116
Diagnostic Guidelines
By means of pressure reading:
Pressure
Data
Circuit
Too low
A
lit
tle
low
Normal
A little
high
Too high
Probable cause
High side
Low side
●
●
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
●
●
1. Poor compression / no compression (compressor
defective)
2. Reversing valve leaking.
High side
Low side
●
●
1. Undercharged with refrigerant.
2. Refrigerant
leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked / seized (heating).
High side
Low side
●
●
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
High side
Low side
●
●
1. Air intake temperature of indoor unit too high.
Summary of Contents for A5LCX 10 C
Page 15: ...13 MODEL A5CMX20E A5LCX20C A5CMX25E A5LCX25C MODEL A5CMX20ER A5LCX20CR ACMX25ER A5LCX25CR...
Page 16: ...14 MODEL A5CCX20C A5LCX20C A5CCX25C A5LCX25C MODEL A5CCX10C A5LCX10C A5CCX15C A5LCX15C...
Page 17: ...15 MODEL A5CCX20CR A5LCX20CR A5CCX25CR A5LCX25CR MODEL A5CCX10CR A5LCX10CR A5CCX15CR A5LCX15CR...
Page 20: ...18 Installation Installation Diagram...
Page 109: ...107 Indoor Unit MODEL A5WMX 20 25 G GR WITH IONIZER Outdoor Unit MODEL A5LCX 20 25 C CR...
Page 110: ...108 MODEL A5CKX 10 15C CR c w A5LCX 10 15 C CR...
Page 111: ...109 MODEL A5CKX 20C CR c w A5LCX 20C CR...
Page 112: ...110 MODEL A5CKX 20 25A AR c w A5LCX 20 25C CR...
Page 113: ...111 MODEL A5CMX 20 25E ER c w A5LCX 20 25C CR...
Page 114: ...112 MODEL A5CCX 10 15C CR c w A5LCX 10 15C CR...
Page 115: ...113 MODEL A5CCX 20 25C CR c w A5LCX 20 25C CR...
Page 127: ...125 MODEL A5CKX 20 25A AR...
Page 129: ...127 MODEL A5CKX 10 15 20C CR...
Page 131: ...129 MODEL A5CMX 15 20 25E ER...