16
ANSI / BHMA A156.19 (LOW ENERGY APPLICATION)
16.1
REQUIREMENTS FOR LOW ENERGY POWER OPERATED DOORS
The following texts are excerpts from American National Standard for low energy power operated
swing doors. Please refer to the full standard if necessary.
16.1.1
Activation
The operator shall be activated by a knowing act.
16.1.2
Opening
Doors shall open from closed to back check, or 80 degrees which ever occurs first, in 3 seconds or
longer as required in Table I. Backcheck shall not occur before 60 degrees opening. Total opening
time to 90 degrees shall be as in Table II. If the door opens more than 90 degrees, it shall continue
at the same rate as backcheck speed. When powered open, the door shall remain at the open po-
sition for not less than 5 seconds.
16.1.3
Closing
Doors shall close from 90 degrees to 10 degrees in 3 seconds or longer as required in Table I.
Doors shall close from 10 degrees to fully closed in not less than 1.5 seconds.
16.1.4
Force and Kinetic Energy
The force required to prevent a stopped door from opening or closing shall not exceed 15 lbf (67
N) measured 1" (25 mm) from the latch edge of the door at any point during opening or closing.
The kinetic energy of a door in motion shall not exceed 1.25 lbf-ft (1.69 Nm). Table I provides
minimum times for various widths and weights of doors for obtaining results complying with this
kinetic energy.
Doors shall open with a manual force not to exceed 15 lbf (67 N) to release a latch, if equipped
with a latch, 30 lbf (133 N) to set the door in motion, and 15 lbf (67 N) to fully open the door. The
forces shall be applied at 1" (25 mm) from the latch edge of the door.
Table I
Minimum Opening Time to Back Check or 80 degrees, which ever occurs first, and the Minimum
Closing Time from 90 degrees to Latch Check or 10 degrees.
“W” Door Weight in Pounds (kg)
“D” Door Leaf Width - Inches (mm)
200 (90.7)
175 (79.4)
150 (68.0)
125 (56.7)
100 (45.4)
3.5
3.0
3.0
3.0
3.0
*30 (762)
4.0
4.0
3.5
3.5
3.0
36 (914)
4.5
4.5
4.0
4.0
3.5
42 (1067)
5.5
5.0
4.5
4.5
4.0
48 (1219)
* Check applicable Building Codes for clear width requirements in Means of Egress.
1020004-en-US-2.0
Issue 2020-10-27
48
16 ANSI / BHMA A156.19 (LOW ENERGY APPLICATION)
Summary of Contents for SW60
Page 13: ...6 Part identification 13 Issue 2020 10 27 1020004 en US 2 0 6 Part identification...
Page 22: ...1020004 en US 2 0 Issue 2020 10 27 22 10 Mechanical installation...
Page 23: ...23 Issue 2020 10 27 1020004 en US 2 0 10 Mechanical installation...
Page 24: ...1020004 en US 2 0 Issue 2020 10 27 24 10 Mechanical installation...
Page 25: ...25 Issue 2020 10 27 1020004 en US 2 0 10 Mechanical installation...
Page 26: ...1020004 en US 2 0 Issue 2020 10 27 26 10 Mechanical installation...
Page 27: ...27 Issue 2020 10 27 1020004 en US 2 0 10 Mechanical installation...
Page 28: ...10 2 PULL arm system 1020004 en US 2 0 Issue 2020 10 27 28 10 Mechanical installation...
Page 29: ...29 Issue 2020 10 27 1020004 en US 2 0 10 Mechanical installation...
Page 30: ...1020004 en US 2 0 Issue 2020 10 27 30 10 Mechanical installation...
Page 31: ...31 Issue 2020 10 27 1020004 en US 2 0 10 Mechanical installation...
Page 32: ...1020004 en US 2 0 Issue 2020 10 27 32 10 Mechanical installation...
Page 33: ...33 Issue 2020 10 27 1020004 en US 2 0 10 Mechanical installation...
Page 34: ...1020004 en US 2 0 Issue 2020 10 27 34 10 Mechanical installation...
Page 37: ...11 2 Control unit CU 37 Issue 2020 10 27 1020004 en US 2 0 11 Electrical connection...
Page 39: ...12 2 2 Log in to the app with owner 39 Issue 2020 10 27 1020004 en US 2 0 12 Start up...
Page 41: ...12 2 4 Test 12 2 5 Settings 41 Issue 2020 10 27 1020004 en US 2 0 12 Start up...
Page 42: ...12 2 6 Add user 12 2 7 Remove user 1020004 en US 2 0 Issue 2020 10 27 42 12 Start up...
Page 43: ...12 2 8 Log in to the app with user 43 Issue 2020 10 27 1020004 en US 2 0 12 Start up...