ASPIRCOMFORT PRO X 460H
2.3 CONDENSATE DISCHARGE CONNECTION
Due to the thermodynamic heat recovery system of the dehumidification coils, the humidity contained in the
indoor air condenses inside the unit.
For the correct operation of the heat recovery unit, it is therefore necessary to connect the condensate discharge
to the hydraulic system (drain); furthermore, in order to allow the correct flow of the condensate water and to
avoid air suction, the condensate discharges must be equipped with a special siphon to be supplied and installed
by the installer;
Condensate discharge exits as standard to the rear of the unit where there should be a hole in the wall as shown
opposite;
If it is not possible to take the condensate discharge outside, it is possible to exit on the right side of the unit using
the pre-cut hole on the side;
For installation of the condensation discharge, follow these rules:
•
set up a slope of at least 2% to the discharge pipe;
•
allow the possibility of disconnecting the discharge pipe for any
maintenance (especially with ceiling installation);
•
make sure that the discharge end of the pipe is at least below the level of
the trap water;
•
make sure that the trap is always full of water;
•
the H dimension as shown in the attached image must be at least H=50mm;