CL33600 Series Cylindrical Lock
13
Copyright © 2017 Corbin Russwin, Inc. All rights reserved.
Reproduction in whole or in part without the express written
permission of Corbin Russwin, Inc. is prohibited.
Before closing door test for cylinder function of lock cylinder and Inside lever:
a. Insert key into cylinder and rotate.
b. The key will retract the latch. Key should rotate freely.
c. Inside lever retracts latch.
d. Close door, ensure latch fully extends into strike and does not bind.
Once electrical wiring has been successfully completed according to proper application:
a. Turn power ON.
b. Verify LED located on reader is ON (red or green
depending on reader configuration (refer to reader
LED configuration).
c. Present proximity credential and verify LED and
sounder activity.
d. Verify valid card read at EAC panel.
e. Verify system operation; i.e., when prox credential
is presented to reader that the door unlocks.
9) Electrical Operational Check
7) Door Status Switch Installation
1.
Install Door Status Switch supplied with product:
a. Drill 1” hole in door for magnet.
b. Drill 1” hole in frame for switch.
2.
Wire to ElectroLynx® frame harness as shown in wiring diagrams on
previous pages.
8) Mechanical Operational Check