codes or, in the absence of local codes, with
the current
National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
This fireplace complies with the National
Safety Standards and is listed and tested by
PFS Corporation to
ANSI Z21.50/CSA 2.22
standard as vented gas fireplace.
NOTICE: Decorative product not
for use as a heating appliance.
WARNING: Installation of this
appliance should be done by
a qualified service person well
trained in the installation of such
appliances. You will also need a
building permit from your local
Building and Safety Commis-
sioner before installing this appli-
ance; otherwise your insurance
co. may not cover this appliance.
Figure 1 - Possible Locations for
Installing Appliance
INTERNAL WALL
INSTALLATION
CORNER
INSTALLATION
FULL
PROJECTION
INSTALLATION
FLUSH
INSTALLATION
CAUTION: Do not connect
appliance before pressure test-
ing gas piping. Damage to gas
valve may result and an unsafe
condition may be caused.
The appliance and it’s individual shutoff valve
must be disconnected from the gas supply
piping system during any pressure testing of
that system at test pressures in excess of 1/2
psi (3.5 kPa).
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psi
(3.5 kPa).
For the purpose of input adjustment two
pressure taps (for IN and OUT pressures)
are provided on the gas control valve for test
gauge connections to the appliance.
INTRODUCTION
Continued
SELECTING LOCATION
To determine the safest and most efficient
location for your appliance, you must take
into consideration the following guidelines:
1. The location must allow for proper clear
-
ances (see
Clearances,
page 7).
2. Consider a location where heat output
would not be affected by drafts, air con
-
ditioning ducts, windows or doors.
3. A location that avoids the cutting of joists
or roof rafters will make installation easier.
Figure 1 shows a plan view of a few com
-
mon locations.
Flush installations
are recommended where
living space is limited or at a premium and
since the space required to enclose the ap
-
pliance would be located beyond an outside
wall, this would also reduce the cutting of
joists, roof rafters and such. Check local
codes for any restrictions.
Projected installations
can extend any
distance into the room. A projection may
be ideal for a new addition on an existing,
finished wall.
Corner installations
make use of space
that may not normally be used and provides
a wider and more efficient range for radiant
heat transference.
Internal wall installations
provide a discreet
option for room separation and can also be
ideal as an addition to an existing wall.
f i r e - p a r t s . c o m