Ascon Tecnologic - KM1E/KR1E - Wine - ENGINEERING MANUAL -
PAG. 9
[11] di.A - Digital Inputs Action
Available:
Always.
Range: 0
DI1 Direct action, DI2 (if configured) Direct action;
1
DI1 Reverse action,
DI2 (if configured) Direct action;
2
DI1 Direct action,
DI2 (if configured) Reverse action;
3
DI1 Reverse action,
DI2 (if configured) Reverse action.
]
out Group - Output parameters
[12] o1.Ac - Out 1 action
Available:
When [14] o1F is different from
nonE
.
Range:
dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reversed LED indication;
rEU.r Reverse action with reversed LED indication.
Notes: 1.
Direct action: the output repeats the status of the
driven element.
e.g.: The output is an alarm output with direct
action. When the alarm changes to ON the relay
will be energized (logic output 1).
2.
Reverse action: the output status is the opposite
of the status of the driven element.
e.g.: The output is an alarm output with reverse
action. When the alarm changes to OFF, the relay
will be energized (logic output 1). This setting is
usually named “
fail-safe
” and it is generally used
in dangerous process in order to generate an
alarm when the instrument power supply goes
OFF or the internal watchdog starts.
[13] o2F - Out2 function
Available:
When the instrument has out 2 option and
[1] nodE is equal to 1.
Range:
nonE Output not used. With this setting the status
of this output can be driven directly from se-
rial link.
AL
Alarm output;
or.bo Out-of-range or burn out indicator;
P.FAL Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure indi-
cator;
St.By Standby status indicator;
on
Out2 always ON;
riSP
Inspection request.
[14] o2.AL - Alarms linked up with Out2
Available:
When [1] nodE is equal to 1 and [13] o2F = AL.
Range:
0... 15 with the following rule:
+1
Alarm 1;
+2
Alarm 2;
+4
Sensor break (burn out);
+8
Overload on Out4 (short circuit on the Out4).
[15] o2Ac - Out 2 action
Available:
When [1] nodE is equal to 1 and [13] o2F is dif-
ferent from
nonE
.
Range:
dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reverse LED indication;
rEU.r Reverse action with reverse LED indication.
[16] o3F - Out3 function
Available:
When the instrument has Out3 option.
Range:
nonE Output not used. With this setting the status
of this output can be driven directly from se-
rial link.
AL
Alarm output;
or.bo Out-of-range or burnout indicator;
P.FAL Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure indi-
cator;
St.By Standby status indicator;
on
Out3 always ON;
riSP
Inspection request.
[17] o3.AL - Alarms linked up with Out3
Available:
When [16] o3F = AL.
Range:
0... 15 with the following rule:
+1
Alarm 1;
+2
Alarm 2;
+4
Sensor break (burn out);
+8
Overload on Out4 (short circuit on the Out4).
[18] o3Ac - Out 3 action
Available:
When [16] o3F is different from
nonE
.
Range:
dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reverse LED indication;
rEU.r Reverse action with reverse LED indication.
[19] o4F - Out 4 function
Available:
When the [8] io4.F = Out4.
Range:
nonE Output not used. With this setting the status
of the this output can be driven directly from
serial link.
AL
Alarm output;
or.bo Out-of-range or burn out indicator;
P.FAL Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure indi-
cator;
St.By Standby status indicator.
[20] o4.AL - Alarms linked up with Out4
Available:
When [25] o4F = AL.
Range:
0... 15 with the following rule.
+1
Alarm 1;
+2
Alarm 2;
+4
Sensor break (burn out);
+8
Overload on Out4 (short circuit on the Out4).
This option only shows
ould
on the display.
[21] o4Ac - Out 4 action
Available:
When [8] Io4.F = Out4 and [19] o4F is different
from
nonE
.
Range:
dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with reverse LED indication;
rEU.r Reverse action with reverse LED indication.