Manual switching amplifier BS 805 

Subject to technical change 10/2017 

Page 1 of 12

 

A.S.T. Angewandte SYSTEM-TECHNIK GmbH Dresden 

 

1.  Safety Instructions 

 

 

ATTENTION!  

Any non-compliance with these safety precautions may result in severe damage to property and health!.

 

 

 

ATTENTION!  

These Operating Instructions explain the installation, bringing into service, and operation of the type BS 
805.0x  amplifier.  It  is  assumed  that  every  action  is  taken  by  qualified  staff  only  who  have  adequate 
knowledge in the fields of measuring and control engineering. 
The  equipment  must  be  installed  and  attached  under  adherence  to  of  the  current  DIN  and  VDE 
standards. 

 

 

ATTENTION!  

The type 

BS 805.01

 Strain-Gauge amplifier has been designed to the purpose of amplifying the output 

signals of sensors with

 metal-foil strain gauges

, preferably force transducers. 

The type 

BS 805.02

 has been designed to the purpose of amplifying the output signals of sensors with 

standard signal 4-20mA

, preferably force transducers. 

Any other application is regarded contrary to intended usage.  
The 

BS  805.0x

  may  not  be  used  as  exclusive  means  for  the  prevention  of  dangerous  conditions  at 

machines and plants. 
Make sure that any erroneous setting or malfunction of the unit or its break-down cannot cause damage 
or be a risk to the staff or other persons.

 

 

 

 

Summary of Contents for BS 805.01

Page 1: ...5 Original Manual Strain gauge switching amplifier BS 805 01 BS 805 11 BS 805 21 A S T Angewandte SYSTEM TECHNIK GmbH Dresden Marschnerstraße 26 01307 Dresden phone 03 51 44 55 30 fax 03 51 44 55 555 www ast de vertrieb dd ast de ...

Page 2: ......

Page 3: ...ED display 4 5 Function of key T1 5 5 1 Code table 5 5 2 Example 6 6 Information on Performance Level PLc in accordance with DIN EN 13849 1 6 6 1 Classification of Type Series Switching Amplifier BS 805 6 6 2 Error detection in operation with a connected sensor 6 6 3 Other functions 7 7 Commissioning 7 7 1 Mounting 7 7 2 Connection 7 7 3 Signal settings 8 7 4 Control of settings 9 8 Specification ...

Page 4: ......

Page 5: ...t must be installed and attached under adherence to of the current DIN and VDE standards ATTENTION The type BS 805 01 Strain Gauge amplifier has been designed to the purpose of amplifying the output signals of sensors with metal foil strain gauges preferably force transducers The type BS 805 02 has been designed to the purpose of amplifying the output signals of sensors with standard signal 4 20mA...

Page 6: ...µC T1 SP2 1 T1 t Force transducer Power supply A Standard signal output 5 4 20mA BS 805 11 Force transducer Standard signal output Power supply 230VAC 0 V SI EX SI EX 1 X1 EX 2 EX 3 SI 4 SI 5 4 20mA 6 0mA SP1 1 X10 1 NC1 2 COM1 3 NO1 X11 1 NC2 2 COM2 3 NO2 X5 1 L 2 N µC T1 SP2 1 T1 t 3 PE 7 8 A X12 1 PE1 2 PE2 3 Operating elements BS 805 01 Strain gauge switching amplifier Supply voltage 10 30VDC ...

Page 7: ...ifier Supply voltage 230VAC case IP65 die cast Setup V T1 LED i O U78 LED SP1 SP1 Cable gland M20 D 6 12mm Cable gland M16 D 5 10mm BS 805 21 Strain gauge switching amplifier Supply voltage 10 30VDC case IP40 DIN rail V T1 LED i O U78 LED SP1 SP1 SH SH PE PE EX EX NC1 NC2 COM1 COM2 NO1 NO2 SI SI 4 20 mA 0mA 24V Schaltverstärker BS 805 SP1 V 20 Power T1 mA 0 4 SP2 D ...

Page 8: ...l operations Error flashing display U1 4mA incorrect code enter U2 4mA I 8mA U4 8mA I 12mA U8 12mA I 16mA U16 16mA I 20mA U32 20mA I U78 Ready for operation break or short in sensor wire blinks once Current level exceeded through EX for BS805 y1 bridge resistance 300 for BS805 y1 sensor current 40mA blinks twice Current level not attained through EX Only for BS805 y1 bridge resistance 1000 blinks ...

Page 9: ...2mA 251 Relay 1 and Relay 2 Reset at normal 255 Constant current 4 0 311 mA 12 0 312 20 0 313 0 2 344 0 5 343 1 0 331 2 0 332 3 0 333 4 0 334 5 0 335 0 2 341 0 5 342 1 0 321 2 0 322 3 0 323 4 0 324 5 0 325 Example 16 8 12 0 5 0 0 2 312 335 341 Current to reset Back to measuring mode 355 or voltage supply 10 30VDC to break Element Function Code Basic setting only BS 805 01 SP1 normal without hyster...

Page 10: ...on of exposure F2 Frequent to permanent and or short duration of exposure Possibility of preventing the hazard P P1 Possible under certain conditions P2 Hardly possible 6 2 Error detection in operation with a connected sensor The Switching Amplifier BS805 identifies the following errors Sensor monitoring Wire breakage also on single core of sensor cable Short circuit on any number of cores of sens...

Page 11: ... designed for mounting on a standard rail 7 2 Connection The cables for the sensor the supply voltage and the signal output are to the strip_X1 to attach Protective conductors of the discharges for the switching signals are to be attached absolutely to the strip_X12 PE Standard contacting of cable shield to contact clip cable jacket and shield dismantle cut around the cable jacket 15mm behind the ...

Page 12: ...ockwise Red LED remains on Extend zeroing range with functions 43x Whenever the appliance detects an error refer to point 4 LED display LED U78 an output current of 2mA is always generated and the red LED U1 lights up A note can be made of the test signal Code No Switch on 422 Switch off 423 for documentation purposes later on For this purpose de charge the sensor measure the output signal and con...

Page 13: ...14mA 4mA 18mA Turn SP2 adjuster clockwise up to the very point where relay 2 just about switches over Switch to measuring mode applying function 355 When geared to the standard setting the relay de energises as soon as the switching point is attained The function 2x2 reverses the switching action and allows the relay to energise when the switching point is attained 7 4 Control of settings The sign...

Page 14: ...pping Switching voltage switching current Normal Invers with T1 mA mA Sec LED display for Switching status 4 22 0 05 0 1 0 5 1 2 0 5 250V 6A adjustable Accuracy Reproducibility the settings Linear error plus hysteresis Temperature effect full load 20mA Temperature effect zero 4mA v E v E v E 10K v E 10K 0 5 0 2 0 2 0 2 Power supply Nominal voltage Current consumption A LED display for stand by 10 ...

Page 15: ...Manual switching amplifier BS 805 Subject to technical change 10 2017 Page 11 of 12 A S T Angewandte SYSTEM TECHNIK GmbH Dresden 9 EC Declaration of Conformity ...

Page 16: ...Manual switching amplifier BS 805 Page 12 of 12 Subject to technical change 10 2017 A S T Angewandte SYSTEM TECHNIK GmbH Dresden ...