PN# 500-18300

 

 

Page 8 

Rev. D, 08/11 

of the door depends on it receiving constant power.  Any time power is cut to the UnLatch, 
it will report the door as secure regardless of whether it is latched or not. 
 

The UnLatch uses the information as to whether the door is latched or not for a second purpose.  
The UnLatch will not operate unless the latch is in the secure position (the spring latch 
plunger is pushed in).  The reason for this is to avoid a potential jam condition.  If the door had 
not fully closed, the spring latch could be adjacent to the dead latch plunger and the dead latch 
pin would be resting on the metal “strike” casing of the UnLatch.  In this condition, if the 

UnLatch was allowed to operate, the dead latch plunger would attempt to push the spring latch 
and it would be unable to do so because the dead latch pin would be pushed in by the metal 
casing of the UnLatch.  The motor would jam.  The UnLatch senses any motor jam condition and 
shuts itself down for that cycle but it is better not to operate at all unless the door is latched.  
Operationally, the door can be opened anyway (it is not latched) so there is no benefit to the 
end user from the UnLatch operating unless the door is latched. 

 
5.  MAGNACARE

 LIFETIME REPLACEMENT WARRANTY 

For warranty information visit: www.securitron.com/en/site/securitron/About/MagnaCare-Warranty/ 

Summary of Contents for Securitron UNLATCH UNL-12

Page 1: ... operating 3 Amp input surge 12 VDC 1 5 Amp input surge 24 VDC for 100 milliseconds and 300 mA 12 VDC or 200 mA 24 VDC thereafter Operating Temperature 10 F to 125 F FIG 1 UNLATCH DIMENSIONS INCHES 4 87 1 245 3 37 4 12 3 38 1 50 1 33 RECOMMENDED TOOLS MEDIUM PHILLIPS DRIVER MEDIUM SLOTTED DRIVER CHISEL WIRE CUTTER STRIPPER VOLT OHM METER CRIMP CONNECTORS CRIMP PLIERS 2 PHYSICAL INSTALLATION 2 1 SU...

Page 2: ...OOD FRAME MOUNTING Installation in a wood frame is straightforward It is a question of using a chisel to create a space for the UnLatch behind the existing strike The procedure depends on whether you have a 4 7 8 ANSI strike commercial or a 2 3 4 ANSI strike residential on the door In the case of a 4 7 8 ANSI strike you will be using the existing holes that mount the strike to mount the UnLatch Re...

Page 3: ...is will avoid chiseling too big a space A tight fit is preferred as it helps the solidity of the mounting which is important if the door receives abuse Normally with a wood frame the wires will be run inside the wall Simply drill from the back of the cavity you have created rearward into the wall space to admit the wires into the walls To mount the UnLatch to the wood frame use the two furnished 1...

Page 4: ...it card in between the door and frame To forestall this the deadlatch was created The deadlatch includes a deadlatch pin which is depressed against the flat part of the strike when the door is closed When the deadlatch pin is depressed the latch cannot be pushed in by a credit card for instance it is mechanically blocked Deadlatches therefore offer a considerably higher level of security and this ...

Page 5: ... WHICH ALLOWS THE DEAD LATCH PIN TO COME OUT THIS UNFREEZES THE SPRING LATCH FINALLY BOTH PLUNGERS MOVE FORWARD TOGETHER THIS PUSHES OUT THE SPRINGLATCH AND DEADLATCH PIN AND THEREBY RELEASES THE DOOR Note that if the door is heavily pre loaded by someone trying to pull it open before the UnLatch has released it for example the UnLatch may not possess enough power to release the door This is terme...

Page 6: ...onal electric strikes the UnLatch is fail secure which means that it will maintain the door in a secure position if power is lost Entry is not possible but people can of course exit by simply turning the door handle or knob from the inside FIG 7 UNLATCH WIRING WHITE STATUS COM BLUE STATUS N O CLOSURE BETWEEN V IN AND TRIGGER RELEASES LATCH ORANGE TRIGGER GREEN STATUS N C POWER SUPPLY RED V BLACK N...

Page 7: ...re being operated from the same power supply If therefore your installation includes a digital keypad or other microprocessor equipped device make sure you have full power supply capacity or use a separate power supply for the keypad or other device 4 2 WIRE GAUGE SIZING If the power supply is some distance from the lock voltage will be lost dropped in the connecting wires so that the UnLatch will...

Page 8: ... dead latch pin would be resting on the metal strike casing of the UnLatch In this condition if the UnLatch was allowed to operate the dead latch plunger would attempt to push the spring latch and it would be unable to do so because the dead latch pin would be pushed in by the metal casing of the UnLatch The motor would jam The UnLatch senses any motor jam condition and shuts itself down for that ...

Page 9: ... and this can crash the microprocessor A crash can also occur as a random event but this is unusual There are two recovery methods that may be used to recover the unit s operation The first technique is a simple reset achieved by cycling power to the unit Remove power V from the unit s red wire momentarily After power is reapplied the unit may reset and begin normal operation If this recovery meth...