7
of 12
H2 (BOND)
H3 (DPS)
JP3 (EXT INIT)
Table 3 Delayed Egress DIP-switch selection and function
Delayed Egress Function Dip-Switches
Position
Selection
Function/Description
Factory Default
Nuisance Delay
SW 1 OFF / SW 2 OFF
0 seconds
Time that the door must be pushed before
triggering the irrevocable alarm cycle. Set
the desired nuisance delay in seconds.
0 seconds
SW 1 ON / SW 2 OFF
1 seconds
SW 1 OFF / SW 2 ON
2 seconds
SW 1 ON / SW 2 ON
3 seconds
Exit Delay
SW 3 OFF
15 seconds
Set the desired irrevocable
alarm interval in seconds.
WARNING: a 30 second delay must be
approved by local code enforcement.
15 seconds
SW 3 ON
30 seconds
Bypass Time
SW 4 OFF / SW 5 OFF
0 seconds
The expected time for a door closure
after manually bypassing (unlocking)
the system to exit or enter.
Set the desired bypass time in seconds.
0 seconds
SW 4 ON / SW 5 OFF
15 seconds
SW 4 OFF / SW 5 ON
30 seconds
SW 4 ON / SW 5 ON
45 seconds
Post Alarm Reminder
SW 6 OFF
Disabled
When enabled, provides audible
indication after an alarm event.
Disabled
SW 6 ON
Enabled
Bypass Expiration
Alarm
SW 7 OFF
Disabled
When enabled, provides audible indication
when the bypass time has been exceeded.
Disabled
SW 7 ON
Enabled
Manual/Delayed
Relock
SW 8 OFF
Disabled
When enabled, the system
automatically relocks 30 seconds
after an irrevocable alarm cycle.
Disabled
SW 8 ON
Enabled
Unlocked at Startup
SW 9 OFF
Disabled
When enabled, system starts
in the unlocked state.
Disabled
SW 9 ON
Enabled
No Irrevocable
Alarm After Bypass
Expiration
SW 10 OFF
Disabled
When enabled, prevents irrevocable
alarm after bypass expiration. If SW7
is on, bypass expiration alarm repeats.
If SW7 is off, LED strobe flashes.
Disabled
SW 10 ON
Enabled
Table 1 Jumper Settings
Jumpers
Position
Selection
Function/Description
Factory Default
H2 (BOND)
1-2
Normally
closed (NC)
Normally closed circuit – opens
when BOND registers secure.
Normally closed
2-3
Normally
open (NO)
Normally open circuit – closes
when BOND registers secure.
H3 (DPS)
1-2
Normally
open (NO)
Normally open circuit
– closes when door opens.
Normally open
2-3
Normally
closed (NC)
Normally closed circuit
– opens when door opens.
JP3 (EXT INIT)
1-2
Disabled
When enabled, allows unit to
be initiated from an external
source. (J1, Terminal 4)
Disabled
2-3
Enabled
Table 2 Magnalock DIP-switch selection and function
Magnalock function DIP-switches
Position
Selection
Function/Description
Factory Default
LED enable
SW 1 ON
LED
enabled
When enabled, LEDs
display lock status.
ON
SW 1 OFF
LED
disabled
(Reserved)
SW 2 – SW 9
N/A
Not used.
OFF
Reset to Factory Defaults
SW 10 OFF
Reset
disabled
When enabled, restores
Magnalock firmware
to factory settings.
OFF
SW 10 ON
Reset
enabled
Diagram 29 Jumper Locations
Diagram 30 DIP-switch Locations
Magnalock Functions
Delayed Egress Functions
Diagram 24 Location of J1 and J4 terminals
Diagram 25 Terminal pin-out diagram