AQD5 12v/24v Series Power Supply continued 

AQD5 Series Instructions:  Doc.# 500-33005 Rev.B 

Page 2 of 4 

Limited, all output devices connected to the AQD5 
would automatically become class II Power Limited. 

 

AQD5 Specifications / Instructions 

AC Input: L, N, G - 3P Terminal block  
Safety block with recessed hardware insulation that will 
accept up to 12AWG  

L= Line, N= Neutral, and G = Ground 

Note: The Ground connection is connected to the 
enclosure back with a metal standoff.  In the case of 
enclosures with a removable lid, a ground wire is used 
to ensure the ground continuity to the lid.  If lid is 
removed, this ground wire must be reconnected 
securely.

 

AC Input  .........................................................  90-250vac/240W 
 

AC Input Operational  ......................................  60-264vac 

Optional 3 wire line cord P/N:  ..............................  HA-LC3SZIP 

AC LED Indicator (Panel mounted on the door of PS-1485 
Enclosure) 

The AC indicator is a bi-color green and red led.  This LED 
off with AC at the terminals would indicate a blown fuse link.  

A blown AC fuse link would indicate catastrophic failure and 
must be returned to the factory for repair. 
DC VOLTAGE SELECTOR SWITCH 

The selector switch is on the right side of DC Output Terminal 
Block.  As marked on board, up is 24vdc and down is 12vdc.  

CAUTION

 To prevent damage, remove DC load and 

battery(s) connections before switching selector switch up or 
down. 

DC OUTPUTS: 2P Terminal block  

Note: There is up to a 10 second delay for initial turn on 
Output voltage Nominal  .......................................  12vdc/24vdc 
Output voltage Typical  ...............................   AC on 13.70/27.40 
Output range with rated load  ................ 10.4–13.7/22.7-25.2vdc 
Output continuous current (UL rating) ..............................   5A/3A 
Load regulation no load to max  .................................   .25%Typ 
AC Line regulation 85-264vac  ...................................   .03%Typ 
Output ripple & noise at full load  ...........   180/25mv pp/rms Typ 
Current Overload Short Circuit Protection  ........................   Yes 
Thermal runaway Protection  ..............................................  Yes 

Current Overload and Thermal shutdown will auto-restart 
without removing load. 

Ambient operating temperature range  .............  32

o

F to +120

o

Product was not evaluated at UL for outdoor use 
Storage Temperature   ......................................   -60

o

F to 190

o

Switching Frequency   ..................................................     132KHz 

DC LED Indicator (Adjacent to battery Header)  ..............  

 Red 

Battery Charging: (Header plug marked [–Bat+]) 
Caution

 – To avoid spark, apply AC before connecting 

battery cable to battery. 
The battery charger is precision set to float charge 12V  
or 24V sealed or wet lead acid batteries.  Two 12V batteries 
are connected in series for 24V.  A 12” battery cable 
assembly is provided that plugs from module to  
 battery.  Red (+) 12vdc, Black (–) Neg. 
Optional 36” battery cable (1) P/N:  ........................  WA-36IBAT 
Battery(s), any type of lead acid  .......................   12v  4AH-40AH 
 

UL evaluated  .............................................................  7AH 

Battery(s) recharge   ..............................................   400ma max 
Battery(s) average recharging current   .........................   250ma 
Battery(s) PTC self resetting Circuit Breaker  ..............   6A PTC 
Battery(s) Reverse hookup protection .................  Yes  .4A PTC 
To estimate the recharge time in hours for depleted battery(s), 
multiply the AH rating times 4 (AH x 4).  As an example, a 24v 

system with two depleted 12v 7AH batteries would take about 
28 hours to re-charge.  See battery standby selection table on 
page 3.  We also have a more elaborate battery standby table 
on our website at  http://www.securitypower.com/an3batby.pdf . 

AQD5 Supervised added features: 

UL Listed 
DC Output Class II Power Limited   ....................................   Yes 

AC Status Output Relay: 3P Terminal block  

AC Fail “C” contacts rating  .....................................   2A/120vac 

Three position AC fail terminal block marked “NO, C, NC” are 
shown in the Normal, energized, AC ON condition. 
Trouble Output: 3P Terminal block - 

annunciates low 

battery “C” contacts rating  ......................................   2A/120vac 

Three position trouble terminal block is marked “NO, C, NC” 
are shown in the Normal, energized, no trouble condition. 

Trouble battery voltage (low)  .........................   12.1vdc/24.2vdc 

Trouble LED Indicator

  ..............................   On Green Normal 

Battery Cutoff 

Battery Cutoff Voltage   ....................................   9.8vdc/19.6vdc 
Battery Cutoff internal relay contacts   ...............................   15A 

Battery Cutoff Relay is normally energized for fail-safe 
operation. 
Physical  

AQD5 Module Dimensions  ...................  6.05”Lx3.87”Wx2.28”H 

Height includes 7/16” standoffs, not provided with module 
only. 

Mounting Holes Center to Center  ..................   4.50”W x 3.41”H

 

AQD5 module only Weight  ............................................   12.4oz 
AQD5 in enclosure  ..........................................   14” x 9” x 3.50” 
AQD5 in enclosure Weight  ..........................................   6.85Lbs 

UL Approvals for AQD5 

UL 294 – Access Control System Unit 
UL 603 – Power supplies for Use with Burglar-Alarm Systems 
ULC S318-96 – Power supplies for Burglar Alarm Systems 
ULC S533-02 – Standard for Egress Door Securing and 
Releasing Devices 

Safety 

AQD5 meets safety  ..................................   UL1950 & EN60950 
 Note: evaluation to these standards was not conducted by 
UL. 