Typical Tests Information:
The Relay Confirm to following standard
Electromagnetic Compatibility Type Test:
Sr. No.
Standard
Test
1.
High Frequency
Disturbance Test
IEC60255-22-1
: Frequency : 1MHz Damped Oscillatory
: Longitudinal :2.5 KV Common Mode,
1 KV Differential Mode
: Duration: sec duration 2 sec.
: On Mains Port.
2. Electrostatic
Discharge Test-
Direct Application
IEC60255-22-2
: IEC 61000-4-2.
: Contact discharge: 2, 4, 6 kV,
: Air discharge: 2, 4 8 KV
: Polarity: both +ve and –Ve polarities.
3.
Fast Transient
Disturbance Test
IEC60255-22-4
: Class A
: 4KV; 5/50ns; 5KHz & 100KHz: Repetition rate 300ms;
Both polarities; Ri = 50
Ω
; duration 1 min.
4.
Surge Immunity
Test
IEC60255-26 &
IEC61000-4-5
: Differential Mode = 2kV
: Common Mode = 4kV
: 1.2/50
µ
s, 8/20µs 5 surges of each polarity
5.
Power Frequency
Immunity Test
IEC60255-22-7
: Class-A
6. Pulse Magnetic
Field Immunity
Test
IEC61000-4-9
: TEST LEVEL 5, TEST specifications = 1000A/m field
applied in all planes
7. Radiated
Electromagnetic
Field Disturbance
Test
IEC60255-22-3
: 10V/m, Performance Class-A
: 10V/m, freq = 80MHz to 1GHz, 80% AM at 1kHz. SPF
= 80, 160, 380, 450, 900 MHz
8. Conducted
Disturbance
Induced By Radio
Frequency Field
IEC60255-26
: Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation
80% AM @ 1 KHz. SPF = 27 and 68 MHz
9. Power Supply
Immunity Test
IEC60255-11 &
IEC61000-4-11
: DC voltage dip:
40% dip 200ms and 70% for 500ms for DC
10 & 20ms without loss of protection for DC
30ms, 50ms, 100ms, 200ms, 300ms, 0.5s, 1s and 5s
with temporary loss of protection for DC
AC voltage dip:
10, 20ms without loss of protection for AC
50ms, 100ms, 200ms, 0.5s, 5s with temporary loss of
protection