1.3 DISPLAY AND FUNCTION KEYS

 

Large  display  screen  makes  the  panel  easily  programmable, 

below  Figure  1.1  shows  LED  indicators  and  functions  keys 

available 

1.3.1 Liquid Crystal Display

 

It  displays  all  programming  screens,  as  well  as  events,  history, 

device and other information. At normal condition it displays Fire, 

Fault  ,  Supervisory  and  general  information.  Mosts  Recent 
events  are  displayed  on  the  7”  touchscreen  LCD.  Effortless 
programming can be performed using alphanumeric keyboard. 

1.3.2  Fixed Function Keys

 

Reset

 

Press RESET to eliminate all current alarms and reboot the system. The whole process takes 30-

60s.RESET clear all latched alarms and other events as well as turn off event LEDs. If alarms or 

other off-normal events exist after reset, they will resound the system and relight the LEDs. 

Evacuate

 

Press this key, holding it down for 2 seconds, to activate all silenceable fire output circuits. 

Panel Buzzer Silence

 

By pressing this key, the panel sound will be silenced but LED will keep open. 

Remote Sounder Silence

 

By pressing this key, it will silence all Notification Appliances. 

Test

 

For Lamp Test, press this key to test the LED indicators on the left of the keypad, the panel circuit 
LEDs

Summary of Contents for AW-FP100 Series

Page 1: ...ASENWARE LTD ADDRESSABLE FIRE ALARM CONTROL PANEL 1 July 2017 Prepared By AK ...

Page 2: ...nes for Notification Appliance Circuits NACs 2 wire cable for all addressable devices Zone test and individual device testing Zone Disable and individual device isolation Delay override and abort functionality User friendly easily configurable windows using Panel itself 250 intelligent detectors or modules for one loop circuit Up to 8 Loop cards can be installed and configured Interconnection of p...

Page 3: ...ixed Function Keys Reset Press RESET to eliminate all current alarms and reboot the system The whole process takes 30 60s RESET clear all latched alarms and other events as well as turn off event LEDs If alarms or other off normal events exist after reset they will resound the system and relight the LEDs Evacuate Press this key holding it down for 2 seconds to activate all silenceable fire output ...

Page 4: ...nt exists Remote Sounder Silence Yellow Illuminate when Notification Appliances is silenced and stay flashing until panel is reset General Disable Yellow Illuminates when disable has been performed Test Yellow Illuminate when the panel carries out Lamp test for all LEDs 1 4 SYSTEM COMPONENTS AW FP 100 Series Fire Alarm Control Panel are composed of the following main parts 1 4 1 Main Control The m...

Page 5: ...icating panel 1 4 6 Interconnection with Devices The system can get access to various intelligent smoke heat or combination detectors produced by the manufacturer and the main types include detectors modules horn strobes manual call point and so on The system can be interconnected to Modules Manual Call Point Relays Deluge vale and Gas System The system can get access to multiple intelligent modul...

Page 6: ...The control panel electronics are contained on one printed circuit board that incorporates with loop cards and the central processing unit CPU The built in power supply includes an integral battery charger A display unit is connected over the PCB ...

Page 7: ...C24V Backup power supply DC24V maintenance free battery BAT12V 5AH 1 5 2 Environmental Condition Ambient temperature 10 55 Ambient humidity 95 40 2 no condensation 1 5 3 Terminals Refer to product instructions for detailed technical parameters of the detector module sounder visual indicator and so on ...

Page 8: ......

Reviews: