background image

Ascon Tecnologic - Y39 Line - Operating Instructions - Pag. 2

regulations, external alarm signals, activating a continuous 
cycle, and activating an auxiliary output etc..
The model Y39S have the “S-touch” capacitive sensor key-
board system.

1.2 

Front Panel Description

P

U

1
5

3
2

4

10

11

7

12

6
9

8

1. 

 

Key:

 Used to change the Set Point (press and release) 

and to program the function parameters (pressed for 5 s).   
In programming mode is used to enter in parameters edit 
mode and confirm the values.  In programming mode it 
can be used together with the   key to change the pro-
gramming level of the parameters.  When the keyboard is 
locked it can be used together with the   (hold pressed 
for 5 s) key to unlock the keyboard.

2. 

/Aux Key:

 In programming mode is used for decreas-

ing the values to be set and for selecting the parameters. 
Hold pressed for 1 s, while in normal mode, it can also be 
programmed via parameter 

t.Fb

 to carry out other func-

tions such as activating the 

Aux

 output, starting up the 

continuous cycle, etc. (see functions of keys   and  ).

3. 

/  Key:

 In normal mode can be used to start/stop a 

manual defrost (pressed for 5 s).  In programming mode 
is used to increase the value to be set and to select the 
parameters.  In programming mode can be used, to-
getherwith key   to change parameters level.  Pressed 
together with   key for 5 s allows the keyboard unlock.

4. 

/  Key:

 Press and release the key to display the 

instrument variables (measured temperatures etc.).  In 
programming mode press the key for 2 s to return in nor-
mal mode.  Hold pressed for 1 s, while in normal mode, it 
can also be programmed via parameter 

tuF

 to carry out 

other functions such as turn ON and OFF (stand-by) the 
device, activate the 

Aux

 output, start up the continuous 

cycle, etc. (see functions of keys   and  ).

5.  LED SET:

 During the normal operating mede, signals 

that a ket is pressed.  In programming mode indicates the 
programming level of the parameters.

6.  LED   - COOL:

 Indicates the output status (compres-

sor or temperature control device) when the istrument is 
programmed for cooling operation: ON (

ON

), OFF (

OFF

or inhibited (

flashing

).

7.  LED   - HEAT:

 Indicates the output status (compres-

sor or temperature control device) when the istrument is 
programmed for heating operation: ON (

ON

), OFF (

OFF

or inhibited (

flashing

).

8.  LED  :

 Indicates: Defrost in progress (

ON

) or drainage 

time in progress (

flashing

).

9.  LED  :

 hows the Fan output status: ON (

ON

), OFF 

(

OFF

) or inhibited (

flashing

).

10. LED  :

 Shows the Alarm status (

ON

), OFF (

OFF

) and 

Acknowledged or Lached (

flashing

)

11. LED Aux:

 Shows the Auxiliary output status: ON (

ON

), 

OFF (

OFF

) or inhibited (

flashing

).

12. LED Stand-By:

 When the instrument is in Stand-by 

mode is the only lit LED.

2  PROGRAMMING

2.1 

Fast Set Point Programming

The normal mode to program the setpoint is done by mo-
mentarily pressing the   key, the display shows 

SP

 (or 

SP2

alternated to the programmed value.
To change it press the   key to increase the value or   to 
decrease it.  These keys increase or decrease the value one 
digit at a time, but if the button is pressed for more than one 
second the value increases or decreases rapidly and, after 
two seconds, the speed increases even more in order to 
quickly reach the desired value.
When the desired value is set press the key   to exit the 
Set Point programming mode.  The Set Point programming 
mode can be abandoned by pressing the   key or automati-
cally if no key is pressed for 10 seconds.  After that time the 
display returns to the Normal function mode.

2.2 

Standard Mode Parameters Programming

To access the instrument function parameters when pass-
word protection is disabled, press the   key and keep it 
pressed for about 5 seconds, after which the display shows 
the code that identifies the first programmable parameter
The desired parameter can be selected using the  /

 keys, then, pressing the   key, the display shows the 

parameter code alternated to its value that can be changed 
with the   and   keys.
Once the desired value has been set, press the key again: 
the new value is stored and the display shows only the code 
of the selected parameter.
Pressing the   and   keys, it is possible to select another 
parameter and change it as described.
To exit the programming mode, press no keys for about 30 s, 
or keep the   key pressed for 2 s until the controller returns 
in normal mode.

PARAMETERS

(PROGRAM MODE)

SET PARAMETER

Previous

Parameter

Next

Parameter

Increase

Value

Decrease

Value

-30.0

s.ls

-25.5

NORMAL MODE

Hold

for 2 s

Hold 

for 5 s

2.3 

Parameter Protection Using a Password

The instrument has a parameter protection function with 
password that can be customized using the 

t.PP

 parameter.

To protect the parameters, set the desired Password Number 
in parameter 

tPP

.

When the protection is active, keep the   key pressed for 
about 5 s to access the parameters, the display shows 

r.p

.  

Press again the   key, the display changes to 

0

, now, using 

the  /  keys, insert the programmed password number 
and press the key   again.
If the password is correct the instrument displays the code of 
the first parameter and it will be possible to program the instru-
ment in the same way described in the previous paragraph.
The password protection can be disabled by setting 

t.PP

 = 

oF

.

Note: 

If the Password gets lost, just switch OFF and ON the 
instrument power supply, push   key during the initial 

Summary of Contents for Y39

Page 1: ...rature probes and a digital input alterna tive to a temperature input in addition can be equipped with an internal buzzer that is the sound system for alarms The 3 outputs can be can all be configured for controlling the compressor or the temperature control device the defrosting device the evaporation fan or alternatively any of the previ ous functions using an auxiliary device or an alarm The 3 ...

Page 2: ...atus ON ON OFF OFF or inhibited flashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 2 PROGRAMMING 2 1 Fast Set Point Programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SP2 alternated to the programmed value To change it press the key to increase the value or to decrease it These keys increase or decr...

Page 3: ...e protected parameters Previous Parameter Next Parameter SET PARAMETER Increase Value Decrease Value 35 0 25 5 NOT Protected PARAMETERS NORMAL MODE Hold for 2 s Hold for 5 s PARAMETERS PROGRAM MODE INS CORRECT PASSWORD Increase Value Decrease Value 0 R P PASSWORD REQUEST S LS a HA 2 5 Reset Parameters to Default Value The instrument allows the reset of the parameters to those values programmed in ...

Page 4: ...er must ensure that EMC rules are respected also after instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical Mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Make a hole 71 x 29 mm and insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree use the screw t...

Page 5: ...nction and the display is turned OFF except for the Stand by LED The transition between Standby and ON status is equivalent to power ON the instrument providing the electrical power In case of power failure the system always sets itself in the condition it was in before the black out The ON Stand by function can be selected Pressing the key for at least 1 s if t UF 4 Pressing the key Aux for at le...

Page 6: ...after the i ti time all the control outputs are disabled the alarm is activated and the instrument alternately shows ON the display the label AL and the variable set at para meter i dS 10 Instrument Switch ON OFF ON Stand by of instrument via NO contact closing the digital input and after the i ti time the instrument is switched ON while it is placed in Stand by when the digital input is open 11 A...

Page 7: ...OUT ot off off ON ON ON time Pr1 Temp Pr1 In the event of probe error it is possible to set the instrument so that the output continues working in cycles according to the times programmed with parameters r t1 activation time and r t2 deactivation time If a probe error occurs the instrument activates the output for the r t1 time then deactivates it for the r t2 time and so on whilst the error remai...

Page 8: ...nterval and automatic defrost start modes are set with parameter d dC rt At real time power ON intervals d di interval is count ed referring to the total time the instrument is switched ON Mode currently used in the refrigerators systems ct At time intervals of the compressor operation output ot switched ON Mode typically used in the posi tive temperature refrigerators systems with defrost by stop...

Page 9: ... A ends because the d tE temperature has been reached defrost B ends when d dE time has elapsed as temperature d tE has NOT been reached defrost C does not take place as the evaporator temperature is higher than d tS d tE d ts dF off off off off d di dSd ON ON ON time d di Defrost d de 1 Temp EP Example of electric defrost with evaporator temperature control The defrost ends when d dE time has ela...

Page 10: ...ion similar to AL but with inverse logic function output active in normal conditions disabled in alarm n Function is similar to An but with inverse logic function output active in normal conditions disabled in alarm The instrument is equipped with the alarm memory function which can be activated via the A tA parameter A tA values are oF The instrument disables the alarm signal when the alarm statu...

Page 11: ...t is possible to enable disable the auxiliary output if configured as o Fo 2 2 Pressing the key for at least 1 s it is possible to enable disable a continuous cycle 3 Pressing the key for at least 1 s it is possible to select one of the 2 stored Set Point in rotation Once the selection has been made the display shows flashing the active Set Point code for about 1 s SP SP2 4 Pressing the key for at...

Page 12: ...upplied by the instrument Supply TLCNV Cable 7 8 9 6 5 4 ON TX RX TTL TLCNV B GND A RS 485 3 2 1 For additional info please consult the TLCNV instruction manual 7 PROGRAMMABLE PARAMETERS TABLE Here below is a description of all the parameters available on the instrument Some of them may not be present because depend on the model type of instrument S Set Point parameters Parameter Description Range...

Page 13: ...essor output conditioning Et Electrical heating with evaporator temperature control EL 24 d di Defrosting interval oF 0 01 9 59 h min 99 5 h min x 10 6 00 25 d Sd 1st defrost delay at power oF Defrost at power on 0 01 9 59 h min 99 5 h min x 10 6 00 26 d dE Length max of defrost cycle oF 0 01 9 59 min s 99 5 min s x 10 20 0 27 d tE Defrost stop temperature 99 9 999 C F 8 0 28 d tS Defrost enable t...

Page 14: ... and continuous cycle and unlock display delay after defrost oF 0 01 9 59 h min 99 5 h min x 10 1 00 52 A oA Alarm delay with door open oF 0 01 9 59 min s 99 5 min s x 10 3 00 o Outputs and buzzer configuration parameters Parameter Description Range Default 53 o o1 OUT1 function oF No function ot Temp Control compressor dF Defrosting Fn Fan Au Auxiliary At Silenceable alarm AL Not silenceable Alar...

Page 15: ...be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50 60 Hz Power consumption 4 VA approx Input s 3 inputs for temperature probes PTC KTY 81 121 990W 25 C or NTC 103AT 2 10kW...

Page 16: ...e 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER MODEL Y39 Instrument with mechanical keyboard Y39S Instrument with Sensitive Touch keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT R Out1 Relay SPST NO 16A for resistive loads d OUT3 OUTPUT R Out3 Relay SPST NO 5A for resistive loads Not pre...

Reviews: