ASENWARE LTD.

 

9

 

1.4.3 Input Method

 

From the display, it is very convenient for the programmer to input and register the devices. 

1.4.4 Power Supply

 

The power supply is designed to supply power to all devices in the system. The system adopts 

the  special  firefighting  equipment  powered  with  DC  24V  output,  which  can  provide  alarm  or 

feedback  signals,  such  as  main  power  fault,  battery  fault,  battery  under-voltage  and  battery 

charging, and have a good capacity for interference. 

Customer is recommended to do battery calculation for proper rating of batteries 

1.4.5 Loop Card

 

The loop card is used as the driver of detector/module bus, which may drive 250 intelligent 
detectors or intelligent modules and can be equipped with bus type fire indicating panel. 

1.4.6 Interconnection with Devices

 

The  system  can  get  access  to  various  intelligent  smoke,  heat  or  combination  detectors 

produced  by  the  manufacturer,  and  the  main  types  include  detectors,  modules,  horn  strobes  , 

manual call point and so on. 

The  system  can  be  interconnected  to  Modules,  Manual  Call  Point,  Relays,  Deluge  vale 

and Gas System. The system can get access to multiple intelligent modules e.g. Input module 

AW-D110  ,  Control  Module  AW-D112 ,  Supervisory  Module  and  Isolator  Module  AW-D111 and 

D114 respectively.  Moreover,  it  can  also get  access  to  intelligent  sounder  visual  indicator  AW- 

D106,  and  intelligent  manual  call  point  AW-D105.  Panel  can  be  configured  with  Gas 

Extinguishing  system,  deluge  system  or  other  water  based  system  and  supervisory  of  various 

types of valves. 

1.4.7 Printer

 

The system is equipped with a special mini-printer as standard, which can print alarm, 
supervisory and fault messages for future reference. 

!

 

Summary of Contents for AW-FP100 Series

Page 1: ...ASENWARE LTD ADDRESSABLE FIRE ALARM CONTROL PANEL 1 July 2017 Prepared By AK ...

Page 2: ...nes for Notification Appliance Circuits NACs 2 wire cable for all addressable devices Zone test and individual device testing Zone Disable and individual device isolation Delay override and abort functionality User friendly easily configurable windows using Panel itself 250 intelligent detectors or modules for one loop circuit Up to 8 Loop cards can be installed and configured Interconnection of p...

Page 3: ...ixed Function Keys Reset Press RESET to eliminate all current alarms and reboot the system The whole process takes 30 60s RESET clear all latched alarms and other events as well as turn off event LEDs If alarms or other off normal events exist after reset they will resound the system and relight the LEDs Evacuate Press this key holding it down for 2 seconds to activate all silenceable fire output ...

Page 4: ...nt exists Remote Sounder Silence Yellow Illuminate when Notification Appliances is silenced and stay flashing until panel is reset General Disable Yellow Illuminates when disable has been performed Test Yellow Illuminate when the panel carries out Lamp test for all LEDs 1 4 SYSTEM COMPONENTS AW FP 100 Series Fire Alarm Control Panel are composed of the following main parts 1 4 1 Main Control The m...

Page 5: ...icating panel 1 4 6 Interconnection with Devices The system can get access to various intelligent smoke heat or combination detectors produced by the manufacturer and the main types include detectors modules horn strobes manual call point and so on The system can be interconnected to Modules Manual Call Point Relays Deluge vale and Gas System The system can get access to multiple intelligent modul...

Page 6: ...The control panel electronics are contained on one printed circuit board that incorporates with loop cards and the central processing unit CPU The built in power supply includes an integral battery charger A display unit is connected over the PCB ...

Page 7: ...C24V Backup power supply DC24V maintenance free battery BAT12V 5AH 1 5 2 Environmental Condition Ambient temperature 10 55 Ambient humidity 95 40 2 no condensation 1 5 3 Terminals Refer to product instructions for detailed technical parameters of the detector module sounder visual indicator and so on ...

Page 8: ......