11
Electrical Connections
Turn circuit breaker off before
wiring he pump to the control panel.
Always rely upon a Certified Electrician for installation.
Level Control
It is recommended that the level control float should be
set to insure that the liquid in the sump never drops
below the top of the motor housing. The level control
should have adequate clearance so it cannot hang up in
it’s swing and that the pump is completely submerged
when the level control is in the “Off ” mode. Minimum
tether length is 3.50”.
DO NOT USE THE POWER CABLE TO LIFT PUMP.
Thermal Protection
Motors are protected by a thermo-overload or thermo sen-
sor depending on the model and single or three phase.
Pre-Operation
1. Check Voltage and Phase compare to the voltage and
phase information stamped on the pump name plate.
2. Check Pump Rotation - Improper motor rotation can
result in poor pump performance and can damage
the motor and/or pump. Check rotation by momen-
tarily applying power and observe the “kickback”.
Kickback should always be in a counter-clockwise
direction as viewed from motor end or opposite to
impeller rotation. Incorrect rotation for Single-Phase
pumps is unlikely. If the rotation is incorrect contact
factory.
3. Name Plate - Record the information from the pump
name plate for future reference.
4. Pump-Down Test - Be sure pump has been plugged in,
lowered into the basin or sump, check the system by
filling with liquid and allowing the pump to operate
through its pumping cycle. The time needed to
empty the system, or pump-down time along with the
volume of water, should be recorded.
Solids Handling Pumps
Models: 3ANC300/500/750,
4ANC2500/3000/4000/5000/6000
6ANC1000/1500/2000/3000/4000/5000/6000
8ANC5000/6000 Installation and Service
Cooling Oil
Recommended Supplier/Grade
BP
Enerpar SE100
Conoco
Pale Paraffin 22
Mobile
D.T.E. Oil Light
Shell Canada
Transformer-10
Texaco
Diala-Oil-AX
Summary of Contents for 3ANC300
Page 5: ...5 Solids Handling Pumps Models 3ANC300 500 750 4ANC2500 3000 4000 Performance ...
Page 7: ...7 Solids Handling Pumps Models 6ANC3000 4000 5000 6000 Performance ...
Page 8: ...8 Solids Handling Pumps Models 8ANC5000 6000 Performance ...
Page 18: ...18 Solids Handling Pumps Models 4ANC2500M4 35 4ANC3000M4 35 Repair Parts ...
Page 20: ...20 Solids Handling Pumps Models 4ANC4000M4 35 Repair Parts ...
Page 22: ...22 Solids Handling Pumps Models 4ANC5000M4 35 4ANC6000M4 35 Repair Parts ...
Page 26: ...26 Solids Handling Pumps Models 6ANC3000M4 35 Repair Parts ...
Page 28: ...28 Solids Handling Pumps Models 6ANC4000M4 35 6ANC5000M4 35 and 6ANC6000M4 35 Repair Parts ...
Page 30: ...30 Solids Handling Pumps Models 8ANC5000M4 35 and 8ANC6000M4 35 Repair Parts ...