Ascon Tecnologic - B05B - OPERATING INSTRUCTIONS - PAG. 16

6.  ACCESSORIES

The instrument is equipped with a 5-pin TTL communica-
tions port that allows the connection of some accessories 
described below.

6.1 

Parameters configuration by “A01”

Through the 5 poles TTL port it is possible to transfer from 
and toward the instrument the functioning parameters to the 

A01

 device.

This device it is mainly usable for the serial programming of 
some instruments which need to have the same parameters 
configuration or to keep a copy of the parameters setting of an 
instrument and allow its rapid retransmission.
The same device allows to connect a PC via USB with which, 
through the appropriate configuration software for “

AT Univer-

salConfig

”, the operating parameters can be configured.

To use the device 

A01

 it is necessary that the device or instru-

ment are being supplied directly or through the key.

AC supply

Supply adapter

12 VDC

Enter

PWS

12 V

A B C 

TTL

+

-

USB

to PC

USB

AC Supply

Enter

PWS

12 V

A B C 

TTL

+

-

USB

to PC

USB

For additional info, please have a look at the 

A01

 instruction 

manual.

6.2 

TVR Y remote display

To the instrument it is possible to connect the remote display 

TVR Y

 through the special cable that can have a maximum 

length of 10 m.  The 

TVR Y

 device is directly supplied by the 

instrument, it allows to show the temperature measured by 
the 

Pr1

 probe through a 2½ digit display.

For additional info, please have a look at the 

TVR Y

 instruc-

tion manual.

TVR Y (--)

cable length 10 m max.

TVRY

6.3 

ARS1 Serial Interface

Through the 

ARS1

 device (TTL/RS485 interface) and the 

appropriate TTL cable is possible to connect the controller to 
a RS485 serial communication network to which other instru-
ments are connected (controller or PLC), typically managed 
by a personal computer used as plant supervisor. 
Using a personal computer it is possible to acquire all the 
function information and to program all the instruments con-
figuration parameters.  The software protocol adopted for the 
instruments is a MODBUS RTU type, widely used in several 
PLC and supervision programs available on the market.
If the instrument is used in a RS485 network, use the param-
eter 

AS

 to set the station Address.

Note: 

The baud-rate is fixed at 9600 baud.

ARS1 interface is directly supplied by the instrument.
For additional info, please have a look at the 

ARS1

 instruc-

tion manual.

cable CATTL I

D+

D-

RS485

ARS1

Summary of Contents for B05B

Page 1: ...ng the temperature or continuous time compressor operating through stopping the compressor electric heating or hot gas cycle inversion The appliance has special defrosting optimisation func tions and...

Page 2: ...n be used to start stop a manual defrost In parameter programming or variables display mode is used for selecting the parameters and for increas ing the values to be set In programming mode if pressed...

Page 3: ...is possible to select which Set Point is to be set as active S1 S2 S3 Once selected the active Set Point press the key or wait 10 s after which the instrument makes the selected Set Point active and...

Page 4: ...pro tected if instead the SET LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and while keeping it pressed press also t...

Page 5: ...ut adequate protections The instrument used with NTC 103AT11 probe identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring t...

Page 6: ...igher than the maximum electricity current permitted As the instrument is built in equipment with permanent con nection inside housing it is not equipped with either switches or internal devices to pr...

Page 7: ...d With the key pressed for 1 s if UF 2 Using a Digital Input if parameter oF 7 where o is the number of the digital input o 1 4 for P03 or o 2 4 for P34 5 2 Normal Economic and Turbo operation The con...

Page 8: ...oods temperature recovery after which it returns to normal operation mode and so on Temp SE SP SH Hd Ed tt 2 tC tC time Normal Turbo Turbo Et 1 d Pr1 1 The Et time count is reset at each door opening...

Page 9: ...nstrument alternately displays the label AL and the variable set at parameter dS 6 Normal ECO mode selection with NO contact at digital input closure the instrument switches to the ECO mode operation...

Page 10: ...d the key pressed 5 6 Temperature control All parameters relative to the temperature control are con tained in the re group The instrument control is ON OFF and acts on the ot and HE outputs depending...

Page 11: ...urned ON last time delay between two switching ON off off off ON S1 Temp time d P3 P3 P3 ot output ON ON Pr1 During the output inhibition the LED of the control output blinks It is also possible to pr...

Page 12: ...rrectly set it is possible to avoid many non necessary defrosting cycles and therefore save energy that could instead happens in normal operation when to guar antee the system efficiency the interval...

Page 13: ...mperature has not reached the lock value or the SP d value or is elapsed the time set at parameter dA dL Lb Shows the label dF during the defrost cycle and Pd after the defrost until at the end of def...

Page 14: ...rms and their differentials 1d 2d With parameters 1y and 2y it is also possible to define whether the alarm thresholds 1H 2H 1L 2L are absolute or relative to the Set Point Depending on the desired op...

Page 15: ...to disable the control outputs when the main voltage is lower or higher than the values set at parameters LU Low voltage Alarm expressed in Volt x 10 HU High voltage Alarm expressed in Volt x 10 At th...

Page 16: ...remote display To the instrument it is possible to connect the remote display TVR Y through the special cable that can have a maximum length of 10 m The TVR Y device is directly supplied by the instru...

Page 17: ...C F 0 0 11 CU 280C Measure offset display only 30 0 30 0 C F 30 9 9 9 9 30 C F 0 0 12 P2 280D Probe Pr2 input function 0 oF 1 EP 2 Au 3 cd 4 r1 5 dG oF No function EP Evaporator Au Aux cd Condenser r1...

Page 18: ...oF 30 tE 2820 Defrost stop temperature 99 9 999 0 C F 99 9 9 9 9 10 99 C F 8 0 31 Ei 2821 Defrost interval for evaporator probe error 0 oF 0 01 99 59 h min oF No interval 01 59 min 01 99 h 6 32 EE 28...

Page 19: ...Description Range MODBUS R W Range display Default display Note 56 1y 283C Temperature alarms 1 Type 1 10 1 Pr1 absolute with label H L 2 Pr1 Relative with label H L 3 Au absolute with label H L 4 Au...

Page 20: ...Au Auxiliary At Silenceable alarm AL Not silenceable Alarm An Stored alarm t Silenceable alarm with inverse logic Output open in alarm L Not silenceable Alarm with inverse logic Output open in alarm n...

Page 21: ...SH and SE limits 2 Direct selection of Active Set Point between the 3 pre set Set Points S1 S2 and S3 using the keys 2 83 PP 285B Access Password to parameter functions 0 oF 1 99 oF No password 1 999...

Page 22: ...e shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Elec...

Page 23: ...ir S A 1 50 C 90 C with probe NTC 103AT11 11 INSTRUMENT ORDERING CODE 11 1 B05B Instrument Code MODEL B05B Controller a POWER SUPPLY H 100 230 VAC b OUTPUT 1 OUT 1 H Relay SPST NO 30A AC1 for resistiv...