AC112Q-3, AC125Q-3, AC150Q-3, and AC165Q-3 Operations Manual.... 27
6.1
POWER TURN-ON PROCEDURE, cont.
The display will sequence to the SUMMARY DISPLAY indicating the converter’s operational
state. Both input and output (converter) should indicate OFFLINE at this time. Press the INFO
(13)
button to review the Shore Power state if desired. The INFO screen will either list the Shore
Power as ONLINE or give a reason for its being off if it was previously on. A press of the F3
(13)
button in the INFO screen will display the last known converter failure. Return to the SUMMARY
DISPLAY at any time by pressing the SYSTEM STATUS
(5)
button.
At this time both of the red LED indicators next to the OFF buttons
(10A & 11A)
should be lit. If
the system has been ordered with the Seamless Transfer option, and the generator is on-line, the
green LED
(12A)
to the left of the GENERATOR
(12)
button will be lit.
Press the SHORE POWER
(2)
display button. The display will indicate basic shore power
information: voltage, current, and kVA. Press the F2
(13)
button to view kW, Power Factor,
frequency, and form. Verify the displayed voltages indicate the expected voltages and frequency.
If not, do not proceed until contacting factory personnel. Additional SHORE POWER information
can be obtained by pressing the F3 and F4
(13)
buttons: peak currents and crest currents, percent
of system rating, and kVAR. Return to the primary screen by pressing the F1
(13)
button.
SUMMARY DISPLAY AC165 MASTER
INPUT: OFFLINE CONVERTER: OFFLINE
LOAD LEVEL: 0.0 % AUTO-RESTART: ON
INFO STATUS
INPUT #1 PHASE A-B PHASE B-C PHASE C-A
VOLTAGE: 400V 400V 400V
CURRENT: 0A 0A 0A
LOAD: 0.0 kVA 0.0 kVA 0.0 kVA