2 digital inputs 

for

 free of voltage contacts

 (1 is on the P03 

display panel).  The 

4 outputs

 can be used to

 control the 

compressor

 or the 

temperature control device

, the 

de-

froster

, the 

evaporator fans

 and a 

configurable auxiliary 

device

 (Light, Alarm, etc.)

The 

3 temperature probe inputs

 can be used to 

control the 

cell temperature

, measure the 

evaporator temperature

and measure an 

auxiliary temperature

 (e.g. product tem-

perature, condenser temperature, etc.).

One digital input

 is always available on 

the control unit 

and, 

as an 

alternative

 to 

Pr2

 and 

Pr3

 temperature probe inputs, 

2 other digital inputs

 can be configured; the 

P03 display 

panel

 has an additional digital input.  

Digital inputs

 can be 

configured

 to 

execute various functions

 such as 

cell 

door signal

defrost commands

, the 

selection of a differ-

ent temperature-control set point

reporting an external 

alarm

, to 

activate a continuous cycle

, to 

activate the 

auxiliary output

, etc..

The sistem is also equipped with an 

alarm voltage function

 

that provides to 

disable the outputs

 if 

the mains

 voltage is 

too high

 or 

too low

.

The 

function selection

 and 

operating parameters pro-

gramming

 is done by the 

4 keys

 (mechanical or capacitive) 

present on the operator panel.
The 

connection between

 the 

B05B

 and the display panel 

P03CB/P34B

 is made via a 

thin three poles cable

 that also 

provides

 the 

power supply

 to the 

operator panel

.

1.2 

HMI Front Panel description

1.2.1 

P03CB Display Unit/Operator Panel

7

6

5

8

3
4

2

1

9

10

11

1.2.2 

P34B Display Unit/Operator Panel

P34B

P

U

trb

4

2

1

5

7

13

12

8

6

3

10

1. 

/ :

 Pressed for 1 s enables the 

ECO

 function or 

forces 

the instrument

 in 

Standby/Run status

 (the function 

selection is made with parameter 

UF

).  Pressing  /  

together with the  /  key for 5 s allows to enter in 
parameter programming mode.  Pressing  /  together 
with the   key for 5 s allows to display the instrument 
variables (measured temperatures etc.).  In programming 
mode  /  can be used to return in normal mode.

2. 

/ :

 Pressed and released is used to access the Set 

Point change function and modify the 

SP

 value.  In normal 

mode (pressed for 5 s) can be used to 

start/stop a manual 

defrost

.  In parameter programming or variables display 

mode is used for selecting the parameters and for increas-
ing the values to be set.  In programming mode, if pressed 
together with the  /  key allows to modify the param-
eters programming level.  When pressed together with the 

/  key for more than 5 s locks/unlocks the keyboard.

3. 

/  

turbo

:

 Pressed and released is used to access 

the Set Point change function and modify the 

SP

 value. 

Pressed for 5 s allows to 

enable/disable

 a 

turbo control 

mode cycle

.  In parameter programming or variables 

display mode is used for selecting the parameters and for 
decreasing the values to be set.

4. 

/ :

 Pressed for 1 s allows to 

manually enable/disable

 

the 

Output

 configured as “

Light

” (the function selection is 

made with parameter 

Fb

).  Pressing  /  together with 

the  /  key for 5 s allows to enter in parameter pro-
gramming mode.  In programming mode  /  is used 
to access parameter editing and value confirmation.  In 
programming mode, if pressed together with the 

/

 

key allows to modify the parameters programming level.  
When pressed together with the 

/

 key for more than 

5 s locks/unlocks the keyboard.

5.  LED SET:

 In normal mode shows when a key is pressed.  

In programming mode 

SET

 indicates the programming 

level of the parameters.

6.  LED 

: Indicates the output status (compressor or 

temperature control device) when the instrument is 
programmed for 

cooling/heating operation (cooling 

operation for P34)

ON

 (lit up), 

OFF

 (turned OFF) or 

inhibited

 (blinking).

7.  LED  :

 Indicates that the 

defrost

 is in 

progress

 (

ON

or 

drainage time in progress

 (blinking).

8.  LED 

: Indicates fan evaporator output status 

ON

 (on), 

OFF

 (off) or 

inhibited

 (blinking).

9.  LED 

:

 On the 

P03 

indicates that the 

ECO function 

is enabled

.  The 

P34

 shows the label 

Eco

 when in 

Eco

 

mode alternated to the normal display.

10. Decimal Point/Stand by:

 When the instrument is placed 

in Stand by mode, this is the only lighted LED.  During 
the normal operation is the decimal separator.

11. Engineering Unit LED:

 Displays the temperature meas-

urement unit in usage 

°C

/

°F

 (

P03 only

).

12. LED  :

 On the 

P34 

shows the 

Alarm status

 (

ON

), off 

(

OFF

) and Acknowledged or Lached (

blinking

).

13. LED  :

 On the 

P34 

indicates the output status (com-

pressor or temperature control device) when the instru-
ment is programmed for 

heating operation

ON

 (lit up), 

OFF

 (turned OFF) or 

inhibited

 (blinking).

Summary of Contents for B05B

Page 1: ...ng the temperature or continuous time compressor operating through stopping the compressor electric heating or hot gas cycle inversion The appliance has special defrosting optimisation func tions and...

Page 2: ...n be used to start stop a manual defrost In parameter programming or variables display mode is used for selecting the parameters and for increas ing the values to be set In programming mode if pressed...

Page 3: ...is possible to select which Set Point is to be set as active S1 S2 S3 Once selected the active Set Point press the key or wait 10 s after which the instrument makes the selected Set Point active and...

Page 4: ...pro tected if instead the SET LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and while keeping it pressed press also t...

Page 5: ...ut adequate protections The instrument used with NTC 103AT11 probe identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring t...

Page 6: ...igher than the maximum electricity current permitted As the instrument is built in equipment with permanent con nection inside housing it is not equipped with either switches or internal devices to pr...

Page 7: ...d With the key pressed for 1 s if UF 2 Using a Digital Input if parameter oF 7 where o is the number of the digital input o 1 4 for P03 or o 2 4 for P34 5 2 Normal Economic and Turbo operation The con...

Page 8: ...oods temperature recovery after which it returns to normal operation mode and so on Temp SE SP SH Hd Ed tt 2 tC tC time Normal Turbo Turbo Et 1 d Pr1 1 The Et time count is reset at each door opening...

Page 9: ...nstrument alternately displays the label AL and the variable set at parameter dS 6 Normal ECO mode selection with NO contact at digital input closure the instrument switches to the ECO mode operation...

Page 10: ...d the key pressed 5 6 Temperature control All parameters relative to the temperature control are con tained in the re group The instrument control is ON OFF and acts on the ot and HE outputs depending...

Page 11: ...urned ON last time delay between two switching ON off off off ON S1 Temp time d P3 P3 P3 ot output ON ON Pr1 During the output inhibition the LED of the control output blinks It is also possible to pr...

Page 12: ...rrectly set it is possible to avoid many non necessary defrosting cycles and therefore save energy that could instead happens in normal operation when to guar antee the system efficiency the interval...

Page 13: ...mperature has not reached the lock value or the SP d value or is elapsed the time set at parameter dA dL Lb Shows the label dF during the defrost cycle and Pd after the defrost until at the end of def...

Page 14: ...rms and their differentials 1d 2d With parameters 1y and 2y it is also possible to define whether the alarm thresholds 1H 2H 1L 2L are absolute or relative to the Set Point Depending on the desired op...

Page 15: ...to disable the control outputs when the main voltage is lower or higher than the values set at parameters LU Low voltage Alarm expressed in Volt x 10 HU High voltage Alarm expressed in Volt x 10 At th...

Page 16: ...remote display To the instrument it is possible to connect the remote display TVR Y through the special cable that can have a maximum length of 10 m The TVR Y device is directly supplied by the instru...

Page 17: ...C F 0 0 11 CU 280C Measure offset display only 30 0 30 0 C F 30 9 9 9 9 30 C F 0 0 12 P2 280D Probe Pr2 input function 0 oF 1 EP 2 Au 3 cd 4 r1 5 dG oF No function EP Evaporator Au Aux cd Condenser r1...

Page 18: ...oF 30 tE 2820 Defrost stop temperature 99 9 999 0 C F 99 9 9 9 9 10 99 C F 8 0 31 Ei 2821 Defrost interval for evaporator probe error 0 oF 0 01 99 59 h min oF No interval 01 59 min 01 99 h 6 32 EE 28...

Page 19: ...Description Range MODBUS R W Range display Default display Note 56 1y 283C Temperature alarms 1 Type 1 10 1 Pr1 absolute with label H L 2 Pr1 Relative with label H L 3 Au absolute with label H L 4 Au...

Page 20: ...Au Auxiliary At Silenceable alarm AL Not silenceable Alarm An Stored alarm t Silenceable alarm with inverse logic Output open in alarm L Not silenceable Alarm with inverse logic Output open in alarm n...

Page 21: ...SH and SE limits 2 Direct selection of Active Set Point between the 3 pre set Set Points S1 S2 and S3 using the keys 2 83 PP 285B Access Password to parameter functions 0 oF 1 99 oF No password 1 999...

Page 22: ...e shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Elec...

Page 23: ...ir S A 1 50 C 90 C with probe NTC 103AT11 11 INSTRUMENT ORDERING CODE 11 1 B05B Instrument Code MODEL B05B Controller a POWER SUPPLY H 100 230 VAC b OUTPUT 1 OUT 1 H Relay SPST NO 30A AC1 for resistiv...