Astraada DRV-28A inverters
-215-
Function
code
Name
Description
Default Modify
1: Method 2
Tens place:
0: Reserved
1: Reserved
P12 group––Parameters of motor 2
P12.00
Type of motor 2
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
◎
P12.01
Rated power of AM
2
0.1–3000.0kW
Model
depended
◎
P12.02
Rated frequency of
AM 2
0.01Hz–P00.03 (Max. output frequency)
50.00Hz
◎
P12.03
Rated speed of AM
2
1–60000rpm
Model
depended
◎
P12.04
Rated voltage of
AM 2
0–1200V
Model
depended
◎
P12.05
Rated current of AM
2
0.8–6000.0A
Model
depended
◎
P12.06
Stator resistance of
AM 2
0.001–65.535Ω
Model
depended
○
P12.07
Rotor resistance of
AM 2
0.001–65.535Ω
Model
depended
○
P12.08
Leakage inductance
of AM 2
0.1–6553.5mH
Model
depended
○
P12.09
Mutual inductance
of AM 2
0.1–6553.5mH
Model
depended
○
P12.10
No-load current of
AM 2
0.1–6553.5A
Model
depended
○
P12.11
Magnetic saturation
coefficient 1 of iron
core of AM 2
0.0–100.0%
80%
○
P12.12
Magnetic saturation
coefficient 2 of iron
core of AM 2
0.0–100.0%
68%
○
P12.13
Magnetic saturation
coefficient 3 of iron
core of AM 2
0.0–100.0%
57%
○
P12.14 Magnetic saturation 0.0–100.0%
40%
○
Summary of Contents for AS28DRV4011A