background image

Ascon Tecnologic - Y39 Line - Operating Instructions - Pag. 7

disabled.  In this mode, the 

Aux

 output can be turned 

OFF automatically after a certain time that can be set ON 
the parameter o

.tu

.  With 

o.tu

 = 

oF

 the output is activated 

and deactivated only manually, using a key  ,  , or via 
the digital input.  Differently, the output, once activated, is 
turned OFF automatically after the 

otu

 time.  This mode 

of operation can be used as a control of the shop window 
lighting, anti-fogging resistors or other utilities.

3. 

Light output managed by Active Set Point (“

eco

”  function).   

This output will be ON in “

Normal

” mode (Set Point 

SP

 

active) and OFF in economy (eco) mode operation (Set 
Point 

SP2

 active).

4. 

Internal Light output managed by digital input.  The output 
will be ON when door is opened (

i.Fi

5

6

).

The internal buzzer (when present) can be configured by 
parameter 

o.bu

 to carry out the following functions:

oF

 

Buzzer always disabled;

The Buzzer sounds when an alarm is active;

The Buzzer sounds when a key pressed (no alarm);

The Buzzer sounds when a key pressed and when an 
alarm is active.

5.5 

Active Set Point Selection

The instrument allows up to 2 different Set Points to be pre-set 
(

SP

 and 

SP2

) and then choose which one is to be made Active.

This function can be used if it is necessary to switch be-
tween two different temperatures (e.g. day and night or posi-
tive and negative etc).  The Active Set Point can be selected:

 

Using the parameter 

S.SA

;

 

Using the key  /  (parameter 

t.UF

 = 

3

;

 

Using the key  /

Aux

 (parameter 

t.Fb

 = 

3

);

 

Using the Digital Input (parameter 

i.Fi

 = 

8

 or 

11

).

The selection of the Active Set point can be combined also 
with the Switch OFF Auxiliary output function if used as light 
(

o.Fo

 = 

3

) and to change between Heating/Cooling action via 

the digital input (

i.Fi

 = 

11

).

SP

 and 

SP2

 can be set to a value between the values pro-

grammed with parameters 

S.LS

 and 

S.HS

.

Note: 

In the examples that follow, the Set point is generally 
indicated as

 SP

, but the instrument will work accord-

ing to the Set point selected as active.

5.6 

Temperature Control

The instrument control is ON/OFF and acts ON the output 
configured as 

ot

 depending on the measure of probe 

Pr1

the active Set Point (

SP

 or 

SP2

), the differential (hysteresis) 

r.d

 and the action 

r.HC

.

Depending ON the function mode programmed with param-
eter 

r.HC

 the differential is automatically considered by the 

controller with 

positive

 values for 

Cooling

 actions (

r.HC

 = 

C

or with 

negative

 values for 

Heating

 actions (

r.HC

 = 

H

).

r.HC

 = 

C

OUT

ot

SP

Temp. 

r.d

time

r.HC

 = 

H

off

off

SP

r.d

ON

ON

ON

OUT

ot

off

off

ON

ON

ON

time

Pr1

Temp. 

Pr1

In the event of probe error, it is possible to set the instrument 
so that the output continues working in cycles according to 
the times programmed with parameters 

r.t1

 (activation time) 

and 

r.t2

 (deactivation time).

If a probe error occurs, the instrument activates the output 

for the 

r.t1

 time, then deactivates it for the 

r.t2

 time and so 

on whilst the error remains.
Programming 

r.t1

 = 

oF

 the output, in probe error condition, 

remains switched OFF.
Programming instead 

r.t1

 to any value and 

r.t2

 = 

oF

 the 

output, in probe error condition, remains switched ON.
The instrument has a continuous cycle function through 
which is possible to mantain active the 

ot

 control output for 

the time set at parameter 

r.tC

, regardless the temperature 

controller command.
The function can be used, for example, when a rapid tem-
perature drop of the product is required after the refrigerator 
has been loaded.
It should be noted that during the continuous cycle defrosts 
are inhibited and the temperature alarms are disabled 
throughout the whole cycle and also subsequently for the 
time set at parameter 

A.dA

.

The start of a continuous cycle can only take place through a 
manual command using the  /  or  /

Aux

 keys (

t.UF

 or 

t.Fb

 

2

) or via the digital input (

i.Fi

 = 

3

) if properly programmed.

The continuous cycle in progress is indicated on the display 
with the indication 

CC

 and can be stopped by further action 

(as for activation) on the button or on the digital input.
The continuous cycle function cannot be activated during 
defrosts and with 

r.tC

 = 

oF

.

Remember that the temperature control function can be 
conditioned by the “

Compressor Protection and output delay 

at power-on

”, “

Defrost

”, “

Door open

” and “

External alarm with 

outputs disable

” functions.

5.7 

Compressor Protection Function and 
Delay at Power-ON

The “

Compressor Protection

” function aims to avoid close 

compressor start ups controlled by the instrument in Cooling 
applications.
This function provides 

3

 time controls.  These control func-

tions manage the switching ON of the output configured as 

ot

 associated with the temperature control request.

The protection consists of preventing the output being 
enabled (switched ON) during the times set with parameters 

P.P1

P.P2

 and 

P.P3

 and therefore that any activation occurs 

only after all the times have elapsed.
First control (parameter 

P.P1

) foresees a delay to the 

ot

 out-

put activation (switching ON delay).

SP

Pr1

off

off

off

P.P1

off

ON

ON

ON

Temp. 

time

P.P1

P.P1

r.d

Out
ot

Second control (parameter 

P.P2

) inhibits the activation of 

ot

 

output by a time delay (

P.P2

) that starts when the output is 

turned OFF (delay after switching-OFF).

SP

Out

ot

off

off

off

ON

ON

time

P.P2

P.P2

r.d

P.P2

ON

Pr1

Temp. 

Summary of Contents for Y39

Page 1: ...rature probes and a digital input alterna tive to a temperature input in addition can be equipped with an internal buzzer that is the sound system for alarms The 3 outputs can be can all be configured for controlling the compressor or the temperature control device the defrosting device the evaporation fan or alternatively any of the previ ous functions using an auxiliary device or an alarm The 3 ...

Page 2: ...atus ON ON OFF OFF or inhibited flashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 2 PROGRAMMING 2 1 Fast Set Point Programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SP2 alternated to the programmed value To change it press the key to increase the value or to decrease it These keys increase or decr...

Page 3: ...e protected parameters Previous Parameter Next Parameter SET PARAMETER Increase Value Decrease Value 35 0 25 5 NOT Protected PARAMETERS NORMAL MODE Hold for 2 s Hold for 5 s PARAMETERS PROGRAM MODE INS CORRECT PASSWORD Increase Value Decrease Value 0 R P PASSWORD REQUEST S LS a HA 2 5 Reset Parameters to Default Value The instrument allows the reset of the parameters to those values programmed in ...

Page 4: ...er must ensure that EMC rules are respected also after instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical Mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Make a hole 71 x 29 mm and insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree use the screw t...

Page 5: ...nction and the display is turned OFF except for the Stand by LED The transition between Standby and ON status is equivalent to power ON the instrument providing the electrical power In case of power failure the system always sets itself in the condition it was in before the black out The ON Stand by function can be selected Pressing the key for at least 1 s if t UF 4 Pressing the key Aux for at le...

Page 6: ...after the i ti time all the control outputs are disabled the alarm is activated and the instrument alternately shows ON the display the label AL and the variable set at para meter i dS 10 Instrument Switch ON OFF ON Stand by of instrument via NO contact closing the digital input and after the i ti time the instrument is switched ON while it is placed in Stand by when the digital input is open 11 A...

Page 7: ...OUT ot off off ON ON ON time Pr1 Temp Pr1 In the event of probe error it is possible to set the instrument so that the output continues working in cycles according to the times programmed with parameters r t1 activation time and r t2 deactivation time If a probe error occurs the instrument activates the output for the r t1 time then deactivates it for the r t2 time and so on whilst the error remai...

Page 8: ...nterval and automatic defrost start modes are set with parameter d dC rt At real time power ON intervals d di interval is count ed referring to the total time the instrument is switched ON Mode currently used in the refrigerators systems ct At time intervals of the compressor operation output ot switched ON Mode typically used in the posi tive temperature refrigerators systems with defrost by stop...

Page 9: ... A ends because the d tE temperature has been reached defrost B ends when d dE time has elapsed as temperature d tE has NOT been reached defrost C does not take place as the evaporator temperature is higher than d tS d tE d ts dF off off off off d di dSd ON ON ON time d di Defrost d de 1 Temp EP Example of electric defrost with evaporator temperature control The defrost ends when d dE time has ela...

Page 10: ...ion similar to AL but with inverse logic function output active in normal conditions disabled in alarm n Function is similar to An but with inverse logic function output active in normal conditions disabled in alarm The instrument is equipped with the alarm memory function which can be activated via the A tA parameter A tA values are oF The instrument disables the alarm signal when the alarm statu...

Page 11: ...t is possible to enable disable the auxiliary output if configured as o Fo 2 2 Pressing the key for at least 1 s it is possible to enable disable a continuous cycle 3 Pressing the key for at least 1 s it is possible to select one of the 2 stored Set Point in rotation Once the selection has been made the display shows flashing the active Set Point code for about 1 s SP SP2 4 Pressing the key for at...

Page 12: ...upplied by the instrument Supply TLCNV Cable 7 8 9 6 5 4 ON TX RX TTL TLCNV B GND A RS 485 3 2 1 For additional info please consult the TLCNV instruction manual 7 PROGRAMMABLE PARAMETERS TABLE Here below is a description of all the parameters available on the instrument Some of them may not be present because depend on the model type of instrument S Set Point parameters Parameter Description Range...

Page 13: ...essor output conditioning Et Electrical heating with evaporator temperature control EL 24 d di Defrosting interval oF 0 01 9 59 h min 99 5 h min x 10 6 00 25 d Sd 1st defrost delay at power oF Defrost at power on 0 01 9 59 h min 99 5 h min x 10 6 00 26 d dE Length max of defrost cycle oF 0 01 9 59 min s 99 5 min s x 10 20 0 27 d tE Defrost stop temperature 99 9 999 C F 8 0 28 d tS Defrost enable t...

Page 14: ... and continuous cycle and unlock display delay after defrost oF 0 01 9 59 h min 99 5 h min x 10 1 00 52 A oA Alarm delay with door open oF 0 01 9 59 min s 99 5 min s x 10 3 00 o Outputs and buzzer configuration parameters Parameter Description Range Default 53 o o1 OUT1 function oF No function ot Temp Control compressor dF Defrosting Fn Fan Au Auxiliary At Silenceable alarm AL Not silenceable Alar...

Page 15: ...be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50 60 Hz Power consumption 4 VA approx Input s 3 inputs for temperature probes PTC KTY 81 121 990W 25 C or NTC 103AT 2 10kW...

Page 16: ...e 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER MODEL Y39 Instrument with mechanical keyboard Y39S Instrument with Sensitive Touch keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT R Out1 Relay SPST NO 16A for resistive loads d OUT3 OUTPUT R Out3 Relay SPST NO 5A for resistive loads Not pre...

Reviews: