IS5591014085B
About LCU9101IV
LCU9101 is an ARX unit that supports a one door installation and
can be expanded with three more wired online doors via DAC, DBL,
PCR or equivalent. LCU9101 can also manage 1-15 Aperio doors.
But total number of doors is 16. E.g. if you connect four online doors
to LCU9101 you can connect another 12 Aperio doors via two AH30
Aperio hubs.
Installation Interface
LCU9101 handle various interfaces for connecting readers etc.
directly or via add-on cards. LCU9101 manages CL connection to
readers and Hi-O connected devices as open button, reader, electric
lock and automatic door. LCU9101 has two relays and two inputs as
base. The relays are Lock relay and LFK relay, both relays are
single pole switching clean contact out. The inputs are RTE open
button and door monitor input.
ADD-ON card to LCU9101
There are various add-on cards to LCU9101 depending on the
desired function, which you can connect to LCU9101.
You can connect one card at a time
•
9101R4850
For connecting Aperio HUB or update reader
•
9101D3
For connecting three door environments via
DAC, DBL ore PCR
•
9101D3A
Expansion
card
to 9101D3.
For connection of Aperio AH30 hubs or
update readers
•
9101RC64
Relay card with four inputs, six relays and
connection of Aperio HUB or update reader
Initiate Hi-O units LCU9101
Lock or unlock the Hi-O units on the LCU9101.
Connect unlocked Hi-O devices to Hi-O terminal on the LCU9101
1)
LCU9101 will be in operation
2)
Set DIP 2 in the ON position, after a while LED "D" lit
3)
Set again DIP2 OFF, LED "D" will start to flash
4)
When the LED "D" goes off the Hi-O bus is locked.
To unlock the Hi-O bus
1)
Set DIP2 ON
2)
When the LED "D" is light the Hi-O bus are unlocked
DIP switch on LCU9101
DIP
1
ON = Telnet active
2
Initializes HiO units
3
ON = Balanced door monitor contact
4
ON = Fixed IP 192.168.1.250
5
No function
6
ON = Master reset and test mode
7
No function
8
No function
Connections and jumpers
Terminals
1
0V (power supply)
2
+ 17-28 V DC (power supply)
Inputs and CL readers
3
SW (Door monitor)
4
0V
5
RTE (Exit Button)
Request to Exit
6
CL+ (Communication CL reader)
7
CL- (Communication CL reader)
12V supply and the Hi-O connection
8
0V
9
+12V
10
Hi-O L
11
Hi-O H
ABP Relay
12
Nc
13
No
14
C
Lock relay
15
NC
16
NO
17
C (
Se P3 info
)
Power supply Jumpers: Choice between PoE or 24V supply
P1
A&B
DC supply via terminal 1, 2
P2
A&B
PoE + power supply
Relay jumper
P3
RE position (relay is potential-free)
+ 12V position (+ 12V connected to the relay connector C)
Technical specifications LCU9101IV
Part Number
S5591014085
Power supply
17-28 V DC
Current consumption at 27,8V: 96mA Max 120mA
Fuse
1A Automatic fuse out +12V
Unit should be fuse
protected
Max 2A
PoE
PoE 15W/ PoE+ 30W IEEE 802.3af/at
Hi-O Cable length
Totally:
Max. 50 m
Cable branch length:
Max. 10 m
Operating Temperature
–
30°C to + 70°C
Humidity during
operation
5 % to 95 %
Dimension
H 182,3 W 182,3 D 45,5
IP
44
Storage and
transportation
Temperature: -50 ºC till 70 ºC (-58 ºF to 158 ºF)
Humidity 5 % to 95 %
Connecting the electric lock via relay on LCU9101IV
When the PoE power supply, is only 12V available
12V Electric lock
4 (0V)
16 (No)
P3
+12V
RE
3 (SW)
NC
C
0V
+12V
4 (0V)
16 (No)
P3
+12V
RE
3 (SW)
NC
C
0V
+12V
_____________________________________
24V Electric lock
4 (0V)
16 (No)
P3
+12V
RE
3 (SW)
NC
C
0V
+24V
2 (24V)
1 (0V)
17 (C)
15 (Nc)
4 (0V)
16 (No)
P3
+12V
RE
3 (SW)
NC
C
0V
+24V
2 (24V)
1 (0V)
17 (C)
15 (Nc)
Technical documentation and support
We reserve the right to correct printing errors and update the information after printing.
At the website (
https://teknisksupport.assa.se/
) technical support can you find detailed manuals
available for the ARX access control system. If you cannot find answers to your questions in the
manuals, we refer to the technical support in your country.
Summary of Contents for LCU9101IV
Page 4: ...IS5591014085B...