
Port: COM1, Data bits 1 Parity: None;
Baud: 9600; Stop bits: 2; Flow Control: None!
5) Press the reset pin on the EtherLink/2 It should return the status of the Device.
The reset pin is located in the hole just above the dip switches on the back of the
unit.
EtherLink/2 -- Version 1.00.0 -- Configurable Network Interface
Copyright (c) 2005, ASI Controls, Inc.
Location = ASI Controls, 2202 Camino Ramon, San Ramon, CA
94583
DHCP = off
MAC = 00:40:9D:28:7E:B7
IP = 192.168.1.201 [IP port 3001]
Subnet = 255.255.255.0
Gateway = 192.168.1.1
Monitor IP = 0.0.0.0 [IP port 2001]
Notify Address = 23264 (5AE0 hex)
Notify Retry = 5 seconds
Serial = 9600 bps, 2 stopbit
Timeout = 1000 milliseconds
Press any key in 15 seconds to change these settings.
6) To Change settings
Press A to Accept the settings, or M to Modify? m
Enter the root password: ********** [Netsilicon]
For each of the following questions, you can press <Return> to select the value
shown in braces, or you can enter a new value.
Do NOT change the MAC Address!
Wait 60 seconds for device to reboot to accept changes.
ASI Software Connections
The EtherLink/2 supports both UDP/IP and TCP/IP connections. Access to a single
ASI serial bus can be shared to multiple remote users simultaneously.
The ASI OPC Server is usually the primary connection. If more than one Etherlink/2
is on the network then the primary connection should be via TCP/IP.
Like the EtherLink/1 before it, the EtherLink/2 can host only one TCP/IP connection
at a time. The TCP/IP connection is automatically reset after 15 seconds of
inactivity. Use of TCP/IP is recommended when you don't want to have to open up a
unique IP port on the host's firewall for each remote EtherLink/2.
While the EtherLink/1 could not host multiple connections, the EtherLink/2 adds
support for multiple simultaneous connections via UDP. If multiple EtherLink/2's
are connected to the same OPC server using UDP, then each EtherLink/2 must use a
unique IP port number so as to avoid traffic crosstalk. .
ASI Expert can also be used to connect to the Etherlink/2 as a secondary connection
using UDP. It is possible to have one or more Expert users connected to an
EtherLink/2 via UDP while an OPC Server is simultaneously polling that same
EtherLink/2 over TCP/IP.
1-14
•
Configuring EtherLink/2
EtherLink/2 User Manual
DOC-1643 (2008-09-16)