24
Name
Holding
Registers
Input
Registers
Coils
Inputs
Description
ID_Address
0x00
This parameter is the address of the Lumiplus, by default it is set
to 0x30. If the installation has more than one device connected in
the bus, is necessary to change the ID_Adress of the device before
connecting another one.
This parameter determinates the Baud rate selection. There are 6
possible configurations to choose:
Factory setting: 0. 9600, 8E1
Supported values: 1. 19200, 8E1
2. 9600, 8N2
3. 19200, 8N2
4. 9600, 8N1
5. 19200, 8N1
ID_Manufacturer_hi
0x02
This parameter indicates the high byte that represents the
Manufacturer code.
ID_Manufacturer_lo
0x03
This parameter indicates the low byte that represents the
Manufacturer code.
ID_Product_code_hi
0x04
This parameter indicates the high byte that represents the
Product code.
ID_Product_code_lo
0x05
This parameter indicates the low byte that represents the Product
code.
Reserved
0x06
Reserved.
HW_Version
0x07
This parameter indicates the
Hardware Version of the Lumiplus.
SW_Version
0x08
This parameter indicates the
Software Version of the Lumiplus.
MODEL_Serie_hi
0x09
This parameter indicates the high byte of the Serial Number.
MODEL_Serie_lo
0x0A
This parameter indicates the low byte of the Serial Number.
MODEL_Production_hi
0x0B
This parameter indicates the high byte of the production batch.
MODEL_Production_low
0x0C
This parameter indicates the low byte of the production batch.
COM_Setup
0x01