AC90SVHE-3 / AC100SVHE-3 Operations Manual....
11
4
SPECIFICATIONS, cont.
4.1
ELECTRICAL SPECIFICATIONS
,
cont.
4.1.2 Output Service, cont.
Table 1 - Output Current (Rated Continuous RMS)
Output Form
AC90SVHE-3
Output Current
AC100SVHE-3
Output Current
3Ø, 277/480V
RMS
108A
RMS
/Ø
120A
RMS
/Ø
3Ø, 254/440V
RMS
118A
RMS
/Ø
131A
RMS
/Ø
3Ø, 240/416V
RMS
125A
RMS
/Ø
139A
RMS
/Ø
3Ø, 230/400V
RMS
131A
RMS
/Ø
145A
RMS
/Ø
3Ø, 220/380V
RMS
136A
RMS
/Ø
156A
RMS
/Ø
3Ø, 127/220V
RMS
237A
RMS
/Ø
263A
RMS
/Ø
3Ø, 120/208V
RMS
250A
RMS
/Ø
278A
RMS
/Ø
4.1.3 Control, Metering, and Status
Input Power Control
Input Service Disconnect Switch, 2 pos.
Shore Power Control
Membrane Switch, Input ON/OFF Control
Ship’s Power Control
Membrane Switch, Output ON/OFF Control,
Converter Power Control
Generator/Shore Power Transfer Control
Shore Power Metering
Voltage, Current, Frequency, kVA, kW, %Load
Converter Power Metering
Voltage, Current, Frequency, kVA, kW, %Load
Generator Power Metering
Generator 1 & 2 Voltage, Frequency
(Optional) Current, kVA, kW, %Load
System Status
Operational status, Diagnostics, Software Calibration