Astria Fireplaces Blackstone Series Installation And Operation Instructions Manual Download Page 12

Astria.us.com

901046-00NC

12

EFFECTIVE HEIGHT

OF TERMINETION CAP 

EFFECTIVE HEIGHT

OF TERMINETION CAP 

EFFECTIVE HEIGHT

OF TERMINETION CAP 

EFFECTIVE HEIGHT

OF TERMINETION CAP 

14.5 FT 

(4.42 m)

MINIMUM 

HEIGHT

30E-8DM

30E-8DM

UP TO 

6 FT (1.83 m)

MAX.

UP TO 

6 FT (1.83 m)

MAX.

14.5 FT 

(4.42 m)

MINIMUM 

HEIGHT

MAX. HEIGHT

50 FT (15.24 m)

ANY SYSTEM

MIN. HEIGHT

22 FT (6.71 m)

WITH 2 ELBOW SETS

MAX. HEIGHT 

OF 50 FT. (15.24 m)

VENTING INSTALLATION  

Continued

CHASE INSTALLATIONS

Instructions for chase installations are included with chase style ter-

mination chosen. In a multiple chase installation, be sure to provide 

adequate distance between terminations to prevent smoke spillage 

from one termination to another. We suggest that terminations be 

separated at least 24", center to center and stacked at a vertical height 

difference of 18" (see Figure 18).

Note:

 If a decorative shroud is to be installed, contact manufacturer 

for specifications.

Figure 18 - Multiple Chase Installation

10

'

(3.05 m) 

10

'

(3.05 m) 

2

(0.61 m)

Min.

2

(0.61 m) Min.

3

(0.92 m)

Min.

3

(0.92 m)

Min.

Level of 

Flue Gas Outlet 

Figure 19 - 10 Foot Rule

10 FOOT RULE

All flue gas outlet chimney terminations must extend a minimum of 

3 feet in height above highest point where it passes through roof and 

must be at least 2 feet above highest point of the roof that is within 

a horizontal distance of 10 feet (see Figure 19).

FINISHING FIREPLACE

Combustible materials, such as wallboard, sheet rock, drywall, ply-

wood, etc., may make direct contact with sides and top around fire-

place face. It is important that combustible materials do not overlap 

face itself. Brick, glass, tile or other noncombustible materials may 

overlap front face provided they do not obstruct essential openings 

such as louvered slots. When overlapping with a noncombustible 

facing material, use only noncombustible mortar or adhesive.

Figure 20 - Typical Residential Installations

24" (610 mm)Min.

24" (610 mm)Min.

18" 

(458 mm)

Min. Typ.

Summary of Contents for Blackstone Series

Page 1: ...iction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autorit comp tente comme le servi...

Page 2: ...red or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local building...

Page 3: ...gnificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CAR...

Page 4: ...RD NOT LESS THAN 12 305 mm TO PERPENDICULAR SIDEWALL 0 0 MM TO BOTTOM 12 305 mm EACH SIDE GAS LINE KNOCK OUT GAS LINE KNOCK OUT RIGHT SIDE LEFT SIDE AIR KIT KNOCK OUT 8 1 4 210 mm 8 1 4 210 mm 25 3 8...

Page 5: ...langes touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be placed between hearth extension not...

Page 6: ...ening of fireplace NFPA 211 Section Clearance from Combustible Material Mantels or any other combustible material may come up to side edge of black metal face of fireplace if projection from front fac...

Page 7: ...ugh a sidewall AK4 See Figure 7 for instruction of operating air kit CAUTION Combustion air inlet ducts shall not terminate in attic space The maximum height for the air vent can not exceed 3 feet bel...

Page 8: ...20 feet must be supported USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combinations of 12 18 24 36 and 48 length of double wall pipe see offset chart page 9 and Figure 9 pag...

Page 9: ...turn Elbow Return Elbow Return Elbow Return Elbow Offset Elbow Offset Elbow Offset Elbow Offset Elbow Offset Elbow 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m Ceiling...

Page 10: ...oof Pitchisthedistancetheroofdrops overagivenspan usually12 A6 12pitchmeansthattheroofdrops 6 for each 12 measure horizontally down from roof rafters 3 Use roof opening chart Figure 14 page 11 to dete...

Page 11: ...ireplace system must be terminated with listed round top or chase terminations In any case refer to installation instructions supplied with termination Terminations approved for this fireplace are RT...

Page 12: ...d is to be installed contact manufacturer for specifications Figure 18 Multiple Chase Installation 10 3 05 m 10 3 05 m 2 0 61 m Min 2 0 61 m Min 3 0 92 m Min 3 0 92 m Min Level of Flue Gas Outlet Figu...

Page 13: ...desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap and water solution to all connections and joints...

Page 14: ...ce with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if too large a fire is built or if combustion air gate is not completely open The following ti...

Page 15: ...in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions provided with the shroud NOTICE The...

Page 16: ...1046 00NC 16 11 27 23 23 22 24 10 14 25 4 17 3 2 1 18 5 20 28 12 7 15 9 16 13 8 26 6 19 21 PARTS WOOD BURNING FIREPLACE MODELS Blackstone42RWS Blackstone42LWS MODEL CAT NO Blackstone42RWS F2539 Blacks...

Page 17: ...9 Wrapper Bottom 1 10 Front Face Weldment Smooth 1 Front Face Weldment Louvered 1 11 See Page 18 Left Side Brick Liner 1 12 See Page 18 Rear Brick Liner 1 13 See Page 18 Right Side Brick Liner 1 14 S...

Page 18: ...n any of these parts Never use substitute materials not ap proved by IHP Use of non approved parts can result in poor performance and safety hazards 1 2 4 3 6 5 REFRACTORY STAIN KITS Use the refractor...

Page 19: ...Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 D...

Page 20: ...AND SLIP SECTION F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TER...

Page 21: ...ns inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the appliance...

Page 22: ...he best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of the un...

Page 23: ...r propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperature...

Page 24: ...0 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your loc...

Reviews: