Manual switching amplifier BS 805
Page 4 of 12
Subject to technical change 10/2017
A.S.T. Angewandte SYSTEM-TECHNIK GmbH Dresden
3.1. Adjustments
3.2. Button
4. LED- display
Switch
Function
Strain gauge switching amplifier
BS 805.01
BS 805.11
BS 805.21
>V<
16 mA - characteristic value setting
0,8 … 2,5mV/V
>0<
4mA - setting to zero point
-0,5 … +0,5mV/V
SP1
Switching point setting/ switching range
4....20mA
SP2
Switching point setting/ switching range
4....20mA
D
Switching delay for SP2
0 ... 5sec.
Switch
Function
T1
Additionally function see Point 5
LED
Normal operations
Error (flashing display)
U1
<4mA
incorrect code enter
U2
4mA < I < 8mA
U4
8mA < I < 12mA
-
U8
12mA < I < 16mA
-
U16
16mA < I < 20mA
-
U32
20mA < I
-
U78
Ready for operation
break or
short in sensor wire
blinks once
Current level exceeded tEX
for BS805.y1 bridge resistance < 300
for BS805.y1 sensor current > 40mA
blinks twice
Current level not attained tEX
Only for BS805.y1 bridge resistance > 1000
blinks 3 times
Input signal exceeded
for BS805.y1 bridge signal = > +2.5mV
blinks 4 times
Input signal not attained
for BS805.y1 bridge signal < -2.5mV/V
blinks 5 times
Bridge median voltage exceeded
only for BS805.y1 (–SI zu –EX >2.2V)
blinks 6 times
Bridge median voltage not attained
only for BS805.y1(–SI zu –EX <1.2V)
U21
SP1 current on
-
U22
SP2 current on
-