Asco 920 Installation Manual Download Page 4

OPTIONAL ACCESSORIES

3

Pilot Lights, Optional Accessory 9

These pilot lights, if furnished, are connected and
installed in the enclosure door, or are supplied loose for
open type switches. Each neon light requires a 1/2”
diameter round hole and can be installed in panels up to
0. 1” thick. See the Wiring Diagram. Acc. 9s can be
added later in Kit form. Kit voltage must be the same as
RC Switch control voltage (coil).

Acc. 9A

light comes on when main contacts are closed.

Acc. 9B

light comes on when main contacts are open.

A resistor is used for 208–277 V RC control. It is supplied
on a terminal block with connections labeled 1, 2.

Acc.

Description

Kit

9A

110–120 V

333270–006

9A

208–277 V

333270–007

9B

110–120 V

333271–006

9B

208–277 V

333271–007

Auxiliary Contacts, Optional Accessory 14

Acc. 14 auxiliary contacts are installed on the right side of
the ASCO 920. Terminals accept wire size #14 AWG Cu.

Acc.

Description

Kit

14A

14B

two auxiliary contacts (14A & 14B)

with bracket, cam, and screws

607039

Auxiliary Relays, Optional Acc. 47, 48, 49

Optional auxiliary relays (Acc. 47, 48, 49) are useful:
– When the control station is located at a distance great-
er than allowable ASCO 920 line run (Table A, page 1).
– When controlling device doesn’t have adequate cur-
rent–carrying capability to control RC (Table B, page 1).
– When the controlling device is a single–pole single–
throw contact, which requires a 2–wire control line.
– When Form 3 (start–stop) control is required.
The relays have a low VA burden: Acc. 47 has 3.0 VA for
ac, 2.5 watts for dc; Acc. 48 & 49 have 2.0 VA for ac, 1.2
watts for dc. Acc. 47 & 48 terminals accept wire sizes
#22–12 AWG Cu; Acc. 49 accepts #18–12 AWG Cu.
The relays are mounted and wired to the RC on enclosed
switches, or supplied loose with open type switches.

Two–Wire Control, Optional Accessory 47

Acc. 47 is an auxiliary relay panel for 2–wire control of
the ASCO 920, The relay panel must be energized to
close the ASCO 920 contacts, and de–energized to open
the ASCO 920 contacts. Therefore, use a single–pole,
maintained–type control station (Acc. 53B or 53C).
Order

Catalog 32lA40

and specify relay coil voltage.

Three–Wire Control, Optional Accessory 48

Acc. 48 is an auxiliary relay panel for 3–wire control of
the ASCO 920. It has two relays. One relay must be
energized to open the ASCO 920 contracts; the other
relay must be energized to close the ASCO 920 contacts.
Therefore, use a single–pole, double–throw, momentary–

type control station (Acc. 53A). Order

Catalog 321A36

and specify relay coil voltage. See the Wiring Diagram.

Form 3 Control, Optional Accessory 49

Acc. 49 is an auxiliary relay for Form 3 control of the
ASCO 920. This relay must be energized to close the
ASCO 920 contacts; the relay must be de–energized to
open the ASCO 920 contacts. Therefore, use one
normally open and one normally closed separate control
stations (Acc. 53D). Order a mounting socket kit and
plug---in relay listed below (specify relay control voltage).

Acc.

Description

Kit

49

mounting socket kit

295855

Acc.

AC

Control

Relay

Acc.

DC

Control

Relay

49A

24 V

115206 49F

12 V

115274

49B

120 V

115201 49G

24 V

115277

49C

208 V

115210 49H

32 V

115279

49D

240 V

115202 49I

48 V

115283

49E

277 V

115213 49J

110 V

115271

Control Line Fuses, Optional Accessory 52

These control line fuses are mounted for enclosed
switches, or are supplied loose for open type switches.
Fuse block has #10–32 terminal screws. The cartridge
fuses are suitable for ac only as listed on

Wiring Diagram

.

Acc.

Description

Kit

52A

one 15 amp, 300 Vac type SC fuse

for 300 Vac max. grounded

333272

52B two 15 amp 300 Vac type SC fuses

for 300 Vac max. ungrounded

333273

52C two 15 amp 600 Vac type KTK fuses

for 301---600 Vac max. ungrounded 333274

Door–Mounted Controls, Optional Acc. 53

These manual controls are connected and mounted on
the enclosure door, or are supplied loose for open type
switches. See the

Composite Wiring Diagram

.

Acc.

Description

Kit

53A

momentary toggle switch

with center–off position

for 3–wire control

333275

53B

3–position selector switch (HOA)

used with Acc. 47

for 2–wire control

333276

53C

maintained toggle switch

used with Acc. 47

for 2–wire control

333277

53D

2 momentary toggle switches

(1 normally closed, 1 norm. open)

used with Acc. 49 for form 3 control

333278

Summary of Contents for 920

Page 1: ... or bus and control circuit wires An experienced licensed electrician should install the RC Switch Each ASCO 920 RC Switch has a ratings identification label defining load types and maximum voltage ratings Use the switch only within the limits shown on this label Do not exceed the values on the rating label Exceeding the rating can cause personal injury or serious equipment damage TABLE OF CONTENT...

Page 2: ...es and minimum wire sizes that can be run between a control station and one ASCO 920 switch Table A Line Run Min Wire Size Maximum Distance feet 1 for these AC Control Voltages Wire Size AWG 120 V 208 V 240 V 277 V 14 12 10 750 1200 2000 1650 2600 4200 2760 4300 6900 3950 6350 10000 1 For ambient temperatures to 40 C Do not exceed these distances for proper switch operation Line run can be extende...

Page 3: ...Station Make sure control stations do not have overlapping contacts RC Switch tries to open or close but cannot 1 Check Voltage Make sure control line voltage is at least 90 of nameplate coil voltage 2 Check Line Run Wire Size Make sure control line size and distance is within the requirements of Table A page 1 3 Check VA Burden of Transformer If a transform er is used in the control line make sur...

Page 4: ...ned type control station Acc 53B or 53C Order Catalog 32lA40 and specify relay coil voltage Three Wire Control Optional Accessory 48 Acc 48 is an auxiliary relay panel for 3 wire control of the ASCO 920 It has two relays One relay must be energized to open the ASCO 920 contracts the other relay must be energized to close the ASCO 920 contacts Therefore use a single pole double throw momentary type...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Reviews: