background image

Version:  V1.0  Apr  28th,2018 

           

 
 

ASENWARE LTD 

ADDRESS: 6 PROSPECT WAY, ROYAL OAK INDUSTRIAL ESTATE    DAVENTRY, 
NORTHAMPTONSHIRE, ENGLAND, NN118PL 
WEBSITE: www.asenware.com 

      EMAIL: [email protected] 

 

 

 

 

 

 

 

 

 

Fig.3 

3.    Remote  Indicator  connection:  the  negative  and  positive  of  remote  indicator  should  respectively 

connect on terminals 2 and 4,as shown in Fig.4. 

 

Fig.4 

4.  Coding address: As shown in Fig.5, detector is accessed via the detector mounting base on the coder, 

non-polarity connection is adopted for the terminals L1 and L2, set the coder with the coding function, 
select the correct address number and press the RUN key to complete the address code setup. (Note: 
See the User’s Manual of the coder for the detailed operation.)   

 

 
 
 
 
 
 
 
 
 
 
 

Fig.5 

 

Intelligent 
two-bus 
controller 

L2 

L1 

Summary of Contents for AW-D302

Page 1: ...m current no remote indicator 1 5mA has remote indicator 3 5mA 6 Work indication The red indicator will blink in the monitoring status or remain lit in the alarm status 7 Weight about 115g with the base 8 External dimensions diameter 100mm height 60mm with the base I Product overview AW D302 Addressable Heat Detector Detector hereunder is a mated product of the AW FP300 fire alarm control panel It...

Page 2: ... machine AW FP300 fire alarm control panel IV Appearance and dimensions see Fig 1 Fig 1 unit mm V Use and engineering application 1 Fig 2 is the schematic diagram of the matched mounting base Fig 2 Definitions of terminals non polarity two wire system 1 Signal terminal L1 2 Negative of remote indicator 3 Signal terminal L2 4 Positive of remote indicator 2 Wiring method The detector is accessed thr...

Page 3: ...ld respectively connect on terminals 2 and 4 as shown in Fig 4 Fig 4 4 Coding address As shown in Fig 5 detector is accessed via the detector mounting base on the coder non polarity connection is adopted for the terminals L1 and L2 set the coder with the coding function select the correct address number and press the RUN key to complete the address code setup Note See the User s Manual of the code...

Page 4: ...tion via the mounting holes A and B shown in Fig 6 as instructed in the construction drawing and make sure the matched mounting base has been firmly installed 3 Use a coder to make the detector coded according to the detector address on the construction drawing 4 Disconnect the power supply of the fire alarm control panel and connect the detector correctly according to the construction drawing 5 T...

Page 5: ...aintained once every two years 2 If a detector fails due to a material defect or a manufacturing process defect under normal conditions of use in one year following the date of its delivery we shall repair or replace it for free However the faults of the detector due to artificial damage improper use or authorized adjustment reconstruction or disassembly are not covered in the guarantee and we sha...

Reviews: