![Ashley AGVF340 Installation And Operating Manual Download Page 7](http://html1.mh-extra.com/html/ashley/agvf340/agvf340_installation-and-operating-manual_2982347007.webp)
7
Check inlet pressure to burner to ensure that it is as shown in table below.
NOTE: The pressure check point is located on the right side of valve facing burner, for SIT Millivolt.
Appliance and its appliance main gas valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psi (3.5kPa). Appliance must be isolated
from gas supply piping system by closing its equipment shut-off valve during any pressure testing of gas supply
piping system at test pressures equal to or less than 1/2 psi (3.5 kPa)
.
NOTE: On initial installation it may be necessary to bleed out air in the gas lines. Do this by holding the control
knob and turning the knob to the “PILOT” position for about 30 seconds. To check the regulator pressure, remove
the pressure tag plug at the left side of the regulator facing the heater. The pressure should be checked with
the heater burning and the control set on high. After measuring the pressure, replace the pressure tap plug,
ensuring that there are no leaks.
• For the purpose of minimum input adjustment.
Solid fuels shall not be burned in the same fireplace where an unvented room heater has been installed.
NOTE: The following label has been provided with this appliance and must be read and then attached to
floor of the fireplace or firebox area beneath the appliance. The label is a peel and stick label. Make sure the
area is cleaned before attaching label to it.
Gas Type
Natural
LP
Maximum Heat Input
33,000
33,000
Minimum Heat Input
23,000
23,000
Gas Inlet Pressure
Maximum
10.5” W.C. 13” W.C.
Minimum
5.0” W.C. 11” W.C.
Manifold Pressure
Maximum
3.5” W.C.
9.0” W.C.
Minimum
3.0” W.C.
8.2” W.C.
“WARNING: THIS SOLID-FUEL BURNING FIREPLACE OR LISTED VENTLESS ENCLOSURE HAS BEEN
CONVERTED FOR USE WITH AN UNVENTED FIREPLACE INSERT ONLY. A SOLID-FUEL BURNING
FIREPLACE CANNOT BE USED FOR BURNING WOOD OR SOLID FUELS UNLESS ALL ORIGINAL
PARTS HAVE BEEN REPLACED AND FIREPLACE RE-APPROVED BY THE AUTHORITY HAVING
JURISDICTION. A VENTLESS FIREBOX ENCLOSURE CANNOT BE USED WITH AN UNVENTED GAS
LOG UNLESS ALL ORIGINAL PARTS HAVE BEEN REPLACED AND VENTLESS FIREBOX ENCLOSURE
REAPPROVED BY AUTHORITY HAVING JURISDICTION.”
WARNING: THIS APPLIANCE IS EQUIPPED FOR (NATURAL OR PROPANE) GAS. FIELD
CONVERSION IS NOT PERMITTED.
GAS PRESSURE CHECK
Summary of Contents for AGVF340
Page 31: ...31 SIT MILLIVOLT VALVE BASE 8 10 12 3 1 2 6 5 7 4 9 11...
Page 35: ...35 NOTES...