AC112Q-3, AC125Q-3, AC150Q-3, and AC165Q-3 Operations Manual.... 50
CONVERTER OUTPUT VOLTAGE CONTROL
Vout = XXX.X
More Less XXXV Exit
the data in this screen. When ready to leave, take down the kW-hours and run time before
disconnecting the shore power. Additionally, this screen can be used to diagnose converter
shutdowns. Since the Max. Level and Max. Power data are updated with slow-response metering
(approximately 1 second), only average use data are represented. Instantaneous motor-start
surges and such will not be represented by the data. If the Max. Level exceeds 110%, and a
shutdown of the Shore Power has occurred, it is very likely the average loading is exceeding the
converter's capacity. The Max. Power is provided since Max. Level is affected by Shore Cord
Setup settings.
7.8
CONVERTER OUTPUT VOLTAGE CONTROL
Press the
CONVERTER POWER + F5
buttons to access the CONVERTER OUTPUT VOLTAGE
CONTROL display.
This function allows the user to increase or decrease the converter output voltage (Vout). Press the
More
(F1)
button to increase the Vout, the Less
(F2)
button to decrease the Vout, the XXXV
(F3)
button to return Vout to the factory programmed setting, and the Exit
(F5)
button to save the setting
and exit.
Default
Range
Increments
Vout
factory prog. voltage +/-5%
0.5 volts
Application: if the line-drop losses in a yacht are such that locations remote of the converter and
Ship's Bus experience undesirable, lower-than-expected voltages, the programmed Vout can be
raised up to 5% via this function. Also, to decrease total power usage, the Vout could be reduced
up to 5%. The new, programmed Vout will be used as the basis for AGC, Seamless Transfer, and
all other voltage dependent functions.
7.9
EVENT LOG