background image

ASSA AB 702796 Utgåva 1 

4 av 6 

 

 
 
Mounting instruction 

        Emergency exit device ASSA 179E 

 
This mounting instruction is intended for installation of emergency exit device ASSA 179E 
with ordering number: 364371 in combination with lock case Abloy EL580 with ordering 
number EL580100011. 
 
Emergency exit device ASSA 179E in combination with lock case Abloy EL580 are approved 
for fire doors up to grade E/EI60.  

 

Warning!

 

The safety features of this product are essential to its compliance with EN 179:2008.  
No modification of any kind, other than those described in these instructions, is permitted. 
ASSA takes no responsibility for products not mounted as described in these instructions or if 
enclosed maintenance and operating instruction not are followed. 
 
In compliance with EN 179:2008 the ASSA 179E is intended for use on single doors with 
following size: 
 

Product

 

Ordering 

number 

Max width of 

door 

Max height of 

door 

Max 

weight of 

door

 

179E 

364371 

1100 mm 

2100 mm 

100 kg 

 
ASSA 179E must be installed together with ASSA strike plate 1887 with following ordering 
numbers: 353355, 353356, 353357, 353358 and 353467 alternative Abloys strike plate 
LP712. When using strike plate 1887 it is recommended to also use accessory 1893 with 
ordering number 808287. 
 
ASSA 179E can be installed with round or oval cylinders with Scandinavian shape.  
In the mounting instruction for EL580 you can find instructions for mounting oval and round 
cylinders. 