Asco 920 Installation Manual Download Page 3

2

MANUAL OPERATION

A means for manual operation is provided for mainte-
nance purposes only. The switch must be completely
de–energized. Open the supply source circuit breaker to
the ASCO 920. Label, tape, and disconnect the control
circuit wires from terminals

L

,

0

, and C.

Do manually operate the RC Switch until all

power sources (service & control) and all loads

are deenergized (open circuit breakers).

A slotted socket in the cover directly connects to the
solenoid operator mechanism. Use a medium blade
screwdriver to turn the socket 1/4 turn clockwise to
close or counterclockwise to open. See Figure 2 below.

insert screwdriver

turn clockwise to

close or counter-

clockwise to open

With all power OFF

Figure 2. Socket in nameplate for manual operation

ALL POWER MUST BE OFF BEFORE TURNING !

TROUBLESHOOTING

Note any Optional Accessories that may have been
furnished with the ASCO 920 and review their operation.

Deenergize all power sources to the Remote

Control Switch before working on it.

RC Switch opens and closes repeatedly

.

1.

Check Wiring.

Make sure control stations are not

calling on the ASCO 920 to open and to close at
the same time. See Wiring Diagram.

2.

Check Control Station.

Make sure control

stations do not have overlapping contacts.

RC Switch tries to open or close, but cannot

.

1.

Check Voltage.

Make sure control line voltage is

at least 90% of nameplate coil voltage.

2.

Check Line Run & Wire Size.

Make sure control

line size and distance is within the requirements of
Table A, page 1.

3.

Check VA Burden of Transformer.

If a transform-

er is used in the control line, make sure it can handle
the VA burden required. See Table B, page 1.

REPLACEMENT PARTS KITS

For convenience, replacement contacts and coils are
sold in kit form. Select kits by noting switch ampere
size, number of poles, and coil control voltage as
specified on the nameplate. The kits can be ordered
from any ASI, 1–800–800–ASCO. (2726).

For other parts, and service procedures, refer to Service
Bulletin 381339–015. This publication is supplied with the
kits. When converting to a control voltage different from
originally furnished, request a new nameplate.

Coil Kits

for these AC Control Voltages

110–120 V

208–240 V

265–277 V

440–480 V

605326–001

605326–008

605326–002

605326–003

ASCO 920

Contact Kits

Coil Control Contact Kit

Lubrication Kit

3

ASCO 920

amp. size

2 Pole

3 Pole

Coil Control Contact Kit

Lubrication Kit

3

30–100

331709

331703

331713

625549

150–225

331710

331704

331713

625549

3

Lubrication points: core and link inside the core tube, operator spring, and rotating weight pin.

Summary of Contents for 920

Page 1: ... or bus and control circuit wires An experienced licensed electrician should install the RC Switch Each ASCO 920 RC Switch has a ratings identification label defining load types and maximum voltage ratings Use the switch only within the limits shown on this label Do not exceed the values on the rating label Exceeding the rating can cause personal injury or serious equipment damage TABLE OF CONTENT...

Page 2: ...es and minimum wire sizes that can be run between a control station and one ASCO 920 switch Table A Line Run Min Wire Size Maximum Distance feet 1 for these AC Control Voltages Wire Size AWG 120 V 208 V 240 V 277 V 14 12 10 750 1200 2000 1650 2600 4200 2760 4300 6900 3950 6350 10000 1 For ambient temperatures to 40 C Do not exceed these distances for proper switch operation Line run can be extende...

Page 3: ...Station Make sure control stations do not have overlapping contacts RC Switch tries to open or close but cannot 1 Check Voltage Make sure control line voltage is at least 90 of nameplate coil voltage 2 Check Line Run Wire Size Make sure control line size and distance is within the requirements of Table A page 1 3 Check VA Burden of Transformer If a transform er is used in the control line make sur...

Page 4: ...ned type control station Acc 53B or 53C Order Catalog 32lA40 and specify relay coil voltage Three Wire Control Optional Accessory 48 Acc 48 is an auxiliary relay panel for 3 wire control of the ASCO 920 It has two relays One relay must be energized to open the ASCO 920 contracts the other relay must be energized to close the ASCO 920 contacts Therefore use a single pole double throw momentary type...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Reviews: