VENTING INSTALLATION

at 60° or greater. The total vertical height in 

this example represents the minimum height 

of 8 feet and therefore the allowable lateral 

is  6  feet  when  the  75%  rule  applies.  If  the 

lateral  length  must  exceed  75%  then  the 

system must be sized in accordance with the 

Category I venting tables.

Example 2:

 Shows a multiple offset each at 

45° of inclination. Multiple offsets are permit

-

ted if they do not exceed 45° of inclination. The 

total lengths of the two offsets are not required 

to meet the 75% allowable rule.

Example 3:

 Shows a single offset at 45° of 

inclination and therefore the lateral length at 

10 feet of offset does not have to meet the 

75% rule.
In each case the offsets must be supported 

and  firestops  must  be  positioned  wherever 

the vent must pass through a sub-floor, ceiling 

joist or an attic overhang. The vent pipe must 

terminate vertically into a listed type vent cap 

and extend a sufficient height through an ap

-

proved roof flashing, roof jack or a roof thimble 

(38FST recommended). At all points the listed 

clearances must be maintained.
Vent  terminations  must  be  located  in  ac

-

cordance with height and proximity rules of 

NFPA No. 54. These rules apply to vents at 

12" diameter or less and require a minimum 

height in accordance with the roof pitch and 

a  minimum  of 8  ft. distance  from a  vertical 

wall or obstruction (see Figure 11, page 11).

A B-type venting system must be connected 

to  appliance  for  venting  to  the  outside  of 

building.

The following section is provided as a guide 

to a standard B-type vent installation.
Standing codes requirements concerning B-

type vent installations may vary within your 

state,  province  or  local  codes  jurisdiction. 

Therefore, it is recommended that you check 

with  your  local  building  codes  for  specific 

requirements or in absence of local codes, 

follow Section 7.0 of the current 

National Fuel 

Gas Code ANSI Z223.1/NFPA 54

.

This  gas  appliance  must  be  vented  to  the 

outdoors only and may not be terminated into 

an attic space or into a chimney flue servicing 

a solid-fuel burning appliance.
This  appliance  may  be  vented  through  a 

manufactured chimney system or a masonry 

chimney using a B-vent adapter or a chim

-

ney  liner  system  if  all  are  listed,  inspected 

and approved by local codes and/or building 

authorities.
The examples shown in Figure 10, page 11 

are  typical  of  most  B-vent  installations  and 

codes practices.

Example 1:

 Shows the minimum allowable 

system height and lateral offset for a 60° or 

greater inclination. Code specifies that offsets 

at  60°  or  greater  are  considered  horizontal 

and  must  follow  the  75%  rule  for  lateral  to 

total  vertical  system  height.  Codes  also  al

-

low only one offset in the total system when 

f i r e - p a r t s . c o m

Summary of Contents for Mission36TEN

Page 1: ...ty damage personal injury or death AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie ou d explosion ou pour viter tout d...

Page 2: ...e absence of these codes complies with the National Fuel Gas Code ANSIZ223 1 NFPA 54 State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas...

Page 3: ...nce is not convertible for use with other gases unless a certified kit is used 2 For propane LP fireplace do not place propane LP supply tank s inside any structure Locate propane LP supply tank s out...

Page 4: ...Shrink wrapped on cardboard Three 3 plastic bags containing lava rock pan and ember materials Rear Log Remove two plastic quick ties from around burner and grate Grate Stand Lift off of burner pan Ch...

Page 5: ...closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psi 3 5 kPa For the purpose of input adjustment two...

Page 6: ...5 WC 2 66 kPa 10 5 WC 2 66 kPa Orifice Size 30 29 GAS RATING PROPANE LP Max Input Rating 40 000 Btu Hr 45 000 Btu Hr Manifold Pressure 10 WC 2 49 kPa 10 WC 2 49 kPa Minimum Supply Pressure 11 WC 2 74...

Page 7: ...e components in relation to fireplace opening Spacer 3 7 6 cm 1 1 2 3 8 cm Max B 6 15 2 cm A 12 22 9 cm Combustible Materials Header Figure 5 Mantel Clearances Side View Cross Section 1 1 2 3 8 cm Max...

Page 8: ...eenthemate rial used and the face is caulked withanoncombustiblecaulking Figure 7 Rough Opening for Installing in Wall B C A Figure 8 Corner Installation Guidelines A B C D These Dimensions Allow for...

Page 9: ...line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP CLEAR...

Page 10: ...um height in accordance with the roof pitch and a minimum of 8 ft distance from a vertical wall or obstruction see Figure 11 page 11 A B type venting system must be connected to appliance for venting...

Page 11: ...lation It is not recommended that this appliance be common vented with an existing gas burning appliance However if it becomes necessary to common vent this appliance the venting system must be sized...

Page 12: ...l Receiver Extension Cord Ignition Module Plug NOTICE This appliance is equipped with a vent safety shutoff switch which will shut down the appliance in the case of aventingproblem Donotbypass thevent...

Page 13: ...black iron gas line be routed from the gas source through a sediment trap shown in Figure 18 and into appliance Once connected through appliance a flexible gas line may be used for ease of installatio...

Page 14: ...aks can be detected and corrected Donotuseanopenflameforleak testing and do not operate any appliance if a leak is detected INSTALLATION Continued Complete your gas installation by connect ing incomin...

Page 15: ...on left of log 2 see Figure 25 Rest lower end of log 5 on grate as shown in Figure 26 6 Insert lower end of log 6 between first two grate fingers as shown in Figure 26 and position upper end of log 6...

Page 16: ...upper end of log 5 into notch on top inner right of log 1 see Figure 29 Rest lower end of log 5 on middle grate finger as shown in Figure 30 6 Place log 6 into notch on top right of log 1 see Figure...

Page 17: ...Between Appliance and Framing INSTALLING OPTIONAL GLASS DOOR ACCESSORY CAUTION Use only glass doors certified for use with this appliance Note Glass door may be heavy for some individuals If this is...

Page 18: ...ide pins are free of frame rail see Figure 35 CAUTION Always operate the appliance with the doors ei ther fully opened or fully closed Operating the appliance with the doors partially open can re sult...

Page 19: ...justment Screw FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A T...

Page 20: ...o press ON OFF buttons on hand held remote control unit for up to 3 seconds to assure proper operation 2 Press the ON OFF button to turn burner on and off Check pilot flame pattern and burner flame pa...

Page 21: ...n cleaning is complete Burner and controls should be cleaned with compressed air to remove dust dirt or lint Use a vacuum cleaner or small soft bristled brush to remove excess dust dirt or lint LOGS I...

Page 22: ...at 1 800 655 2008 When calling please have your model and serial numbers of your fireplace ready You can also visit INNOVATIVE HEARTH PRODUCTS s web site at IHP US com IMPORTANT NOTICE Young children...

Page 23: ...MEDY 1 Check to see if you have gas supply and that equipment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air out of lines If after repeated attempts appliance does...

Page 24: ...as low fuel supply 3 Gas leak See Warning statement at top of page 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas lea...

Page 25: ...ed Brass Finish BD42P 42 Platinum Finish FIXED GLASS DOORS FD36 36 Black Finish FD36B 36 Brushed Brass Finish FD36P 36 Platinum Finish FD42 42 Black Finish FD42B 42 Brushed Brass Finish FD42P 42 Plati...

Page 26: ...0858 F0860 AND F0862 MISSION42TEN CATALOG NUMBERS F0864 F0866 AND F0868 51 21 1 10 11 6 50 50 22 3 8 20 9 52 13 43 14 45 48 44 40 23 4 39 17 2 42 41 9 54 54 46 19 47 7 53 53 47 18 5 16 12 15 52 33 31...

Page 27: ...1 25 11165 11165 Screw 10 x 5 8 2 26 107796 01 107796 02 Grate Assy 1 27 107742 01 107742 02 Burner Pan 1 28 107795 01 107831 01 Burner Tube 1 29 107748 01 107748 01 Burner Brckt 1 30 107985 01 107985...

Page 28: ...1 108166 01 108171 01 Rear Refractory Herringbone 1 15 106661 01 107818 01 Bottom Rear Refractory Std Brick 1 108167 01 108172 01 Bottom Rear Refractory Herringbone 1 16 106662 01 107820 01 Bottom Fr...

Page 29: ...AND F0862 KEY NO PART NO DESCRIPTION QTY 107999 01 Log Set 1 108724 01 Right Front 9 Split Log 1 2 901098 01 Rear Log 1 3 108720 01 Top Right Log 11 3 4 1 4 108721 01 Top Right Log 16 1 5 108722 01 T...

Page 30: ...Log 11 1 2B 108839 01 Right Front Log 15 3 4 Round 1 3 108722 01 Top Left Log 13 1 2 Y Log 1 4 108838 01 Inside Top Left Log 15 3 4 Split 1 5 108721 01 Inside Top Right Log 16 1 6 108720 01 Top Right...

Page 31: ...r acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Pro...

Page 32: ...arranty verification P126754 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications pricesandalsotodiscontinuecolors stylesandpr...

Reviews: