For technical support contact Yale
®
at 800.438.1951 or [email protected]
An ASSA ABLOY Group brand
8
80-9470-0162-000 10/18
Delayed Egress
Installation Instructions
Exit Device
Copyright © 2018, ASSA ABLOY Access and Egress Hardware Group, Inc.
All rights reserved. Reproduction in whole or in part without the express written
permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
6
Wiring Layout and Jumper Settings
Pin Number
Input/Output
Wire Color
Description
Pin Number
1
Input
Black
24VDC Power Supply (-Circuit Ground)
1
2
Input
Red
24VDC Power Supply (+Positive)
2
3
Input
Brown
Remote Reset Input
- Momentary input from
key switch, pushbutton, etc. Will release device
for 20 seconds for egress or ingress and also
reset device when in bypass or alarmed state.
7
4
Input
Yellow
Remote Bypass Input
- Momentary input from
key switch, pushbutton, etc. Will maintain device
in an unlocked state for normal device operation.
Device must be rearmed by resetting from
remote reset on device.
8
5
Output
Orange
Secure Relay Output
- Normally closed (NC)
contact that changes to normally open (NO)
when device has released.
5
6
Output
Blue
Secure Relay Output
- Normally open (NO)
contact that changes to normally closed (NC)
when device has released.
6
7
Output
Green
Alarm Relay Output
- Normally open (NO)
contact that changes to normally closed (NC)
when device alarm cycle has been activated.
4
8
Output
White
Alarm Relay Output
- Normally closed (NC)
contact that changes to normally open (NO)
when device alarm cycle has been activated.
3
J2
Connector
ElectroLynx
Connector
NOTE: • Pins 5-8 are negative (-) outputs. Use with LEDs and audibles (horns, sirens, etc.).
See wiring diagrams for details.
• Cap all unused wires with enclosed wire nuts.
Figure 7
1. (J5)
Nuisance Delay (Figure 7)
Jumper on - 3 seconds (Default)
Jumper off - immediate alarm
2. (J8)
Reset Delay (Figure 7)
Jumper on - 10 seconds (Default)
Jumper off - 20 seconds
Activating Legs
Arming Switch
Circuit Board
End Cover
J2: To Power Transfer
J1: To Device Connections
J5
J8